ART C KLEIN CONSTRUCTION, INC. | B= | C | 06/19/2013 | All other required Final inspections are complete. (This is a computer generated result) | JOHNP | JOHNP | | B= | C | 4545704 |
ART C KLEIN CONSTRUCTION, INC. | B= | P | 02/07/2013 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-5982, x2). All other required Final inspections are complete. (This is a computer generated result) | JOHNP | JOHNP | | B= | P | 4468791 |
ART C KLEIN CONSTRUCTION, INC. | B= | P | 02/05/2013 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-5982, x2), HVAC SOLUTIONS, INC. Mechanical Final Inspection is not Completed yet. Need Mechanical & Fire finals | JOHNP | JOHNP | | B= | P | 4466820 |
ART C KLEIN CONSTRUCTION, INC. | BFR | P | 01/24/2013 | North & West security ramp walls OK | JOHNP | JOHNP | | BFR | P | 4460124 |
ART C KLEIN CONSTRUCTION, INC. | BFR | P | 12/28/2012 | Walls & bulkhead at ramp area OK | JOHNP | JOHNP | | BFR | P | 4446491 |
ART C KLEIN CONSTRUCTION, INC. | BFN | P | 12/20/2012 | Slab reinforcement OK | JOHNP | JOHNP | | BFN | P | 4443964 |
ART C KLEIN CONSTRUCTION, INC. | BFR | P | 12/17/2012 | Ramp OK, need rebar for slab inspected | JOHNP | JOHNP | | BFR | P | 4441505 |
FOSTER ELECTRIC CORPORATION | E= | C | 01/17/2013 | | TIMA | TIMA | | E= | C | 4455862 |
FOSTER ELECTRIC CORPORATION | ER | P | 01/10/2013 | Drop ceiling in the corridor, Phase 2. | JOSEPH | JOSEPH | | ER | P | 4452199 |
FOSTER ELECTRIC CORPORATION | ER | P | 12/27/2012 | WALLS OK PHASE 2 | TIMA | TIMA | | ER | P | 4445807 |
HVAC SOLUTIONS, INC. | H= | C | 02/07/2013 | REVISED TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 4468790 |
HVAC SOLUTIONS, INC. | H= | P | 02/05/2013 | MECHANICAL FINAL OK PENDING RECEIPT OF REVISED TEST AND BALANCE REPORT. SUPPLY/RETURN IN CLOSET OK. | NANCY | NANCY | | H= | P | 4466591 |
HVAC SOLUTIONS, INC. | H= | P | 01/24/2013 | TEST AND BALANCE REPORT RECEIVED. 6 INCH SUPPLY WITH 45 CFM IS NOT ON REPORT. IF THAT DIFFUSER HAS BEEN DELETED WILL NEED REVISED/APPROVED PRINTS. | NANCY | NANCY | | H= | P | 4459669 |
HVAC SOLUTIONS, INC. | H= | P | 01/16/2013 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4455073 |
HVAC SOLUTIONS, INC. | HD | C | 01/11/2013 | ABOVE CEILING ALL OK, OK TO COVER PER MECHANICAL ONLY. | NANCY | NANCY | | HD | C | 4452935 |
HVAC SOLUTIONS, INC. | HD | P | 01/07/2013 | NON-STERILE SIDE: SUPPLY AIR TRUNK AND LATERALS OK, OK TO WRAP LATERALS. STERILE SIDE: MEDIUM PRESSURE ROUND DUCT AND SQUARE TO ROUND OK, OK TO WRAP. | NANCY | NANCY | | HD | P | 4449680 |
FRONTIER MECHANICAL SYSTEMS INC | HWP | P | 12/28/2012 | WRONG PERMIT, INSPECTION WAS SUPPOSED TO BE CALLED IN FOR PERMIT I48708. | NANCY | NANCY | | HWP | P | 4446485 |
HVAC SOLUTIONS, INC. | HD | P | 12/17/2012 | NON-STERILE SIDE: MEDIUM PRESSURE DUCT UNDER FLOOR OK, OK TO COVER. BY FINAL NEED ACCESS DOOR FOR FIRE/SMOKE DAMPER UNDER FLOOR. 16 INCH ROUND ABOVE CEILING OK TO WRAP. STERILE SIDE: MEDIUM PRESSURE RECTANGULAR DUCT IN CHASE AND CEILING OK, OK TO COVER. SQUARE TO ROUND OK, OK TO WRAP. | NANCY | NANCY | | HD | P | 4441137 |