GC LUXURY HOMES, LLC | B= | C | 04/12/2013 | | DANF | DANF | | B= | C | 4505410 |
GC LUXURY HOMES, LLC | B= | R | 04/10/2013 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-5982, x2), External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: enijkamp@springsgov.com or 385-5977). need to put back drywall at ceiling in garage / need to seal all exterior penetrations / unfinished basement | JOND | JOND | | B= | R | 4503368 |
GC LUXURY HOMES, LLC | BIN | C | 02/28/2013 | | JIMP | JIMP | | BIN | C | 4479366 |
GC LUXURY HOMES, LLC | BFR | C | 02/28/2013 | | JIMP | JIMP | | BFR | C | 4479364 |
GC LUXURY HOMES, LLC | BFR | R | 02/26/2013 | plan calls for 4-2x6 interior AG; header rear wall not per plan; truss B1S missing laterial bracing; strap plumbing at bearing walls; fasten insulation used as firestop | JIMP | JIMP | | BFR | R | 4477585 |
GC LUXURY HOMES, LLC | BFR | T | 02/25/2013 | PAID (REC#1113271): no plans at 10:12 | JIMP | JIMP | | BFR | T | 4477065 |
GC LUXURY HOMES, LLC | BFD | C | 01/08/2013 | drain usable space; isolate pads; float walls; 5% grade at final; eufer ground installe | JIMP | JIMP | | BFD | C | 4450716 |
GC LUXURY HOMES, LLC | BFN | C | 01/08/2013 | engineers observation on file | JIMP | JIMP | | BFN | C | 4450712 |
GC LUXURY HOMES, LLC | BFT | C | 01/08/2013 | engineers observation on file | JIMP | JIMP | | BFT | C | 4450708 |
RON COVINGTON HOMES LLC | BFN | P | 12/19/2012 | AUTHORIZED INSPECTION BY ENGINEER | BPHILLIPS | BPHILLIPS | BPHILLIPS | BFN | P | 4443024 |
RON COVINGTON HOMES LLC | BFT | P | 12/19/2012 | AUTHORIZED INSPECTION BY ENGINEER | BPHILLIPS | BPHILLIPS | BPHILLIPS | BFT | P | 4443023 |
BLUE MOUNTAIN ELECTRIC, INC. | E= | C | 04/05/2013 | A.C PREWIRE | MIKEC | MIKEC | | E= | C | 4501160 |
BLUE MOUNTAIN ELECTRIC, INC. | ES | C | 02/26/2013 | Residential Underground: 150 AMP 3/W NEW RES. | TIMA | TIMA | | ES | C | 4477432 |
BLUE MOUNTAIN ELECTRIC, INC. | ES | R | 02/20/2013 | NEED WATER GEC,SPARE CIRCUITS FOR BASEMENT? | TIMA | TIMA | | ES | R | 4475160 |
BLUE MOUNTAIN ELECTRIC, INC. | ER | C | 02/20/2013 | 1-20 #6AL #6AL ALSO FOR FUTURE SUB PANEL---UNFINISHED BASEMENT---- | TIMA | TIMA | | ER | C | 4475159 |
CLANTON HEATING & AIR, INC. | H= | C | 04/04/2013 | No mantel, a/c rough(lineset only). | MICHAELS | MICHAELS | | H= | C | 4499947 |
CLANTON HEATING & AIR, INC. | HC | C | 02/22/2013 | RELEASE METER | MICHAELS | MICHAELS | | HC | C | 4475629 |
CLANTON HEATING & AIR, INC. | HRR | C | 02/22/2013 | Duct design and equipment ok. Note: UB, NO osa, NO a/c, 8" round from outside to mech for combustion air. | MICHAELS | MICHAELS | | HRR | C | 4475628 |
BURNS RITE GAS | HI | C | 02/20/2013 | 10# test ok. 1" main to furn, w/h, fp. | MICHAELS | MICHAELS | | HI | C | 4475040 |
CLANTON HEATING & AIR, INC. | HRR | R | 02/19/2013 | Upstairs R/A is pushed inside wall, insulation shield is not tall enough, b-vent lacks clearance at top plate below attic, b-vent disconnected in basement, stopped inspection. Re-inspect all. | MICHAELS | MICHAELS | | HRR | R | 4473730 |
BURNS RITE GAS | HI | P | 02/19/2013 | No test (gauge is damaged). | MICHAELS | MICHAELS | | HI | P | 4473729 |
C & T PLUMBING, LLC. | P= | C | 04/04/2013 | NO CARD | LEE | LEE | | P= | C | 4500594 |
C & T PLUMBING, LLC. | PTO | C | 02/20/2013 | | LEE | LEE | | PTO | C | 4475303 |
C & T PLUMBING, LLC. | PTO | R | 02/19/2013 | KITCHEN GAUGE ON ZERO -- 2ND TRIP -- REINSP-FEE ?? | LEE | LEE | | PTO | R | 4474383 |
C & T PLUMBING, LLC. | PTO | P | 02/15/2013 | ONLY ALLOWED 9.5 W.F.U ON 3/4" -- PIPE 1" TO W/H LEG -- LOW TEST ON KITCHEN DWV | LEE | LEE | | PTO | P | 4473235 |
C & T PLUMBING, LLC. | PB | C | 01/16/2013 | 3/4" COPPER STUBBED UP AT WALL | LEE | LEE | | PB | C | 4455645 |