ROBERT SCOTT GENERAL CONTRACTORS, INC. | B= | C | 07/22/2013 | | JOND | JOND | | B= | C | 4568333 |
ROBERT SCOTT GENERAL CONTRACTORS, INC. | BSP | P | 07/11/2013 | 3 deck footers ok | BLAKE | BLAKE | | BSP | P | 4561620 |
ROBERT SCOTT GENERAL CONTRACTORS, INC. | BFR | C | 05/16/2013 | | JOND | JOND | | BFR | C | 4525117 |
ROBERT SCOTT GENERAL CONTRACTORS, INC. | BIN | C | 05/16/2013 | | JOND | JOND | | BIN | C | 4525115 |
ROBERT SCOTT GENERAL CONTRACTORS, INC. | BFR | R | 05/15/2013 | need to fireblock garage bracket | JOND | JOND | | BFR | R | 4524280 |
ROBERT SCOTT GENERAL CONTRACTORS, INC. | BLA | C | 05/15/2013 | | JOND | JOND | | BLA | C | 4524279 |
ROBERT SCOTT GENERAL CONTRACTORS, INC. | BIN | P | 05/15/2013 | insulation ok / need frame signed off | JOND | JOND | | BIN | P | 4524278 |
ROBERT SCOTT GENERAL CONTRACTORS, INC. | BFR | R | 05/13/2013 | brace off ends of laterals / clean out b-vent chase / strap top plate where it meets ml / 2-2x4's under sloped ml beam / strap studs at balloon wall at south end where you have a hinge pt / 2-2x4's under ml beam by stairs / fireblock garage brackets / plans call for 2x8 ledger at entry / firestop / re-do stairs at winder section at upper part / ok to insulate | JOND | JOND | | BFR | R | 4522311 |
ROBERT SCOTT GENERAL CONTRACTORS, INC. | BIN | P | 05/13/2013 | Qualified third party energy inspection documentation must be presented at time of final building (B=) inspection | INTERNET | INTERNET | | BIN | P | 4521984 |
ROBERT SCOTT GENERAL CONTRACTORS, INC. | BFD | C | 03/14/2013 | | JIMP | JIMP | | BFD | C | 4487493 |
ROBERT SCOTT GENERAL CONTRACTORS, INC. | BFN | C | 03/11/2013 | drain usable space below grade; isolate pads; float walls; 5% grade at final; eufer OK | JIMP | JIMP | | BFN | C | 4484859 |
ROBERT SCOTT GENERAL CONTRACTORS, INC. | BFT | P | 03/11/2013 | needed engineers letter on footing observation | JIMP | JIMP | | BFT | P | 4484852 |
SERVICE FIRST ELECTRIC | E= | C | 07/17/2013 | NEED INTERSYSTEM BONDING TERMINAL. STRAP A.C FLEX. 30 AMP A.C | MIKEC | MIKEC | | E= | C | 4565457 |
SERVICE FIRST ELECTRIC | ES | C | 05/10/2013 | Residential Underground: new 150 amp service | MIKEC | MIKEC | | ES | C | 4521788 |
SERVICE FIRST ELECTRIC | ER | C | 05/10/2013 | | MIKEC | MIKEC | | ER | C | 4521784 |
GENE'S HEATING AND AIR LLC | H= | C | 07/17/2013 | All OK. Notes: louvered door to mech with open stairwell - A/C sizing OK | JERRYF | JERRYF | | H= | C | 4565372 |
WESTERN FIREPLACE SUPPLY, INC. | H= | C | 07/17/2013 | All OK. Notes: no mantel | JERRYF | JERRYF | | H= | C | 4565368 |
GENE'S HEATING AND AIR LLC | HC | C | 05/10/2013 | RELEASE METER | MICHAELS | MICHAELS | | HC | C | 4521670 |
GENE'S HEATING AND AIR LLC | HRR | C | 05/10/2013 | Corrections made and heat calcs ok. | MICHAELS | MICHAELS | | HRR | C | 4521669 |
GENE'S HEATING AND AIR LLC | HRR | P | 05/09/2013 | Seal supply boot in bsmt. bdrm., b-vent lacks insulation shield, Rest ok. BY FINAL: need heat calcs. Note: FB, no osa, a/c rough(coil and lineset), direct vent furnace, NO w/h installed at this time. | MICHAELS | MICHAELS | | HRR | P | 4520625 |
KAMPP-L ENTERPRISES, INC. | HI | C | 05/07/2013 | 10# test ok. 1" main to furn, w/h, fp, range. | MICHAELS | MICHAELS | | HI | C | 4518797 |
KAMPP-L ENTERPRISES, INC. | P= | C | 07/17/2013 | | LEE | LEE | | P= | C | 4565696 |
KAMPP-L ENTERPRISES, INC. | PTO | C | 05/07/2013 | NO W/H AT THIS TIME -- WILL F/D BE ACCESSIBLE IN W/H CLOSET ?? | LEE | LEE | | PTO | C | 4519315 |
KAMPP-L ENTERPRISES, INC. | PB | C | 03/19/2013 | | LEE | LEE | | PB | C | 4490193 |