PCL CONSTRUCTION SERVICES, INC | B= | C | 11/18/2013 | All other required Final inspections are complete. (This is a computer generated result) | BERTW | BERTW | | B= | C | 4643220 |
PCL CONSTRUCTION SERVICES, INC | B= | P | 06/27/2013 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), HEATING & PLUMBING ENGRS, INC Mechanical Final Inspection is not Completed yet, HEATING & PLUMBING ENGRS, INC Plumbing Final Inspection is not Completed yet. | BERTW | BERTW | | B= | P | 4552117 |
PCL CONSTRUCTION SERVICES, INC | BFR | C | 06/27/2013 | | BERTW | BERTW | | BFR | C | 4552116 |
PCL CONSTRUCTION SERVICES, INC | BSP | P | 06/27/2013 | penetrations sealed ok at perimeter walls of this scope of work | BERTW | BERTW | | BSP | P | 4552115 |
PCL CONSTRUCTION SERVICES, INC | BFR | L | 06/26/2013 | no call ahead # provided | BERTW | BERTW | | BFR | L | 4551046 |
PCL CONSTRUCTION SERVICES, INC | BFR | P | 06/07/2013 | framing ok/revised plan on file/pending mech inspections | BERTW | BERTW | | BFR | P | 4538540 |
PCL CONSTRUCTION SERVICES, INC | BFR | R | 05/30/2013 | same condition as previous inspection/need architect to approve as built framing conditions for smoke damper support wall not built per plans-no supporting construction for smoke partition | BERTW | BERTW | | BFR | R | 4532954 |
PCL CONSTRUCTION SERVICES, INC | BFR | P | 05/23/2013 | interior room dividing walls only ok pending other roughs complted/restroom wall is a smoke partition and not built for continuity requirements to underside of deck above due to a roof drain pipe in the way/will need stamped revised plan for new framing and smoke damper framing inspection | BERTW | BERTW | | BFR | P | 4529396 |
GREINER ELECTRIC, LLC. | E= | C | 06/10/2013 | still need F/A inspections | CRAIGS | CRAIGS | | E= | C | 4539793 |
GREINER ELECTRIC, LLC. | ER | C | 06/07/2013 | PLEASE LEAVE A POINT OF CONTACT # --above ceiling electrical only | CRAIGS | CRAIGS | | ER | C | 4539320 |
GREINER ELECTRIC, LLC. | ER | P | 05/20/2013 | walls emt with equipment ground. | BRET | BRET | | ER | P | 4526583 |
HEATING & PLUMBING ENGINEERS, INC | H= | C | 11/18/2013 | TEST AND BALANCE REPORT RECEIVED | ROBERTV | ROBERTV | | H= | C | 4643219 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 07/03/2013 | SMOKE DAMPER SHUTDOWN AND OPERATION IS COMPLETE, REST OK. NEED TEST AND BALANCE REPORT | ROBERTV | ROBERTV | | H= | P | 4557260 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 06/25/2013 | OK FOR REMAINING INSULATION AND TILES, LEAVE TILES OUT BY SMOKE DAMPER. NEED SMOKE DAMPER OPERATIONAL TO INSPECT CLOSURE AND TIGHTNESS. PLEASE COORDINATE METHOD FOR TESTING ON NEXT INSPECTION. NEED TEST AND BALANCE | ROBERTV | ROBERTV | | H= | P | 4549971 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 06/14/2013 | INSPECTION WAS FOR SMOKE DAMPER, NEED TO ENSURE SMOKE DAMPER CLOSES DUE TO INSTALLATION IN WALL FRAMING AND NOT INSTALLED IN A DUCT. PROPERLY SEAL DAMPER FOR PASSAGE OF SMOKE AROUND DAMPER OPENING IN WALL PER INSTRUCTIONS FOR SEALING, LEAVE OPEN FOR INSPECTION ON DROP CEILING SIDE. | JON | JON | | HD | P | 4543469 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 06/13/2013 | CALL AHEAD INDICATED NOBODY WAS ONSITE, PLEASE RESCHEDULE | ROBERTV | ROBERTV | | HD | P | 4543021 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 05/15/2013 | SUPPLY DUCTS OK TO INSULATE, EF DUCTING OK. GC AND CONTRACTOR TO DISCUSS WITH ENGINEER ABOUT LOCATION OF SMOKE DAMPER WITH CONFLICTING ROOF DRAIN PIPING | ROBERTV | ROBERTV | | HD | P | 4523897 |
HEATING & PLUMBING ENGINEERS, INC | P= | C | 06/28/2013 | | JOEL | JOEL | | P= | C | 4553249 |
HEATING & PLUMBING ENGINEERS, INC | P= | R | 06/25/2013 | CONTRACTOR CANCELLED | JOEL | JOEL | | P= | R | 4550076 |
HEATING & PLUMBING ENGINEERS, INC | P= | R | 06/21/2013 | WAIVE TRIP FEE, NEED ACCESS TO COMPLETE PTO | JOEL | JOEL | | P= | R | 4548017 |
HEATING & PLUMBING ENGINEERS, INC | P= | R | 06/20/2013 | PTO NOT COMPLETE, CONTRACTOR CANCELLED | JOEL | JOEL | | P= | R | 4546828 |
HEATING & PLUMBING ENGINEERS, INC | PTO | P | 05/23/2013 | 3RD FLOOR O.K | JOEL | JOEL | | PTO | P | 4529449 |
HEATING & PLUMBING ENGINEERS, INC | PTO | R | 05/22/2013 | CONTRACTOR CANCELLED | JOEL | JOEL | | PTO | R | 4528481 |