BRYAN CONSTRUCTION, INC. | B= | C | 11/26/2014 | | BERTW | BERTW | | B= | C | 4861226 |
RK MECHANICAL, LLC | BSP | T | 11/21/2014 | PAID (REC#1233545) PLAN SPLICE FEE: $50 by: DALEH for Mechanical | DALEH | DALEH | | BSP | T | 4857957 |
BRYAN CONSTRUCTION, INC. | BSP | T | 11/20/2014 | PAID (REC#1233397) PLAN SPLICE FEE: $50 by: SHELBY for Electrical: Add elevator to scope | SHELBY | SHELBY | | BSP | T | 4857630 |
BRYAN CONSTRUCTION, INC. | BSP | T | 11/20/2014 | PAID (REC#1233397) PLAN SPLICE FEE: $50 by: DANM for Construction: Additional elevator | DANM | DANM | | BSP | T | 4857507 |
BRYAN CONSTRUCTION, INC. | BSP | P | 11/04/2014 | letter of observation for new elevator walls and structural rebar on file/need elevator on plans with RBD approval and open hole report | BERTW | BERTW | | BSP | P | 4848171 |
BRYAN CONSTRUCTION, INC. | BBB | C | 10/23/2014 | report on file for elevator walls | BERTW | BERTW | | BBB | C | 4840396 |
BRYAN CONSTRUCTION, INC. | BFR | C | 02/03/2014 | Structural connection observation report on file | BERTW | BERTW | | BFR | C | 4681893 |
BRYAN CONSTRUCTION, INC. | BIN | C | 02/03/2014 | | BERTW | BERTW | | BIN | C | 4681885 |
BRYAN CONSTRUCTION, INC. | BSP | P | 12/13/2013 | smoke barriers through penetrations caulked ok | BERTW | BERTW | | BSP | P | 4656420 |
BRYAN CONSTRUCTION, INC. | B= | P | 12/11/2013 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 385-5982), External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: enijkamp@springsgov.com or 385-5977), External Agency Inspection HD= by HEALTHDEPT is not Completed yet, GREINER ELECTRIC, LLC Electrical Final Inspection is not Completed yet, OTIS ELEVATOR CO - TAX DEPT Mechanical Final Inspection is not Completed yet, RK MECHANICAL, INC Mechanical Final Inspection is not Completed yet, RK MECHANICAL, INC Plumbing Final Inspection is not Completed yet. -- Schedule a new Building Final when above items are complete. | BERTW | BERTW | | B= | P | 4655094 |
BRYAN CONSTRUCTION, INC. | B= | P | 12/10/2013 | ok pending other finals completed/Rated walls at pool equipment room and sauna walls need through penetrations sealed/install glass in new doors/install rated doors -- Schedule a new Building Final when above items are complete. | BERTW | BERTW | | B= | P | 4654482 |
BRYAN CONSTRUCTION, INC. | BFR | P | 12/10/2013 | ok for 2B building permit only/pending other roughs completed | BERTW | BERTW | | BFR | P | 4654473 |
BRYAN CONSTRUCTION, INC. | BIN | P | 12/10/2013 | changed to partial 12-13-13 | BERTW | BERTW | | BIN | P | 4654445 |
BRYAN CONSTRUCTION, INC. | BSP | P | 12/09/2013 | firecaulking @ 2hr Firewall dampers ok | BERTW | BERTW | | BSP | P | 4653970 |
BRYAN CONSTRUCTION, INC. | BFR | P | 12/06/2013 | repair 2hr infills at 1st fllor where fire dampers penetrate and recall inspection | BERTW | BERTW | | BFR | P | 4653343 |
BRYAN CONSTRUCTION, INC. | BSP | P | 08/23/2013 | reviewed firestopping at expansion joint | BERTW | BERTW | | BSP | P | 4591446 |
BRYAN CONSTRUCTION, INC. | BFR | P | 08/21/2013 | infill framing at 2hr fire wall 1st level ok per approved 3M details #WW-D-0047 and #WW-D-0040 on file | BERTW | BERTW | | BFR | P | 4589905 |
BRYAN CONSTRUCTION, INC. | BFN | C | 08/21/2013 | underpinning observation report on file | BERTW | BERTW | | BFN | C | 4589883 |
BRYAN CONSTRUCTION, INC. | BSP | P | 08/13/2013 | 2-hr fire wall training with Bert W | JEREMYA | JEREMYA | | BSP | P | 4583683 |
BRYAN CONSTRUCTION, INC. | BSP | P | 08/13/2013 | Commercial building inspector Bert W doing on site training with Building inspector Jeremy Anderson regarding type II-B construction 2 hr fire wall south wall | BERTW | BERTW | | BSP | P | 4583680 |
BRYAN CONSTRUCTION, INC. | BFN | P | 08/06/2013 | pending push pile installation report oks | BERTW | BERTW | | BFN | P | 4579134 |
BRYAN CONSTRUCTION, INC. | BFD | C | 08/06/2013 | | BERTW | BERTW | | BFD | C | 4579133 |
BRYAN CONSTRUCTION, INC. | BFT | C | 08/06/2013 | all paperwork for design of push piles on file | BERTW | BERTW | | BFT | C | 4579132 |
BRYAN CONSTRUCTION, INC. | BFR | P | 07/19/2013 | reviewed with job super Steve the documents needed to complete footing and foundation inspections | BERTW | BERTW | | BFR | P | 4567781 |
BRYAN CONSTRUCTION, INC. | BFR | P | 07/16/2013 | 1st floor framing ok/2hr infills at fire barrier precast sections windows 2 layers interior ok-need exterior infills inspected/2hr 4" rated expansion joint need clarification for design/pending other roughs completed | BERTW | BERTW | | BFR | P | 4563684 |
BRYAN CONSTRUCTION, INC. | BFN | P | 06/19/2013 | slab reinforcing at hydro pool area ok | BERTW | BERTW | | BFN | P | 4545869 |
BRYAN CONSTRUCTION, INC. | BFD | R | 06/19/2013 | no drain on this permit | BERTW | BERTW | | BFD | R | 4545867 |
BRYAN CONSTRUCTION, INC. | BFR | P | 06/19/2013 | interior framing in progress | BERTW | BERTW | | BFR | P | 4545866 |
BRYAN CONSTRUCTION, INC. | BFT | P | 06/05/2013 | wrong permit called in | BERTW | BERTW | | BFT | P | 4536748 |
BRYAN CONSTRUCTION, INC. | BFT | P | 06/04/2013 | hydro therapy pool walls ok | BERTW | BERTW | | BFT | P | 4535970 |
BRYAN CONSTRUCTION, INC. | BFT | P | 05/29/2013 | east and west hdro therapy pools ok/pending ufer inspection | BERTW | BERTW | | BFT | P | 4532007 |
BRYAN CONSTRUCTION, INC. | BFN | R | 05/23/2013 | hydro therapy pool west section of a 2 phase job structural sheet missing rebar details/will need RBD stamp on plan revision-reviewed with Beb job super | BERTW | BERTW | | BFN | R | 4529429 |
BRYAN CONSTRUCTION, INC. | BFT | P | 05/02/2013 | Underpinning design on file/letter of observation for installation to design to follow | BERTW | BERTW | | BFT | P | 4516196 |
GREINER ELECTRIC, LLC. | E= | C | 11/21/2014 | | CRAIGS | CRAIGS | | E= | C | 4858016 |
GREINER ELECTRIC, LLC. | E= | P | 11/05/2014 | Need to look at elevator | CRAIGS | CRAIGS | | E= | P | 4848527 |
GREINER ELECTRIC, LLC. | ER | P | 10/16/2014 | | CRAIGS | CRAIGS | | ER | P | 4835676 |
GREINER ELECTRIC, LLC. | EE | L | 06/20/2014 | Renewed at 6/20/2014 10:51:17 AM | RITA | RITA | | EE | L | 4762139 |
GREINER ELECTRIC, LLC. | E= | P | 12/11/2013 | | CRAIGS | CRAIGS | | E= | P | 4654784 |
GREINER ELECTRIC, LLC. | EP | P | 11/26/2013 | EPO and the timer has to be outside the 5' area | CRAIGS | CRAIGS | | EP | P | 4648110 |
GREINER ELECTRIC, LLC. | ER | P | 10/30/2013 | see room numbers on inspection log card | CRAIGS | CRAIGS | | ER | P | 4632027 |
GREINER ELECTRIC, LLC. | ES | C | 10/18/2013 | Commercial Service: 1200 amp 480 volt 4-w replacement MDP--ok to energize -------- NOTES ---- still need to look at panels--- | BRIAN | BRIAN | | ES | C | 4625018 |
GREINER ELECTRIC, LLC. | ER | P | 10/18/2013 | partial ceilings see plans--- hand rail bonding on hydro tub--- | BRIAN | BRIAN | | ER | P | 4624998 |
GREINER ELECTRIC, LLC. | ER | P | 10/07/2013 | HYDRO THERAPY FLOOR DRAIN BONDING----MRI WAII ROUGH OK---- | BRIAN | BRIAN | | ER | P | 4617996 |
GREINER ELECTRIC, LLC. | ER | P | 08/12/2013 | hard lids and soffit see high lighted plans with Robby | CRAIGS | CRAIGS | | ER | P | 4582798 |
GREINER ELECTRIC, LLC. | ER | P | 08/02/2013 | see plans | MIKEC | MIKEC | | ER | P | 4576995 |
GREINER ELECTRIC, LLC. | ER | P | 08/01/2013 | Walls and fire alarm in area highlighted in orange, with the exception of hydro therapy room. The outlets are too close to the pools. | JOSEPH | JOSEPH | | ER | P | 4576246 |
GREINER ELECTRIC, LLC. | ER | P | 07/16/2013 | walls in yellow prints pg. a 2.11 --- also F/A | CRAIGS | CRAIGS | | ER | P | 4563701 |
GREINER ELECTRIC, LLC. | ER | P | 06/19/2013 | bonding around spa area --- OK | CRAIGS | CRAIGS | | ER | P | 4545771 |
GREINER ELECTRIC, LLC. | ESL | C | 05/21/2013 | pvc coated in slab for treatment tables OK | CRAIGS | CRAIGS | | ESL | C | 4528178 |
GREINER ELECTRIC, LLC. | ESL | R | 05/17/2013 | need receptacle conduits to be metal raceway --plans call this area treatment | CRAIGS | CRAIGS | | ESL | R | 4525643 |
OTIS ELEVATOR COMPANY | HE= | C | 11/26/2014 | ELEVATOR COMPLETE STATE ID # CP14-000664 | JOHNW | JOHNW | | HE= | C | 4860776 |
OTIS ELEVATOR COMPANY | HE= | P | 11/25/2014 | STILL NEED STATE REGISTRATION
| JOHNW | JOHNW | | HE= | P | 4859893 |
OTIS ELEVATOR COMPANY | HE | P | 11/24/2014 | Renewed at 11/24/2014 7:34:51 AM | JOHNW | JOHNW | | HE | P | 4858959 |
RK MECHANICAL, LLC | H= | C | 11/21/2014 | COMPLETED | ROBERTV | ROBERTV | | H= | C | 4858027 |
RK MECHANICAL, LLC | H= | P | 10/29/2014 | TEST AND BALANCE REPORT RECEIVED AND ATTACHED TO PERMIT. PER BRYAN CONSTRUCTION, MECHANICAL ENGINEER IS DELETING 2ND LEVEL SHAFT CONSTRUCTION AS PREVIOUS ISSUE WAS NOTED, SPLICE WILL BE REVIEWED WHEN AVAILABLE. | ROBERTV | ROBERTV | | H= | P | 4844148 |
RK MECHANICAL, LLC | H= | R | 10/07/2014 | DISCUSSED UNCONSTRUCTED SHAFT SHOWN ON MECHANICAL DRAWING M2.21 AT 2ND FLOOR PENETRATION. CHRIS FROM BRYAN CONSTRUCTION TO CONTACT MECHANICAL ENGINEER AND DETERMINE SHAFT REQUIREMENT. IF REMOVED, PLANS WILL HAVE TO BE SPLICED TO REFLECT AS-BUILT. ITEMS LISTED IN PREVIOUS INSPECTION STILL NEED ADDRESSED. | ROBERTV | ROBERTV | | H= | R | 4829643 |
RK MECHANICAL, LLC | H= | R | 04/24/2014 | TEST AND BALANCE REPORT INCOMPLETE, SECOND LEVEL FLOOR PENETRATIONS ABOVE POOL EQUIPMENT ROOM AND LAUNDRY NEED TO COMPLY WITH THIS SCOPE OF WORK SHOWN ON THIS PLAN AS THE TENANT FINISH RELIES ON THESE ITEMS TO BE COMPLETED, MECHANICAL CONTRACTOR NEEDS TO ACKNOWLEDGE ITEMS THAT NEED COMPLETED AND CALL INSPECTION WHEN READY. | ROBERTV | ROBERTV | | H= | R | 4726177 |
OTIS ELEVATOR COMPANY | HER | C | 03/24/2014 | ELEVATORS ARE STILL UNDER CONSTRUCTION, OK FOR BUILDING TCO WITHOUT USE OF ELEVATORS IF APPROVED BY BUILDING INSPECTOR AND FIRE DEPARTMENT | ERIC | ERIC | | HER | C | 4707481 |
RK MECHANICAL, LLC | H= | R | 03/21/2014 | NOT READY, NOBODY ONSITE -- MECHANICAL CONTRACTOR NEEDS TO IDENTIFY AREAS LACKING INSPECTIONS AND ACKNOWLEDGE INSPECTIONS NEEDED BASED FROM PREVIOUS NOTE HISTORY. NEED ONSITE CONTACT TO BE PRESENT ALONG WITH ESCORT WHEN NEXT REQUEST IS SCHEDULED. | ROBERTV | ROBERTV | | H= | R | 4706629 |
OTIS ELEVATOR COMPANY | HE | L | 02/21/2014 | Renewed for 1/2 Fee at 2/21/2014 3:06:31 PM (Receipt#1180391) | JESSIE | JESSIE | | HE | L | 4691298 |
RK MECHANICAL, LLC | H= | P | 12/10/2013 | (ENOUGH MECH COMPLETED FOR TCO) -- ALL FIRE AND SMOKE DAMPERS COMPLETED. SEE PREVIOUS NOTES FOR ITEMS REMAINING TO COMPLETE. | ROBERTV | ROBERTV | | H= | P | 4654300 |
RK MECHANICAL, LLC | HD | C | 12/09/2013 | (1ST FLOOR)---ABOVE CEILING OK. RETAINAGE FOR FIRE DAMPERS AT 2HR WALL OK PENDING COMPLETION OF FASTENERS TO PRECAST. SHEETROCK GAP AT MECH ROOM DAMPERS OK FOR RETAINAGE. (2ND FLOOR)--RETAINAGE FOR FIRE DAMPERS AT 2HR WALL OK PENDING COMPLETION OF FASTENERS TO PRECAST. BY FINAL NEED COMPLETED: POOL EXHAUST DUCT AND FAN AT 2ND LEVEL, PVC EXHAUST FOR POOL EQUIPMENT ROOM, DRYER VENT, COMBUSTION AIR AND GAS, TEST AND BALANCE REPORT. | ROBERTV | ROBERTV | | HD | C | 4653916 |
RK MECHANICAL, LLC | HD | P | 12/06/2013 | (1ST FLOOR)--2 HOUR WALL DAMPERS OK FOR RETAINAGE PENDING VERIFICATION OF SHEETROCK GAP INCREASE ON BOTTOM HORIZONTAL PORTION. ALL SMOKE DAMPERS OK PENDING DETAIL FROM ENGINEER SHOWING SMOKE BARRIER CHANGES, 1 HOUR MECH ROOM WALL DAMPER FRAMING OK FOR RETAINAGE PENDING VERIFICATION OF EXPANSION GAP FROM SHEETROCK. (2ND FLOOR)--2 HOUR WALL DAMPER OPENINGS OK FOR RETAINAGE, NEED ACCESS TO DAMPER CURTAINS FOR INSPECTION. NEED DAMPER INSTALLATION INSTRUCTIONS ONSITE FOR NEXT INSPECTION. | ROBERTV | ROBERTV | | HD | P | 4653374 |
RK MECHANICAL, LLC | H= | R | 11/20/2013 | NO PARTIAL H= WILL BE GIVEN UNTIL ALL FIRE/SMOKE DAMPER INSTALLATIONS ARE APPROVED AND COMPLETED, REMAINING DIFFUSERS AND FLEX'S STILL NEED INSPECTED. SEE ALL PREVIOUS NOTES. CONFORMATION OF INSPECTION RESULT WAS COMMUNICATED TO MIKE AND TIM FROM RK MECHANICAL 11-20-2013 @ 9:00 AM | ROBERTV | ROBERTV | | H= | R | 4645019 |
RK MECHANICAL, LLC | H= | R | 11/19/2013 | WHAT NEEDS INSPECTED ??? THIS JOB IS NOT EVEN CLOSE FOR FINAL. NO CALL AHEAD OR POINT OF CONTACT INFO PROVIDED IN INSPECTION REQUEST. COULD NOT CONTACT MIKE CASE. DUE TO UNRESOLVED ISSUES FROM PREVIOUS INSPECTIONS, NO INSPECTIONS WILL BE PERFORMED UNLESS MECHANICAL SUPERVISOR IS ONSITE. PLEASE PROVIDE CONTACT INFO FOR NEXT INSPECTION REQUEST. (INSPECTOR DID NOT MAKE TRIP TODAY) | ROBERTV | ROBERTV | | H= | R | 4644742 |
RK MECHANICAL, LLC | HD | P | 11/07/2013 | (POOL MECH/LAUNDRY ROOM WALL)--SUPPLY FIRE DAMPER NOT FRAMED CORRECTLY, STUDS AND SHEETROCK DESTROYED BY PLUMBING PENETRATIONS, DO NOT PROCEED. NEED GAPS FROM SHEETROCK TO EXHAUST FIRE DAMPER CORRECTED BEFORE RETAINAGE. NEED LETTER AND DRAWING FROM ENGINEER REGARDING MOVED SMOKE BARRIER BEFORE REMAINING DAMPERS ARE OK TO CONCEAL. CHANGES WILL HAVE TO BE NOTED ON SPLICED DRAWING BY FINAL. | ROBERTV | ROBERTV | | HD | P | 4637690 |
RK MECHANICAL, LLC | HI | C | 10/25/2013 | TEST ON REMAINDER OF GAS PIPING TO RTU OK, SEE PREVIOUS HI INSPECTION COMMENTS | ROBERTV | ROBERTV | | HI | C | 4629713 |
RK MECHANICAL, LLC | HD | P | 10/23/2013 | (1ST FLOOR)--TOP AND SIDE DAMPER SAWCUT OPENINGS AT PRE-CAST WALL OK, NEED APPROVED SUPPORTING METHOD FOR BOTTOM SIDE OR FRAME VERTICAL WALL UNDERNEATH TO DAMPER MANUFACTURER INSTALLATION INSTRUCTIONS | ROBERTV | ROBERTV | | HD | P | 4628159 |
RK MECHANICAL, LLC | HD | P | 10/10/2013 | (SEE PLAN PAGE M2.11)-- ALL ABOVE CEILING OK TO CONCEAL EXCEPT AREAS PREVIOUSLY NOTED INVOLVING LAUNDRY, POOL MECH AND POOL CHEM. EXHAUST DAMPER FRAMING AT LAUNDRY WALL OK FOR SHEETROCK, STILL NEED FRAMING INSPECTION ON SUPPLY DAMPER AT SAME WALL. | ROBERTV | ROBERTV | | HD | P | 4620018 |
RK MECHANICAL, LLC | HC | C | 10/09/2013 | RELEASE METER--INCREASING LOAD TO 5,043,000 BTU, UPGRADING TO 2PSI. METER # 159547 | ROBERTV | ROBERTV | | HC | C | 4619608 |
RK MECHANICAL, LLC | HI | P | 10/09/2013 | (SEE PLAN PAGE MG 2.30)--REGULATOR AND CONNECTIONS ON ROOF OK, NEED LABELING COMPLETED ON 2PSI PIPING, NEEDS TO CHECK INSTALLATION OF PIPING FOR RTU. CHECK GAS PIPING FOR DELETED RTU'S AT FINAL. NEED LETTER FROM CSPU REGARDING DELIVERY OF MEDIUM PRESSURE BY FINAL. NEED GAS SCOPE OF WORK LISTED ON THIS PERMIT | ROBERTV | ROBERTV | | HI | P | 4619594 |
RK MECHANICAL, LLC | HD | P | 09/26/2013 | 2-FIRE/SMOKE DAMPERS AT POOL MECH /LAUNDRY ROOM ARE NOT FRAMED CORRECTLY, REFRAME AND CALL INSPECTION BEFORE SHEETROCK. SMOKE DAMPER ABOVE LAUNDRY ROOM ENTRY OK FOR RETAINAGE | ROBERTV | ROBERTV | | HD | P | 4611606 |
RK MECHANICAL, LLC | HD | P | 09/16/2013 | (SEE M2.11)--OK TO WRAP IN GRID AREAS C-D AND 1.4-4, RM 121 OK, MRI ROOM NOT READY YET. QUESTIONING LOCATION OF SMOKE DAMPERS AT SAUNA ROOM WALL WHERE APPROVED PLANS SHOW RATED WALL AT LAUNDRY ROOM. NO EXHAUST OR DAMPERS YET | ROBERTV | ROBERTV | | HD | P | 4605348 |
RK MECHANICAL, LLC | HD | P | 09/09/2013 | (SEE M2.11)-- AREAS OK TO WRAP MEDIUM AND LOW PRESSURE ONLY (GRID LINES 5 WEST AND 1.6 EAST AND A SOUTH TO C NORTH). NEED ALL DAMPER AND EXHAUST INSPECTIONS | ROBERTV | ROBERTV | | HD | P | 4601117 |
COLORADO SHEET METAL CO., INC. | H= | C | 08/13/2013 | THIS CONTRACTOR SCOPE OF WORK COMPLETE | ROBERTV | ROBERTV | | H= | C | 4584466 |
COLORADO SHEET METAL CO., INC. | H= | P | 03/21/2013 | ROOF INSPECTION OK, NEED ELECTRICAL CONTRACTOR ATTACHED TO PERMIT, ALSO NEED ADDITIONAL MECHANICAL CONTRACTOR ATTACHED TO PERMIT FOR REMAINING MECHANICAL SCOPE OF WORK BEFORE FINAL IS GIVEN. (NOTE: PLANS ARE UNDER #I64199) | ROBERTV | ROBERTV | | H= | P | 4491343 |
COLORADO SHEET METAL CO., INC. | HRP | P | 03/08/2013 | RELOCATED CONDENSERS AND PIPING FOR 4-LIEBERT UNITS. #1, #2, #3 AND #4 TEST OK. WILL NEED ROOF INSPECTION AT FINAL. | ROBERTV | ROBERTV | | HRP | P | 4484210 |
RK MECHANICAL, LLC | P= | C | 12/09/2013 | | DICK | DICK | | P= | C | 4653820 |
RK MECHANICAL, LLC | PTO | P | 08/20/2013 | EXISTING BUILDING O.K | JOEL | JOEL | | PTO | P | 4588874 |
RK MECHANICAL, LLC | PRD | P | 08/02/2013 | 6'' REROUTED AT COLUMN | JOEL | JOEL | | PRD | P | 4577156 |
RK MECHANICAL, LLC | PTO | P | 07/29/2013 | 2-VENTS FROM BASEMENT, CHANGING ROOM H2O IN CHASE, POOL THERAPY VENTB AND DRAIN IN WALL O.K | JOEL | JOEL | | PTO | P | 4573656 |
RK MECHANICAL, LLC | PTO | R | 07/26/2013 | NOT READY | JOEL | JOEL | | PTO | R | 4572052 |
RK MECHANICAL, LLC | PTO | P | 07/24/2013 | CMU WALLS DWV AND EAST SIDE SINK NEXT TO POOLS O.K | JOEL | JOEL | | PTO | P | 4570329 |
RK MECHANICAL, LLC | PTO | P | 07/23/2013 | LIBRARY/BREAK ROOM, DENTAL/OPTOMETRY, CHANGING ROOM O.K | JOEL | JOEL | | PTO | P | 4569074 |
RK MECHANICAL, LLC | PRD | P | 06/12/2013 | UNDERGROUND SEE PLANS | JOEL | JOEL | | PRD | P | 4541639 |
RK MECHANICAL, LLC | PB | P | 05/29/2013 | SANITARY TRUNKLINE FOR LOCKER ROOMS O.K | JOEL | JOEL | | PB | P | 4532385 |
RK MECHANICAL, LLC | PB | P | 05/17/2013 | 4-F.DRAINS POOL AREA O.K | JOEL | JOEL | | PB | P | 4525873 |
RK MECHANICAL, LLC | PB | P | 05/15/2013 | | JOEL | JOEL | | PB | P | 4523875 |
RK MECHANICAL, LLC | PB | P | 05/13/2013 | 1-FS O.K ON NORTH END OF THERAPY POOL | JOEL | JOEL | | PB | P | 4522092 |
RK MECHANICAL, LLC | PB | P | 05/09/2013 | 3-F.S IN HYDRO THERAPY AREA | JOEL | JOEL | | PB | P | 4520575 |
RK MECHANICAL, LLC | PB | P | 05/08/2013 | CHANGING ROOM RESTROOM OK | LEE | LEE | | PB | P | 4519506 |
RK MECHANICAL, LLC | PB | P | 05/03/2013 | DENTAL AREA SINK AND FLOOR SINK | JOEL | JOEL | | PB | P | 4516888 |
RK MECHANICAL, LLC | PRD | P | 04/26/2013 | STUB IN WITH 2-RISERS O.K | JOEL | JOEL | | PRD | P | 4512605 |
RK MECHANICAL, LLC | PB | P | 04/26/2013 | NORTHEND TIE IN O.K | JOEL | JOEL | | PB | P | 4512602 |
RK MECHANICAL, LLC | PBS | P | 04/25/2013 | TEST DWV | JOEL | JOEL | | PBS | P | 4511952 |