HOMEOWNER | B= | C | 12/17/2013 | | CHRISM | CHRISM | | B= | C | 4658027 |
HOMEOWNER | B= | P | 12/10/2013 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet. insulate floor joists above vault, unfinished basement -- Schedule a new Building Final when above items are complete. | CHRISM | CHRISM | | B= | P | 4654380 |
HOMEOWNER | BLA | C | 08/19/2013 | | CHRISM | CHRISM | | BLA | C | 4588256 |
HOMEOWNER | BLA | P | 08/16/2013 | ok all but around door on south wall | CHRISM | CHRISM | | BLA | P | 4587210 |
HOMEOWNER | BFR | C | 08/08/2013 | | CHRISM | CHRISM | | BFR | C | 4581350 |
HOMEOWNER | BIN | C | 08/08/2013 | | CHRISM | CHRISM | | BIN | C | 4581342 |
HOMEOWNER | BFR | R | 08/01/2013 | ok to insulate, missing laterals D2-3-4-5-6, A12-13, H2,5s missing at entry and truss to girders in loft, roll block truss heals in loft, draftstop | CHRISM | CHRISM | | BFR | R | 4576617 |
HOMEOWNER | BIN | P | 07/31/2013 | Qualified third party energy inspection documentation must be presented at time of final building (B=) inspection | KENYATTA | KENYATTA | | BIN | P | 4575787 |
HOMEOWNER | BSP | T | 07/31/2013 | PAID (REC#1145480) PLAN SPLICE FEE: $50 by: MICHAEL for Construction: revise side porch framing | MICHAELA | MICHAELA | | BSP | T | 4575212 |
HOMEOWNER | BTR | C | 07/15/2013 | | CHRISM | CHRISM | | BTR | C | 4563484 |
HOMEOWNER | BSP | T | 03/28/2013 | PAID (REC#1119916) ADDITIONAL PLAN REVIEW TIME: $50 From: SHELLEY revised deck framing | SHELLEY | SHELLEY | | BSP | T | 4495960 |
HOMEOWNER | BSP | P | 03/22/2013 | rear deck piers ok / deck pier pad ok | JEREMYA | JEREMYA | | BSP | P | 4492068 |
HOMEOWNER | BFT | C | 01/31/2013 | rec'd copy of eng inspection report | BLAKE | BLAKE | | BFT | C | 4464792 |
HOMEOWNER | BFN | C | 01/31/2013 | received copy of eng inspection report, soils letter, open excavation letter, compaction test and fdtn design/ float any walls on slab/ 5% final grade req'd | BLAKE | BLAKE | | BFN | C | 4464791 |
HOMEOWNER | BFD | C | 01/31/2013 | | BLAKE | BLAKE | | BFD | C | 4464790 |
HOMEOWNER | BIN | P | 01/31/2013 | not a bin but a bfi which is ok | BLAKE | BLAKE | | BIN | P | 4464783 |
HOMEOWNER | BFN | P | 01/02/2013 | AUTHORIZED INSPECTION BY ENGINEER | BPHILLIPS | BPHILLIPS | BPHILLIPS | BFN | P | 4447424 |
HOMEOWNER | BFT | P | 01/02/2013 | AUTHORIZED INSPECTION BY ENGINEER | BPHILLIPS | BPHILLIPS | BPHILLIPS | BFT | P | 4447423 |
HOMERUN ELECTRONICS, INC. | E= | C | 11/26/2013 | | MATTHEW | MATTHEW | | E= | C | 4648604 |
HOMERUN ELECTRONICS, INC. | E= | R | 11/21/2013 | need rated lamps in showers---need gfci protection for tv in master bath not an outlet----patch around relocated outlets----strap mc cable in island---need gfci protection with in 6' of sink at wet bar---3-way for upstairs lights mot working----outlet not working to basement entrance from garage----need breaker locks for ovens-----need to protect NM cable in unfinished basement walls---- | BRIAN | BRIAN | | E= | R | 4646403 |
H&H ELECTRICAL SERVICE | ES | C | 07/30/2013 | Residential Underground: 200 amp 3/w: new res | MATTHEW | MATTHEW | | ES | C | 4574685 |
H&H ELECTRICAL SERVICE | ER | C | 07/30/2013 | basement exterior walls and bath to be finished, 1-20, sub-panel ok | MATTHEW | MATTHEW | | ER | C | 4574676 |
H&H ELECTRICAL SERVICE | ES | R | 07/26/2013 | need caution tape installed in non-forest area | MATTHEW | MATTHEW | | ES | R | 4572730 |
H&H ELECTRICAL SERVICE | ER | T | 07/26/2013 | PAID (REC#1145078) corrections not completed--------- I took a closer look at remodel cans above shower (not ic rated and needs connectors installed)--------------- complete re-inspect | MATTHEW | MATTHEW | | ER | T | 4572717 |
H&H ELECTRICAL SERVICE | ES | R | 07/23/2013 | see rough | MATTHEW | MATTHEW | | ES | R | 4569918 |
H&H ELECTRICAL SERVICE | ER | R | 07/23/2013 | complete re-inspect: install all can lights, non-ic cans need to be caged so no insulation can be in contact and 1/2" form combustibles, correct spacing on both sides of master slider, install fan box in sun room, ground all metal boxes, make up grounds at lights, add outlet on exterior at upstairs slider, verify spacing for kitchen countertop, land nm under sink, neutrals need to land on neutral bar in panel, caution tape needs to be installed over service conductors----- is basement complete? | MATTHEW | MATTHEW | | ER | R | 4569906 |
H&H ELECTRICAL SERVICE | EUG | C | 07/22/2013 | 2 service laterals--- 1 to new house and 1 to existing house--- the existing service to be removed at existing house | MATTHEW | MATTHEW | | EUG | C | 4568447 |
BROWN'S HEATING & COOLING, INC | H= | C | 12/06/2013 | Corrections made. | MICHAELS | MICHAELS | | H= | C | 4653522 |
BROWN'S HEATING & COOLING, INC | H= | P | 11/27/2013 | Need furnace termination on loft furnace, stucco in termination on north side. Note: mantels are non-combustible, UB, a/c rough(coil only) on main and loft. | MICHAELS | MICHAELS | | H= | P | 4649217 |
BROWN'S HEATING & COOLING, INC | HC | C | 07/31/2013 | RELEASE METER | MICHAELS | MICHAELS | | HC | C | 4575461 |
BROWN'S HEATING & COOLING, INC | HRR | C | 07/31/2013 | PARTIAL finish basement, duct design ok, 6" osa to main, a/c rough(coil and lineset on main and upper), direct vent furnace x3. | MICHAELS | MICHAELS | | HRR | C | 4575454 |
L & L GAS SHOP, LLC. | HO | C | 07/22/2013 | 10# test ok. 1 1/4" poly from meter at road to house. AT FINAL: need 2lb. letter, reg installed at existing structure from same meter. | MICHAELS | MICHAELS | | HO | C | 4568453 |
L & L GAS SHOP, LLC. | HI | C | 05/29/2013 | 10 LB TEST OK NOTE 3 FURN,2 W/H ,2 F/P,1 RANGE BBQ AND FUTURE FIRE RING | DAVIDH | DAVIDH | | HI | C | 4532518 |
HOMEOWNER | P= | C | 12/10/2013 | received potable water cert | TIM | TIM | | P= | C | 4654229 |
TEAM PLUMBING, INC. | P= | R | 12/09/2013 | need proof of potable water | TIM | TIM | | P= | R | 4654048 |
TEAM PLUMBING, INC. | P= | P | 12/06/2013 | need proof of potable water | TIM | TIM | | P= | P | 4653695 |
TEAM PLUMBING, INC. | PTO | C | 06/05/2013 | PLEASE COMPLETE NAIL PROTECTION AT W-BOX AND SILL COCK --- NOTE: THE ONLY PLUMBING IN BASEMENT COMPLETED IS POWDER BATH - OTHER BATHROOMS / BAR HAS NO WATER PIPING | LEE | LEE | | PTO | C | 4536825 |
TEAM PLUMBING, INC. | PTO | P | 06/03/2013 | LOST TEST ON DWV -- IMPROPER TEST ON H20 -- NAIL PROTECTION INCOMPLETE -- LEAK ON KITCHEN DRAIN IN BASEMENT -- NEED FREEZE PROTECTION ON P-TRAP AT FURNACE OFF GARAGE | LEE | LEE | | PTO | P | 4535329 |
HOMEOWNER | PWO | C | 05/29/2013 | TWO 1" LINES IN DITCH | LEE | LEE | | PWO | C | 4532392 |
TEAM PLUMBING, INC. | PB | C | 02/06/2013 | H20 SERVICE THRU WALL AT LATER DATE | LEE | LEE | | PB | C | 4467469 |