GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 06/19/2014 | | CHRISM | CHRISM | | B= | C | 4761178 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | R | 02/13/2014 | no one on site from G.E. Johnson, or call ahead phone # | ED | ED | | B= | R | 4686665 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 10/01/2013 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), COLORADO SHEET METAL CO., INC. Mechanical Final Inspection is not Completed yet, GREEN ELECTRIC INC Electrical Final Inspection is not Completed yet, OLSON PLUMBING & HEATING CO Mechanical Final Inspection is not Completed yet. O.R. rooms 1 & 3 ok -- Schedule a new Building Final when above items are complete. | ED | ED | | B= | P | 4614167 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 09/05/2013 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), COLORADO SHEET METAL CO., INC. Mechanical Final Inspection is not Completed yet, GREEN ELECTRIC INC Electrical Final Inspection is not Completed yet, OLSON PLUMBING & HEATING CO Mechanical Final Inspection is not Completed yet. operation rooms 5& 6 ok, rooms 1,2,3,&4 at next phase, pending other inspections -- Schedule a new Building Final when above items are complete. | ED | ED | | B= | P | 4599334 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 07/29/2013 | smoke partitions at operating rooms 5 & 6, above ceiling ok | ED | ED | | BSP | P | 4573356 |
GREEN ELECTRIC INC | BSP | T | 07/22/2013 | PAID (REC#1144613): PLAN SPLICE FEE: $50 by: SHELBY for Electrical | SHELBY | SHELBY | | BSP | T | 4568863 |
COLORADO SHEET METAL CO., INC. | BSP | T | 07/22/2013 | PAID (REC#1143958): PLAN SPLICE FEE: $50 by: RUSSELL for Mechanical: Changes to fire evacuation system. | RUSSELL | RUSSELL | | BSP | T | 4568840 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 06/03/2013 | walls ok pending other roughs | CHRISM | CHRISM | | BFR | P | 4535022 |
GREEN ELECTRIC INC | E= | C | 01/31/2014 | O.R. rooms 5 and 6 | BRIAN | BRIAN | | E= | C | 4681126 |
GREEN ELECTRIC INC | E= | C | 10/21/2013 | FIRE ALARM INSPECTION: | MATTHEW | MATTHEW | | E= | C | 4626346 |
GREEN ELECTRIC INC | ER | C | 10/21/2013 | FIRE ALARM INSPECTION: dampers and ex-fans for op rooms | MATTHEW | MATTHEW | | ER | C | 4626345 |
GREEN ELECTRIC INC | E= | C | 10/21/2013 | FIRE ALARM INSPECTION: | MATTHEW | MATTHEW | | E= | C | 4626335 |
GREEN ELECTRIC INC | E= | P | 09/04/2013 | or rooms 05 and 06 ---see drawings | BRIAN | BRIAN | | E= | P | 4597923 |
GREEN ELECTRIC INC | ER | C | 07/29/2013 | ceiling rough and 3 new 100 amp panels ok | MATTHEW | MATTHEW | | ER | C | 4573346 |
GREEN ELECTRIC INC | ER | P | 07/29/2013 | FIRE ALARM INSPECTION: phase 1--- both operating rooms fire alarm rough ok | MATTHEW | MATTHEW | | ER | P | 4573336 |
GREEN ELECTRIC INC | ER | P | 06/03/2013 | walls only in rooms 5 and 6 | GARYL | GARYL | | ER | P | 4535116 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 02/05/2014 | MECHANICAL PIPING FINAL OK. | NANCY | NANCY | | H= | C | 4683556 |
COLORADO SHEET METAL CO., INC. | H= | C | 01/30/2014 | TEST AND BALANCE REPORTS AND LETTERS APPROVING REPORTS RECEIVED AND SCANNED. | NANCY | NANCY | | H= | C | 4681069 |
COLORADO SHEET METAL CO., INC. | H= | P | 10/23/2013 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4627574 |
COLORADO SHEET METAL CO., INC. | HD | P | 09/18/2013 | OR1 AND 0R3: TWO MOTORIZED DAMPERS IN RETURN AIR DUCTS INSTALLED. SMOKE EVAC IN CEILING INSTALLED. | NANCY | NANCY | | HD | P | 4606640 |
OLSON PLUMBING & HEATING COMPANY | H= | P | 07/29/2013 | INSTALL STERILIZER. COMPLETE INSULATION AND LABELING. | NANCY | NANCY | | H= | P | 4573177 |
COLORADO SHEET METAL CO., INC. | HD | P | 07/26/2013 | OR 5, OR 6, EQUIPMENT ROOMS FOR OR 5 AND 6: ABOVE CEILING ALL OK. SMOKE EVACUATION: SMOKE EVAC FOR OR 5 AND 6: ABOVE CEILING AT FAN TO OUTSIDE WALL OK. SMOKE EVAC FOR OR 1 AND 3: OK FROM OR'S TO FAN. NEED REVISED/APPROVED PRINTS SHOWING SMOKE EVAC SYSTEM. | NANCY | NANCY | | HD | P | 4572256 |
COLORADO SHEET METAL CO., INC. | HD | P | 07/12/2013 | OR 6: SUPPLY LATERALS OK, OK TO WRAP. | NANCY | NANCY | | HD | P | 4562457 |
COLORADO SHEET METAL CO., INC. | HD | P | 07/08/2013 | OR 5: SUPPLY LATERALS OK, OK TO WRAP. HUMIDIFIERS 2-8 AND 2-9: INSTALLATION IN DUCTS OK. OK TO WRAP. STERILIZATION 2276 AND 2272: EXHAUST OK. SUPPLIES ROOMS 2236 AND 2274: SUPPLY/RETURN/EXHAUST ABOVE CEILING OK, OK TO WRAP SUPPLIES. EQUIPMENT CABINETS: TWO 10 INCH ROUND RETURNS TO EQUIPMENT CABINETS OK. | NANCY | NANCY | | HD | P | 4558762 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 06/24/2013 | test ok on low pressure steam lines | JON | JON | | HWP | P | 4549446 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 06/18/2013 | HUMIDIFIERS: LOW TEST ON STEAM LINES. 100 LB TEST OK ON CONDENSATE LINES, OK TO INSULATE. STERILIZER: 100 LB TEST OK ON STEAM LINE AND CONDENSATE LINE. OK TO INSULATE. | NANCY | NANCY | | HWP | P | 4545084 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 06/17/2013 | CANCELED AT CALL AHEAD. ALREADY RESCHEDULED FOR TOMORROW. | NANCY | NANCY | | HWP | P | 4544670 |
COLORADO SHEET METAL CO., INC. | HD | P | 05/30/2013 | BY FINAL NEED ACCURATE SCOPE OF WORK LISTED, MORE THAN ONE DUCT BEING INSTALLED HERE. OR 5 AND OR 6: SUPPLY TRUNKS OK, OK TO WRAP. RETURN AIR DUCTS IN ENCLOSURES OK, OK TO COVER. | NANCY | NANCY | | HD | P | 4533590 |
OLSON PLUMBING & HEATING COMPANY | PTO | C | 07/29/2013 | | TIM | TIM | | PTO | C | 4573482 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 07/29/2013 | | TIM | TIM | | P= | C | 4573476 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 06/27/2013 | Sterile room complete. | JACK | JACK | | PTO | P | 4552112 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 06/03/2013 | in walls ok o.r. 6 | TIM | TIM | | PTO | P | 4535211 |