TWIN SHORES MANAGEMENT,LLC | B= | C | 02/25/2014 | | CHRISM | CHRISM | | B= | C | 4692354 |
TWIN SHORES MANAGEMENT,LLC | B= | P | 12/18/2013 | Temp CO: pending mech/elect/building finals ( Expires: 1/17/2014 12:00:00 AM) | MINDY | MINDY | | B= | P | 4659196 |
TWIN SHORES MANAGEMENT,LLC | B= | P | 12/12/2013 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 385-5982), External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: enijkamp@springsgov.com or 385-5977), External Agency Inspection HD= by HEALTHDEPT is not Completed yet, Floodplain Final Inspection is not Completed yet, FRONTIER MECHANICAL INC Mechanical Final Inspection is not Completed yet, RESTAURANT EQUIPMENT SERVICE, INC. Mechanical Final Inspection is not Completed yet. seal holes in ceiling in electric room -- Schedule a new Building Final when above items are complete. | CHRISM | CHRISM | | B= | P | 4656246 |
TWIN SHORES MANAGEMENT,LLC | B= | P | 11/14/2013 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: kmagargal@springsgov.com or 385-5060), External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: enijkamp@springsgov.com or 385-5977), External Agency Inspection HD= by HEALTHDEPT is not Completed yet, Floodplain Final Inspection is not Completed yet, FRONTIER MECHANICAL INC Mechanical Final Inspection is not Completed yet, INTERSTATE MECHANICAL, INC. Mechanical Final Inspection is not Completed yet, INTERSTATE MECHANICAL, INC. Plumbing Final Inspection is not Completed yet, MEISNER ELECTRIC ,INC. Electrical Final Inspection is not Completed yet, RESTAURANT EQUIPMENT SERVICE, INC. Mechanical Final Inspection is not Completed yet. ok to remove temp wall from mall entrance -- Schedule a new Building Final when above items are complete. | CHRISM | CHRISM | | B= | P | 4642179 |
TWIN SHORES MANAGEMENT,LLC | BSP | P | 11/12/2013 | PLAN SPLICE: (No Fee) by: MICHAEL for Construction: Add walk-in cooler - revise floor plan | MICHAELA | MICHAELA | | BSP | P | 4639146 |
INTERSTATE MECHANICAL, INC. | BSP | T | 11/07/2013 | PAID (REC#1166407) PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: new splice page see clouds | TCRIPPEN | TCRIPPEN | | BSP | T | 4637099 |
MEISNER ELECTRIC ,INC. | BSP | T | 10/16/2013 | PAID (REC#1160500) PLAN SPLICE FEE: $50 by: SHELBY for Electrical | SHELBY | SHELBY | | BSP | T | 4623393 |
INTERSTATE MECHANICAL, INC. | BSP | T | 10/14/2013 | PAID (REC#1160501) PLAN SPLICE FEE: $50 by: RUSSELL for Mechanical: revised mechanical and the gas piping with gas meter in new location | RUSSELL | RUSSELL | | BSP | T | 4621738 |
INTERSTATE MECHANICAL, INC. | BSP | T | 10/11/2013 | PAID (REC#1160501) PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: new splice pages see clouds | TCRIPPEN | TCRIPPEN | | BSP | T | 4620732 |
TWIN SHORES MANAGEMENT,LLC | BSP | T | 10/10/2013 | PAID (REC#1159376) PLAN SPLICE FEE: $100 by: MICHAEL for Construction: Revised architectural details - no structural included | MICHAELA | MICHAELA | | BSP | T | 4620460 |
TWIN SHORES MANAGEMENT,LLC | BFR | P | 10/09/2013 | seating/riser framing for theater 1307 (80 foot screen room) ok | BLAKE | BLAKE | | BFR | P | 4619776 |
TWIN SHORES MANAGEMENT,LLC | BFR | P | 10/04/2013 | link between building faming OK | DANF | DANF | | BFR | P | 4617015 |
TWIN SHORES MANAGEMENT,LLC | BFR | P | 09/11/2013 | 1308.1309,1312, lobby walls ok | CHRISM | CHRISM | | BFR | P | 4603062 |
TWIN SHORES MANAGEMENT,LLC | BFR | P | 08/27/2013 | riser framing in 1301,1310 and 1311 | CHRISM | CHRISM | | BFR | P | 4593894 |
TWIN SHORES MANAGEMENT,LLC | BSP | P | 08/22/2013 | reviewed storage areas under seating sections fire resistance requirements with super | BERTW | BERTW | | BSP | P | 4590896 |
TWIN SHORES MANAGEMENT,LLC | BFR | P | 08/22/2013 | light gauge stadium risers in 1302,1305 and 1306 and walls under seating ok | BERTW | BERTW | | BFR | P | 4590881 |
TWIN SHORES MANAGEMENT,LLC | BFD | P | 08/16/2013 | DRAIN INSTALLED AT OUTSIDE REAR WALL OF 1308 | CHRISM | CHRISM | | BFD | P | 4586627 |
TWIN SHORES MANAGEMENT,LLC | BFR | P | 08/15/2013 | bleacher framing ok to pour concrete decking in rooms 1303 and 1304 | BLAKE | BLAKE | | BFR | P | 4586098 |
TWIN SHORES MANAGEMENT,LLC | BFR | P | 08/08/2013 | walls ok theatre 8-9-10-11-12-13 | CHRISM | CHRISM | | BFR | P | 4581679 |
TWIN SHORES MANAGEMENT,LLC | BSP | P | 07/31/2013 | training on A1 occupancy with Inspector Mr Morin | BERTW | BERTW | | BSP | P | 4575168 |
TWIN SHORES MANAGEMENT,LLC | BFR | P | 07/31/2013 | rear theater walls 1308 thru 1313 | CHRISM | CHRISM | | BFR | P | 4575165 |
TWIN SHORES MANAGEMENT,LLC | BFR | P | 07/30/2013 | canceled at site | CHRISM | CHRISM | | BFR | P | 4574820 |
TWIN SHORES MANAGEMENT,LLC | BFR | P | 07/26/2013 | 1306- rear wall and south side furred walls ok 1303 and 1304- rear walls and both side furred walls ok | BLAKE | BLAKE | | BFR | P | 4572638 |
TWIN SHORES MANAGEMENT,LLC | BFR | P | 07/24/2013 | met with chris 563-542-8766- room 1305- above curtain furred wall ok rooms 1301, 1302 and 1305- back of theater/ projection room wall ok | BLAKE | BLAKE | | BFR | P | 4570611 |
TWIN SHORES MANAGEMENT,LLC | BSP | P | 07/10/2013 | slab insulation and grade beams at 1307, 1308, 1313 | CHRISM | CHRISM | | BSP | P | 4560520 |
TWIN SHORES MANAGEMENT,LLC | BSP | P | 06/20/2013 | roof insulation started on north end ok, slab insulation and grade beams in 1308-1309-1310-1311 | CHRISM | CHRISM | | BSP | P | 4546821 |
TWIN SHORES MANAGEMENT,LLC | BFI | P | 06/13/2013 | ok in 1301, 1306, 1310 and 1311 | CHRISM | CHRISM | | BFI | P | 4542859 |
TWIN SHORES MANAGEMENT,LLC | BBB | P | 06/11/2013 | top of wall east walls 1306 and 1308, need Teracon inspection reports by final | CHRISM | CHRISM | | BBB | P | 4540749 |
TWIN SHORES MANAGEMENT,LLC | BSP | P | 06/06/2013 | perimeter insulation and grade beams in 1302 and 1305 | CHRISM | CHRISM | | BSP | P | 4538327 |
TWIN SHORES MANAGEMENT,LLC | BBB | P | 06/05/2013 | grout scheduled for 6:30 am, ok for terracon eng to do inspection | BLAKE | BLAKE | | BBB | P | 4536696 |
TWIN SHORES MANAGEMENT,LLC | BBB | P | 05/30/2013 | east wall of 1307 at 44'4" | CHRISM | CHRISM | | BBB | P | 4532984 |
TWIN SHORES MANAGEMENT,LLC | BSP | P | 05/29/2013 | slab insulation and rebar at grade beams 1303 and 1304 | CHRISM | CHRISM | | BSP | P | 4532764 |
TWIN SHORES MANAGEMENT,LLC | BBB | P | 05/28/2013 | see page S1.1, top of wall | CHRISM | CHRISM | | BBB | P | 4531060 |
TWIN SHORES MANAGEMENT,LLC | BBB | P | 05/23/2013 | see page S1.1 at truss bearing | CHRISM | CHRISM | | BBB | P | 4529594 |
TWIN SHORES MANAGEMENT,LLC | BBB | P | 05/08/2013 | see page S1.1 west wall south three theaters at joist bearing | CHRISM | CHRISM | | BBB | P | 4519649 |
TWIN SHORES MANAGEMENT,LLC | BBB | P | 04/26/2013 | top of wall ok as marked on S1.1, ok for terracon to inspect over weekend | CHRISM | CHRISM | | BBB | P | 4512598 |
TWIN SHORES MANAGEMENT,LLC | BBB | P | 04/25/2013 | joist bearing on walls marked page S1.1 | CHRISM | CHRISM | | BBB | P | 4511890 |
TWIN SHORES MANAGEMENT,LLC | BSP | P | 02/25/2013 | met with project manager, Teracon engineering to inspect rap piers | CHRISM | CHRISM | | BSP | P | 4476947 |
TWIN SHORES MANAGEMENT,LLC | BSP | T | 02/11/2013 | PAID (REC#1110815) PLAN SPLICE FEE: $50 by: MICHAEL for Construction: Rervise foundation design | MICHAELA | MICHAELA | | BSP | T | 4470021 |
MEISNER ELECTRIC ,INC. | E= | C | 02/25/2014 | 30 day metering complete and successful ( see splice 2/25/14 ). | SHELBY | SHELBY | | E= | C | 4692332 |
MEISNER ELECTRIC ,INC. | E= | P | 12/13/2013 | site lighting ok,,,,,,, NOTE! DO NOT FINAL THIS JOB UNTIL METERING OF SERVICE HAS BEEN APPROVED BY RBD ELECTRICAL | GARYL | GARYL | | E= | P | 4656919 |
MEISNER ELECTRIC ,INC. | E= | C | 12/10/2013 | FIRE ALARM INSPECTION: | GARYL | GARYL | | E= | C | 4654771 |
MEISNER ELECTRIC ,INC. | E= | P | 12/10/2013 | 1) 25 amp fuses, beer cooler--20 amp breaker, 13-projectors, building exterrior lighting | GARYL | GARYL | | E= | P | 4654760 |
MEISNER ELECTRIC ,INC. | E= | P | 12/09/2013 | lobby, re-fill station, beer cooler, work room, connector room | GARYL | GARYL | | E= | P | 4654153 |
MEISNER ELECTRIC ,INC. | EP | P | 12/09/2013 | panel "F" | GARYL | GARYL | | EP | P | 4654094 |
MEISNER ELECTRIC ,INC. | ER | C | 11/15/2013 | FIRE ALARM INSPECTION: | GARYL | GARYL | | ER | C | 4642923 |
MEISNER ELECTRIC ,INC. | ER | P | 11/15/2013 | above server room ceilings and panel C2 | GARYL | GARYL | | ER | P | 4642898 |
MEISNER ELECTRIC ,INC. | E= | P | 11/13/2013 | FIRE ALARM INSPECTION: STORE ROOMS ----105.1---105.2---105.3---105.5--105.6--105.8---105.9--105.10---- | BRIAN | BRIAN | | E= | P | 4640966 |
MEISNER ELECTRIC ,INC. | E= | P | 11/13/2013 | FIRE ALARM INSPECTION: main corridor --except drinking fountains and poster signs | BRIAN | BRIAN | | E= | P | 4640954 |
MEISNER ELECTRIC ,INC. | ER | P | 11/12/2013 | above ceiling in coordinator 1902, Panel "S", | GARYL | GARYL | | ER | P | 4640130 |
MEISNER ELECTRIC ,INC. | E= | P | 11/12/2013 | auditoriums 1308-1313 | GARYL | GARYL | | E= | P | 4640067 |
MEISNER ELECTRIC ,INC. | E= | P | 11/12/2013 | FIRE ALARM INSPECTION: #1308-1313 | GARYL | GARYL | | E= | P | 4640062 |
MEISNER ELECTRIC ,INC. | EP | P | 11/08/2013 | panelsHL andC | GARYL | GARYL | | EP | P | 4638612 |
MEISNER ELECTRIC ,INC. | E= | P | 11/08/2013 | auditorium and projection booths: 1301-1306 AND ceilings in projection booth 1307 | GARYL | GARYL | | E= | P | 4638605 |
MEISNER ELECTRIC ,INC. | E= | P | 11/08/2013 | FIRE ALARM INSPECTION: Auditoriums and projection booths: 1301-1306 ok | GARYL | GARYL | | E= | P | 4638597 |
MEISNER ELECTRIC ,INC. | ER | P | 11/06/2013 | FIRE ALARM INSPECTION: Projection booths: 1308, 1309, 1310, 1311, 1312, 1313 | GARYL | GARYL | | ER | P | 4636951 |
MEISNER ELECTRIC ,INC. | ER | P | 11/06/2013 | Projection booths: 1308, 1309, 1310, 1311, 1312, 1313 | GARYL | GARYL | | ER | P | 4636932 |
MEISNER ELECTRIC ,INC. | EP | P | 11/05/2013 | Panels: R2, E, R3 | GARYL | GARYL | | EP | P | 4636087 |
MEISNER ELECTRIC ,INC. | E= | P | 11/05/2013 | #18 RTU, 25amp breaker | GARYL | GARYL | | E= | P | 4636079 |
MEISNER ELECTRIC ,INC. | ER | P | 11/01/2013 | ABOVE CEILINGS----projection booths 1301--1302--1303---1304---1305---1306----CORRIDOR ----117.1--116.2---116,3----116.5-----STORAGE-----105.6---- | BRIAN | BRIAN | | ER | P | 4634530 |
MEISNER ELECTRIC ,INC. | ER | P | 11/01/2013 | FIRE ALARM INSPECTION: FIRE ALARM----projection booths--1301,1302,1303,1304,1305,1306--------CORRIDORS----117.1---116.2 ---116.3 ---116.5 --- STORAGE----105.6--- | BRIAN | BRIAN | | ER | P | 4634529 |
MEISNER ELECTRIC ,INC. | EP | P | 11/01/2013 | panels---R-1------A | BRIAN | BRIAN | | EP | P | 4634528 |
MEISNER ELECTRIC ,INC. | ER | P | 10/30/2013 | FIRE ALARM INSPECTION: SOUTH CORRIDOR --EXCEPT ROOMS---115.1 ---113.1----111.2--- FIRE ALARM | BRIAN | BRIAN | | ER | P | 4632275 |
MEISNER ELECTRIC ,INC. | EP | P | 10/30/2013 | PANELS---L -----L-2 -----B---P--- OK | BRIAN | BRIAN | | EP | P | 4632257 |
MEISNER ELECTRIC ,INC. | ER | P | 10/30/2013 | CEILINGS --SOUTH CORRIDOR EXCEPT ROOMS---115.1---113.1---111.2---OK | BRIAN | BRIAN | | ER | P | 4632252 |
MEISNER ELECTRIC ,INC. | E= | P | 10/29/2013 | the following RTU's ok: 6A, #5. 1B, 1A, #16, #17, #14, 13A, 13B, #9, 8A,
the following need to change breakers to match unit, 6B, #4, #3, #2, #15, 7C, 7A, 7B, 7D, #12, #11, #10, 8b, note 3-SPLIT UNITS NOT READY, #18 RTU, beer cooler/condenser | GARYL | GARYL | | E= | P | 4631692 |
MEISNER ELECTRIC ,INC. | EP | L | 10/29/2013 | not ready | GARYL | GARYL | | EP | L | 4631688 |
MEISNER ELECTRIC ,INC. | E= | R | 10/28/2013 | CONTRACTOR TO RESCHEDULE | MIKEC | MIKEC | | E= | R | 4630247 |
MEISNER ELECTRIC ,INC. | EP | P | 10/25/2013 | disconnect PDT and switch gear related to same | GARYL | GARYL | | EP | P | 4629615 |
MEISNER ELECTRIC ,INC. | ER | P | 10/25/2013 | FIRE ALARM INSPECTION: above ceiling north end of building | GARYL | GARYL | | ER | P | 4629600 |
MEISNER ELECTRIC ,INC. | ER | P | 10/25/2013 | ceiling north of beam work room 104.1 | GARYL | GARYL | | ER | P | 4629595 |
MEISNER ELECTRIC ,INC. | ER | P | 10/22/2013 | north and south soffits of connector room | GARYL | GARYL | | ER | P | 4627324 |
MEISNER ELECTRIC ,INC. | EP | P | 10/22/2013 | Panels: D1, D2 and transformer T1 | GARYL | GARYL | | EP | P | 4627278 |
MEISNER ELECTRIC ,INC. | EUG | P | 10/22/2013 | east island to front of eastern island or just Ester islands (for Matts eyes only) | GARYL | GARYL | | EUG | P | 4627263 |
MEISNER ELECTRIC ,INC. | ER | L | 10/21/2013 | not ready | GARYL | GARYL | | ER | L | 4626405 |
MEISNER ELECTRIC ,INC. | EUG | P | 10/21/2013 | southeast, 1st island to the east | GARYL | GARYL | | EUG | P | 4626402 |
MEISNER ELECTRIC ,INC. | ES | C | 10/21/2013 | Commercial Service: 1600 amp 277/480 ok for CT metering | GARYL | GARYL | | ES | C | 4625703 |
MEISNER ELECTRIC ,INC. | ES | C | 10/17/2013 | Commercial Service: Pre-release--after looking at service for a Sunday shut down and power transfer | GARYL | GARYL | | ES | C | 4624415 |
MEISNER ELECTRIC ,INC. | ER | C | 10/16/2013 | FIRE ALARM INSPECTION: work room 104.1 and west wall of connector room | GARYL | GARYL | | ER | C | 4623672 |
MEISNER ELECTRIC ,INC. | ER | P | 10/16/2013 | work room #104.1 and west wall of connector room | GARYL | GARYL | | ER | P | 4623671 |
MEISNER ELECTRIC ,INC. | ES | T | 10/09/2013 | PAID (REC#1160119): need revised prints with correct loads to continue with service inspection | GARYL | GARYL | | ES | T | 4619759 |
MEISNER ELECTRIC ,INC. | ER | P | 10/07/2013 | FIRE ALARM INSPECTION: East wall in 1307 lobby and connector room walls | GARYL | GARYL | | ER | P | 4618179 |
MEISNER ELECTRIC ,INC. | ER | P | 10/07/2013 | east wall in #1307 lobby, and connector room walls | GARYL | GARYL | | ER | P | 4618177 |
MEISNER ELECTRIC ,INC. | EUG | P | 10/07/2013 | east of north/east island going east | GARYL | GARYL | | EUG | P | 4618172 |
MEISNER ELECTRIC ,INC. | ER | P | 10/03/2013 | FIRE ALARM INSPECTION: west wall of main lobby | GARYL | GARYL | | ER | P | 4616047 |
MEISNER ELECTRIC ,INC. | EUG | R | 10/03/2013 | not ready--ran into hard ground | GARYL | GARYL | | EUG | R | 4616044 |
MEISNER ELECTRIC ,INC. | ER | P | 10/02/2013 | FIRE ALARM INSPECTION: west lobby wall /entry wall | BRIAN | BRIAN | | ER | P | 4615168 |
MEISNER ELECTRIC ,INC. | EUG | P | 10/02/2013 | north land scape feed---east pole light feed from 2nd island to east island on north | BRIAN | BRIAN | | EUG | P | 4615163 |
MEISNER ELECTRIC ,INC. | ER | P | 09/30/2013 | FIRE ALARM INSPECTION: lobby poster case soffit and walls-----refill station walls | SHELBY | SHELBY | | ER | P | 4613388 |
MEISNER ELECTRIC ,INC. | ER | P | 09/30/2013 | consessions soffit OK------lobby poster case soffit and walls OK------refill station walls OK--1307 lobby was not inspected | SHELBY | SHELBY | | ER | P | 4613386 |
MEISNER ELECTRIC ,INC. | EUG | P | 09/30/2013 | | SHELBY | SHELBY | | EUG | P | 4613384 |
MEISNER ELECTRIC ,INC. | ER | P | 09/20/2013 | FIRE ALARM INSPECTION: PROJECTION BOOTHS --1308--1309--1310--1311--1312--1213---CONDUIT STUBS IN WALLS | BRIAN | BRIAN | | ER | P | 4608250 |
MEISNER ELECTRIC ,INC. | ER | P | 09/20/2013 | PROJECTION BOOTHS # 1308,1309,1310,1311,1312,1313 WALLS ONLY | BRIAN | BRIAN | | ER | P | 4608246 |
MEISNER ELECTRIC ,INC. | ER | P | 09/19/2013 | FIRE ALARM INSPECTION: rooms: 116.2, 116.3, 105.6, 108.1, 111.2, same as rough on same day | GARYL | GARYL | | ER | P | 4607104 |
MEISNER ELECTRIC ,INC. | ER | P | 09/19/2013 | Rooms: 116.2, 116.3, 111.2, 105.6, 108.1 | GARYL | GARYL | | ER | P | 4607082 |
MEISNER ELECTRIC ,INC. | EUG | P | 09/19/2013 | north and west of "connector", except where crosses into same area, all under concrete, nothing inspected further north out of concrete--not ready, 11/4 going east to pole light in island | GARYL | GARYL | | EUG | P | 4607072 |
MEISNER ELECTRIC ,INC. | ER | P | 09/17/2013 | FIRE ALARM INSPECTION: auditorium above ceiling 1307 --- walls 1307 ----walls below stadium seating 1309 ,10 , 11,12,13 and server room ------ exit vestibule 1301 --- OK | CRAIGS | CRAIGS | | ER | P | 4605800 |
MEISNER ELECTRIC ,INC. | ER | C | 09/17/2013 | auditorium above ceiling 1307 ,walls in 1307,exit vestibule 1301, below stadium seating south end 1309.10,11,12,13---- server room walls OK | CRAIGS | CRAIGS | | ER | C | 4605796 |
MEISNER ELECTRIC ,INC. | ER | P | 09/13/2013 | FIRE ALARM INSPECTION: walls except the following: "connector hallway" concession, lobby, Refill area, #1307---Big D | GARYL | GARYL | | ER | P | 4604573 |
MEISNER ELECTRIC ,INC. | EP | R | 09/13/2013 | not ready | GARYL | GARYL | | EP | R | 4604549 |
MEISNER ELECTRIC ,INC. | ER | R | 09/13/2013 | not ready in managers office and control room | GARYL | GARYL | | ER | R | 4604546 |
MEISNER ELECTRIC ,INC. | ER | P | 09/11/2013 | Projection rooms: 06,09,====bathrooms: men/women and unisex, ======volmatory walls only: 8, 9, 10. 11, 12, 13 | GARYL | GARYL | | ER | P | 4602933 |
MEISNER ELECTRIC ,INC. | EUG | P | 09/09/2013 | secondaries, informed EC to incorporate CSU | GARYL | GARYL | | EUG | P | 4600956 |
MEISNER ELECTRIC ,INC. | ER | P | 09/06/2013 | Projection rooms: 1301 thru 1305 , walls only | GARYL | GARYL | | ER | P | 4599820 |
MEISNER ELECTRIC ,INC. | ER | P | 08/30/2013 | bath room and storage and entry 1301 ---- entry and poster boards both sides 1301 1306 OK | CRAIGS | CRAIGS | | ER | P | 4596509 |
MEISNER ELECTRIC ,INC. | ER | P | 08/28/2013 | "Exit" lighing in 1302, 1305, 1306, and north woman's bathroom | GARYL | GARYL | | ER | P | 4594420 |
MEISNER ELECTRIC ,INC. | ER | P | 08/27/2013 | walls for 1302 and 1305 , norht men's bathroom | GARYL | GARYL | | ER | P | 4593775 |
MEISNER ELECTRIC ,INC. | ER | P | 08/26/2013 | walls only for 1303, 1304 | GARYL | GARYL | | ER | P | 4592648 |
MEISNER ELECTRIC ,INC. | ER | P | 08/21/2013 | ceilings for 1312 | GARYL | GARYL | | ER | P | 4590102 |
MEISNER ELECTRIC ,INC. | ER | P | 08/20/2013 | ceiling for unit 1309 | GARYL | GARYL | | ER | P | 4589032 |
MEISNER ELECTRIC ,INC. | ER | P | 08/19/2013 | 1308, 1309 not ready, Ceilings only | GARYL | GARYL | | ER | P | 4588139 |
MEISNER ELECTRIC ,INC. | EUG | P | 08/19/2013 | "Connector" room, between mall and theaters | GARYL | GARYL | | EUG | P | 4588125 |
MEISNER ELECTRIC ,INC. | ER | P | 08/15/2013 | walls: 1311, 1312, ceilings in 13 11 | GARYL | GARYL | | ER | P | 4586149 |
MEISNER ELECTRIC ,INC. | ER | P | 08/13/2013 | 1313 WALLS AND CEILING--- 1310 CEILING | BRIAN | BRIAN | | ER | P | 4584271 |
MEISNER ELECTRIC ,INC. | ER | P | 08/12/2013 | demising wall for rooms 1308, 1309., 1310 | GARYL | GARYL | | ER | P | 4583505 |
MEISNER ELECTRIC ,INC. | ER | P | 08/12/2013 | above ceiling s in 1305, | GARYL | GARYL | | ER | P | 4583488 |
MEISNER ELECTRIC ,INC. | ER | P | 08/08/2013 | #1306--ceilings only | GARYL | GARYL | | ER | P | 4581271 |
MEISNER ELECTRIC ,INC. | ER | P | 08/07/2013 | ceilings only: 1301, 1303, 1304, 1305 | GARYL | GARYL | | ER | P | 4580560 |
MEISNER ELECTRIC ,INC. | ER | P | 08/02/2013 | demising walls 1301, 1306 | GARYL | GARYL | | ER | P | 4577741 |
MEISNER ELECTRIC ,INC. | EUG | P | 08/02/2013 | refill area eug | GARYL | GARYL | | EUG | P | 4577737 |
MEISNER ELECTRIC ,INC. | ER | P | 08/01/2013 | DEMISING WALLS FOR 1302 -- 1305 | BRIAN | BRIAN | | ER | P | 4576613 |
MEISNER ELECTRIC ,INC. | EUG | P | 07/30/2013 | SOUTH /WEST OF MAIN ENTRANCE--- POLE LIGHTS AND PLANTERS--- 1 CONDUIT FOR RAIN PLANTER--- OK TO COVER | BRIAN | BRIAN | | EUG | P | 4574594 |
MEISNER ELECTRIC ,INC. | ER | P | 07/30/2013 | AUDITORIUMS 1303 / 1304 NORTH EXTERIOR AND SOUTH DEMISING WALLS / THIS INCLUDES FIRE ALARM CONDUIT | BRIAN | BRIAN | | ER | P | 4574593 |
MEISNER ELECTRIC ,INC. | EUG | P | 07/25/2013 | LOBBY OK --- STILL NEED REFILL AREA-- | BRIAN | BRIAN | | EUG | P | 4571566 |
MEISNER ELECTRIC ,INC. | EUG | P | 07/15/2013 | 1308 and 1313, thru to grade beams | GARYL | GARYL | | EUG | P | 4563219 |
MEISNER ELECTRIC ,INC. | EUG | P | 07/11/2013 | AUDITORIUM 1307 UPPER SECTION | MIKEC | MIKEC | | EUG | P | 4561178 |
MEISNER ELECTRIC ,INC. | EUG | P | 06/27/2013 | telecom ok to cover to connectors feeder conduit for panels A,L,C and C2 to grid line 4 ok to cover | TOMC | TOMC | | EUG | P | 4552902 |
MEISNER ELECTRIC ,INC. | EUG | P | 06/25/2013 | rooms 1309 and 1312 up to grade beam 1 -1-1/4" and 1" and 3/4" pvc | CRAIG | CRAIG | | EUG | P | 4549860 |
MEISNER ELECTRIC ,INC. | EUG | P | 06/20/2013 | room 1308 under ground to east side of grade beam 1 -------------- room 1307 under ground to east side of columns | CRAIG | CRAIG | | EUG | P | 4547354 |
MEISNER ELECTRIC ,INC. | EUG | P | 06/18/2013 | rooms 1310 and 1311 to grade beam 1 under ground 3/4" 1" and 1-1/4" pvc | CRAIG | CRAIG | | EUG | P | 4545550 |
MEISNER ELECTRIC ,INC. | EUG | P | 06/14/2013 | 3 ground rods in room 1309 ------------------main trench line for under ground in main hallway up to rooms 1301 and 1306 only | CRAIG | CRAIG | | EUG | P | 4543543 |
MEISNER ELECTRIC ,INC. | EUG | P | 06/13/2013 | trench for temp power to bldg | GARYL | GARYL | | EUG | P | 4542773 |
MEISNER ELECTRIC ,INC. | EUG | P | 06/11/2013 | Room 1306 to grade beam 1 | GARYL | GARYL | | EUG | P | 4541044 |
MEISNER ELECTRIC ,INC. | EUG | P | 06/06/2013 | rm 313 1" and 3/4 " pvc up to west side of grade beam 1302 and 1305 1" and 1.25 pvc to main hall way | CRAIG | CRAIG | | EUG | P | 4537834 |
MEISNER ELECTRIC ,INC. | EUG | P | 05/30/2013 | Rooms 1303, 1304 to grade beam, 1st level for electric room | GARYL | GARYL | | EUG | P | 4533560 |
MEISNER ELECTRIC ,INC. | EUG | P | 05/21/2013 | east of grade beam room 1307 | GARYL | GARYL | | EUG | P | 4528096 |
MEISNER ELECTRIC ,INC. | EUG | P | 05/15/2013 | 1301 TO GRADE BEAM | MIKEC | MIKEC | | EUG | P | 4524001 |
MEISNER ELECTRIC ,INC. | EUG | P | 05/13/2013 | slab 1309 to gb 1 | BRET | BRET | | EUG | P | 4522755 |
MEISNER ELECTRIC ,INC. | EUG | P | 05/08/2013 | Room 1305, north and east in the middle | GARYL | GARYL | | EUG | P | 4519985 |
MEISNER ELECTRIC ,INC. | EUG | P | 05/07/2013 | 1302 AND 1304 TO GRADE BEAMS | MIKEC | MIKEC | | EUG | P | 4519046 |
MEISNER ELECTRIC ,INC. | EUG | P | 05/02/2013 | marked on permit card | GARYL | GARYL | | EUG | P | 4516418 |
MEISNER ELECTRIC ,INC. | EUG | P | 05/01/2013 | see orange card | MIKEC | MIKEC | | EUG | P | 4515766 |
MEISNER ELECTRIC ,INC. | EUG | P | 04/29/2013 | ELECTRIC ROOM AND WEST SIDE OF 1303 | MIKEC | MIKEC | | EUG | P | 4513532 |
MEISNER ELECTRIC ,INC. | EUG | P | 04/23/2013 | SEE ORANGE CARD | MIKEC | MIKEC | | EUG | P | 4510787 |
MEISNER ELECTRIC ,INC. | ESL | P | 04/03/2013 | ufer, #4 20' tied into re-bar | GARYL | GARYL | | ESL | P | 4499545 |
CLIFFORD PERKINS DBA RESTAURANT EQUIPMENT SERVICE | H= | C | 02/12/2014 | REFRIGERATION FINAL OK. | NANCY | NANCY | | H= | C | 4685674 |
CLIFFORD PERKINS DBA RESTAURANT EQUIPMENT SERVICE | H= | P | 01/16/2014 | REFRIGERATION FINAL OK PENDING CONTRACTOR CALLING IN INSPECTION. | NANCY | NANCY | | H= | P | 4672760 |
FRONTIER MECHANICAL INC. | H= | C | 01/16/2014 | MECHANICAL FINAL OK. | NANCY | NANCY | | H= | C | 4672749 |
FRONTIER MECHANICAL INC. | H= | P | 01/08/2014 | REVISED TEST AND BALANCE REPORT RECEIVED. STILL NEED OTHER ITEMS FROM MECHANICAL INSPECTION OF 12/12/13 ADDRESSED. | NANCY | NANCY | | H= | P | 4668628 |
FRONTIER MECHANICAL INC. | H= | P | 12/12/2013 | COMPLETE INSTALLATION OF MINI-SPLIT 4. INSTALL SPEED CONTROLS ON EXHAUST FANS AS PER PRINTS. VERIFY INTERLOCKS ON EXHAUST FANS 16 - 18. INSTALL ACCESS LADDERS ON ROOF. PROVIDE LETTER FROM ENGINEER APPROVING CFM READINGS FOR PROJECTION BOOTH EXHAUST FANS. | NANCY | NANCY | | H= | P | 4655853 |
FRONTIER MECHANICAL INC. | H16 | C | 12/12/2013 | TEST AND BALANCE REPORT RECEIVED. QUESTION REGARDING CFM READINGS FOR EXHAUST FANS 1 THROUGH 13. READINGS OUTSIDE OF THE +/- 10% ALLOWED. DID THE SPEED CONTROLLERS GET INSTALLED AS PER NOTE 1 IN THE FAN SCHEDULE? REST OF REPORT OK. | NANCY | NANCY | | H16 | C | 4655498 |
INTERSTATE MECHANICAL, INC. | H= | C | 12/11/2013 | GAS FINAL OK. | NANCY | NANCY | | H= | C | 4655088 |
CLIFFORD PERKINS DBA RESTAURANT EQUIPMENT SERVICE | HRP | C | 11/25/2013 | 225 LB TEST OK ON COOLER. | NANCY | NANCY | | HRP | C | 4647726 |
FRONTIER MECHANICAL INC. | HD | P | 11/22/2013 | RTU'S 16 AND 17 LOBBY AREA: ALL OK, COMPLETE. PROJECTION BOOTHS: ABOVE CEILING OK IN ALL BOOTHS. | NANCY | NANCY | | HD | P | 4647081 |
FRONTIER MECHANICAL INC. | HD | P | 11/14/2013 | RTU18 CONNECTOR: ABOVE CEILING OK. RTU15 REFILL: ABOVE CEILING OK. | NANCY | NANCY | | HD | P | 4642017 |
CLIFFORD PERKINS DBA RESTAURANT EQUIPMENT SERVICE | HRP | R | 10/31/2013 | NO COOLER SHOWN ON APPROVED PLANS. NEED APPROVED SPLICED PLAN SHOWING COOLER DETAIL AND LOCATION ONSITE BEFORE ANY INSPECTIONS ARE PERFORMED. TEST GAUGE ON EVAPORATOR SHOWING 225 PSI, NEED TO KNOW DESIGN PRESSURE OF SYSTEM TO DETERMINE PRESSURE TEST REQUIREMENTS. NEED CONTRACTOR SUPERVISOR CONTACT INFORMATION LISTED ON NEXT REQUEST. DO NOT CONCEAL ANYTHING | ROBERTV | ROBERTV | | HRP | R | 4633437 |
FRONTIER MECHANICAL INC. | HD | P | 10/28/2013 | NORTH AND SOUTH CORRIDORS. ISOLATE ALL PVC IN RETURN AIR PLENUM. SUPPLIES IN CORRIDORS ALL OK. | NANCY | NANCY | | HD | P | 4630312 |
INTERSTATE MECHANICAL, INC. | HC | C | 10/23/2013 | OK TO SET 2 LB METER. | NANCY | NANCY | | HC | C | 4628129 |
INTERSTATE MECHANICAL, INC. | HI | C | 10/23/2013 | 60 LB TEST OK. INSTALLED AS PER PRINTS. FOR FINAL INSTALL REGULATORS, LABEL ALL MEDIUM PRESSURE GAS LINES. | NANCY | NANCY | | HI | C | 4628125 |
FRONTIER MECHANICAL INC. | HD | P | 10/08/2013 | RTU14 CORRIDOR, SOUTH END: SUPPLY AIR ALL OK, OK TO WRAP. EF15 SOUTH CORRIDOR: ABOVE CEILING ALL OK. RTU17 (MAIN ENTRY): SUPPLY/RETURN ROUGH DUCTS ALL OK. RTU18 (CONNECTOR): SUPPLY/RETURN ROUGH DUCTS ALL OK. | NANCY | NANCY | | HD | P | 4618928 |
FRONTIER MECHANICAL INC. | HD | P | 09/17/2013 | BIG D THEATER RTU'S 7A, 7B, 7C AND 7D: ABOVE CEILING ALL OK, OK TO COVER. NO PROJECTION BOOTH YET. RTU 14: SUPPLY TRUNK LINE GOING NORTH ALL OK OK TO WRAP. NO SOUTH TRUNK LINE YET. RTU15: SUPPLY/RETURN AIR ABOVE CEILING ALL OK, OK TO WRAP. RTU16: SUPPLY AIR ABOVE CEILING IN REFILL AREA OK, OK TO WRAP. EF16, EF17 AND EF18: EXHAUST DUCTS ABOVE CEILING UP THROUGH ROOF DECK OK. NO TYPE II HOODS YET. | NANCY | NANCY | | HD | P | 4605687 |
FRONTIER MECHANICAL INC. | HD | P | 09/05/2013 | RTU 14 CORRIDOR, NORTH END: SUPPLY ALL OK, OK TO WRAP. EF14 NORTH CORRIDOR: EXHAUST DUCTS ABOVE CEILING ALL OK. | NANCY | NANCY | | HD | P | 4598923 |
FRONTIER MECHANICAL INC. | HD | P | 08/29/2013 | BIG D THEATER RTU'S 7A, 7B, 7C AND 7D: ROUGH DUCTS ALL OK, OK TO WRAP ALL LATERALS. CORRIDOR RTU14: RETURN AIR DROP OK, OK TO WRAP. NO SUPPLY AIR YET. | NANCY | NANCY | | HD | P | 4595203 |
FRONTIER MECHANICAL INC. | HD | P | 08/22/2013 | STADIUM 1308 RTU'S 8A AND 8B: ABOVE CEILING ALL OK EXCEPT STILL NEED PROJECTION BOOTH. STADIUM 1309, RTU 9 AND STADIUM 1312 RTU 12: ABOVE CEILING ALL OK EXCEPT STILL NEED THERMAFUSERS AND PROJECTION BOOTH. | NANCY | NANCY | | HD | P | 4590882 |
FRONTIER MECHANICAL INC. | HD | P | 08/14/2013 | STADIUM 1302, RTU2, STADIUM 1310, RTU 10 AND STADIUM 1311, RTU 11: ABOVE CEILING ALL OK EXCEPT STILL NEED THERMAFUSERS AND PROJECTION BOOTH. STADIUM 1301, RTU'S 1A AND 1B, STADIUM 1306 RTU'S 6A AND 6B, STADIUM 1313 RTU'S 13A AND 13B: ABOVE CEILING ALL OK EXCEPT STILL NEED PROJECTION BOOTH. | NANCY | NANCY | | HD | P | 4584901 |
FRONTIER MECHANICAL INC. | HD | P | 08/09/2013 | STADIUM 1305, RTU5: ABOVE CEILING ALL OK EXCEPT STILL NEED THERMAFUSER DIFFUSERS INSTALLED AND PROJECTION BOOTH COMPLETED. | NANCY | NANCY | | HD | P | 4582387 |
FRONTIER MECHANICAL INC. | HD | P | 08/07/2013 | STADIUM 1310, RTU 10 AND STADIUM 11, RTU 11: SUPPLY/RETURN DUCTS OK, OK TO WRAP. STADIUM 1303 AND 1304: ABOVE CEILING ALL OK IN THEATER EXCEPT STILL NEED TO INSTALL MASTER AND DRONE THERMAFUSER DIFFUSERS. PROJECTION BOOTHS NOT COMPLETE YET. | NANCY | NANCY | | HD | P | 4580564 |
FRONTIER MECHANICAL INC. | HD | P | 08/02/2013 | STADIUM 1308, RTU'S 8A AND 8B: SUPPLY/RETURN DUCTS OK, OK TO WRAP. STADIUM 1309, RTU 9: SUPPLY/RETURN OK, OK TO WRAP. STADIUM 1312, RTU 12: SUPPLY/RETURN OK, OK TO WRAP. STADIUM 1313, RTU'S 13A AND 13B: SUPPLY.RETURN OK, OK TO WRAP. | NANCY | NANCY | | HD | P | 4577263 |
FRONTIER MECHANICAL INC. | HD | P | 07/23/2013 | STADIUM 1301, RTU'S 1A AND 1B: SUPPLY/RETURN DUCTS OK, OK TO WRAP. STADIUM 1306, RTU'S 6A AND 6B: SUPPLY/RETURN DUCTS OK, OK TO WRAP. | NANCY | NANCY | | HD | P | 4569793 |
FRONTIER MECHANICAL INC. | HD | P | 07/09/2013 | ROUGH DUCT IN THEATERS BEING SERVED BY RTU-2,3,4, AND 5 OK TO WRAP ONLY | ROBERTV | ROBERTV | | HD | P | 4559754 |
INTERSTATE MECHANICAL, INC. | P= | C | 12/11/2013 | | JOEL | JOEL | | P= | C | 4655396 |
INTERSTATE MECHANICAL, INC. | PTO | C | 11/01/2013 | | LEE | LEE | | PTO | C | 4634118 |
INTERSTATE MECHANICAL, INC. | PTO | P | 10/17/2013 | NEED VERTICAL SUPPORT ON 3" VTR CONCESSIONS AREA -- COMPLETE NAIL / SCREW PROTECTION CONCESSIONS WALL -- NEED ALL CLOSET FLANGES INSTALLED | LEE | LEE | | PTO | P | 4624326 |
INTERSTATE MECHANICAL, INC. | PRD | P | 10/17/2013 | FOR FRONT CANOPY -- LACKS UNDER-DECK CLAMPS ON TWO DRAINS -- TESTS OK | LEE | LEE | | PRD | P | 4624320 |
INTERSTATE MECHANICAL, INC. | PTO | P | 09/18/2013 | CONCESSIONS AREA REST ROOMS | JOEL | JOEL | | PTO | P | 4606551 |
INTERSTATE MECHANICAL, INC. | PTO | P | 09/17/2013 | MIDDLE WEST RESTROOMS -- NOT READY, CHASING LEAKS -- MISSING SCREW PROTECTION -- ANCHOR CLOSET FLANGES -- ETC: | LEE | LEE | | PTO | P | 4605439 |
INTERSTATE MECHANICAL, INC. | PTO | P | 09/12/2013 | MENS AND WOMENS RESTROOMS SOUTH END OK | LEE | LEE | | PTO | P | 4603421 |
INTERSTATE MECHANICAL, INC. | PTO | P | 08/27/2013 | NORTH MENS AND WOMENS RESTROOMS O.K LESS WC FLANGES | JOEL | JOEL | | PTO | P | 4593576 |
INTERSTATE MECHANICAL, INC. | PTO | P | 08/26/2013 | H2O UNDERSIZED | JOEL | JOEL | | PTO | P | 4592594 |
INTERSTATE MECHANICAL, INC. | PB | C | 07/30/2013 | | LEE | LEE | | PB | C | 4574314 |
INTERSTATE MECHANICAL, INC. | PB | P | 07/29/2013 | LACKS GREASE TRAP INSTALL INSTRUCTIONS AND OUTLET VENT | LEE | LEE | | PB | P | 4573349 |
INTERSTATE MECHANICAL, INC. | PRD | P | 07/23/2013 | 8"-10" east side (big d) area.
| DICK | DICK | | PRD | P | 4569278 |
INTERSTATE MECHANICAL, INC. | PRD | P | 07/02/2013 | TWO SETS OF PRIMARY'S NORTH END AND ONE SET S/E CORNER | LEE | LEE | | PRD | P | 4555431 |
INTERSTATE MECHANICAL, INC. | PRD | P | 06/17/2013 | 8''/10'' STUB OUT ON SOUTH END O.K | JOEL | JOEL | | PRD | P | 4544070 |
INTERSTATE MECHANICAL, INC. | PB | P | 06/06/2013 | SOUTH MAIN RESTROOMS AND F/D IN ELECT. ROOM OK | LEE | LEE | | PB | P | 4537726 |
INTERSTATE MECHANICAL, INC. | PB | P | 05/06/2013 | WOMENS MAIN RESTROOM 12- W/C OK | LEE | LEE | | PB | P | 4517791 |
INTERSTATE MECHANICAL, INC. | PRD | P | 05/06/2013 | UNDERGROUND NORTH SIDE -- 1- 10" AND 1- 8" OK | LEE | LEE | | PRD | P | 4517788 |
INTERSTATE MECHANICAL, INC. | PB | P | 04/25/2013 | MEN'S RESTROOM NORTH SIDE OK -- NEED ACCESSIBLE C/OUTS ON 3- URINALS NORTH WALL | LEE | LEE | | PB | P | 4511905 |
INTERSTATE MECHANICAL, INC. | PB | P | 04/03/2013 | 3-29 INSPECTION OK | LEE | LEE | | PB | P | 4498962 |
INTERSTATE MECHANICAL, INC. | PB | R | 03/29/2013 | JOB TRAILER ALL LOCKED UP -- NO PLANS -- NO PERMIT -- LOOKED AT LOBBY RESTROOMS -- CONCESSION / REFILL BAR -- DESIGN OK -- (NO PLANS) | LEE | LEE | | PB | R | 4496200 |
INTERSTATE MECHANICAL, INC. | PB | P | 03/07/2013 | TRUNK COMPLETE -- MISC STUBS NORTH END | LEE | LEE | | PB | P | 4482939 |
INTERSTATE MECHANICAL, INC. | PB | P | 02/28/2013 | TRUNKS & RISERS C.6 TO EXTERIOR | LEE | LEE | | PB | P | 4479160 |