J. E. DUNN CONSTRUCTION COMPANY | B= | C | 04/24/2014 | All other required Final inspections are complete. (This is a computer generated result) | ED | ED | | B= | C | 4726108 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | BSP | P | 01/31/2014 | PLAN SPLICE: (No Fee) by: DOUG for Electrical | DOUG | DOUG | | BSP | P | 4681665 |
J. E. DUNN CONSTRUCTION COMPANY | B= | P | 12/05/2013 | Additional Inspections Required: BERWICK ELECTRIC CO Electrical Final Inspection is not Completed yet. building side ok, pending electrical final | ED | ED | | B= | P | 4652947 |
COLORADO SHEET METAL CO., INC. | BSP | T | 11/15/2013 | PAID (REC#1167020) PLAN SPLICE FEE: $50 by: DALEH for Mechanical | DALEH | DALEH | | BSP | T | 4642392 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 11/13/2013 | fire caulking and rated labeling above ceilings ok | ED | ED | | BSP | P | 4640775 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 10/31/2013 | building side ok, pending electrical. | ED | ED | | BFR | P | 4633182 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 10/23/2013 | inspections assigned to Chris | BLAKE | BLAKE | | BSP | P | 4627809 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 04/24/2014 | load justification ok | MATTHEW | MATTHEW | | E= | C | 4726107 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 04/23/2014 | 2 different loads are being shown for panel---- need to talk to plan check---- call me in the am | MATTHEW | MATTHEW | | E= | P | 4725468 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 12/02/2013 | need gfci protection 6' from sink----------------------- plans need to be resubmitted: circuits shown fed from CL2B are being fed from CL2C----- panel NL2B has more circuits fed from it than approved plans show (148 amp load), panel NL2B is shown as 150 amp panel but is listed as 125 amp max --------- | MATTHEW | MATTHEW | | E= | P | 4650048 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 11/19/2013 | ceilings ok in 2nd floor doctor lounge | TOMC | TOMC | | ER | P | 4644875 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 10/31/2013 | walls in physicians lounge area second floor | MATTHEW | MATTHEW | | ER | P | 4633651 |
COLORADO SHEET METAL CO., INC. | H= | C | 12/03/2013 | TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 4651962 |
COLORADO SHEET METAL CO., INC. | H= | P | 11/19/2013 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4644187 |
COLORADO SHEET METAL CO., INC. | HD | P | 10/28/2013 | BY FINAL NEED REVISED/APPROVED PRINTS. SUPPLY/RETURN/EXHAUST ROUGH DUCTS OK. OK TO WRAP SUPPLY/RETURN. NO FLEX OR DIFFUSERS YET. | NANCY | NANCY | | HD | P | 4630921 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 12/02/2013 | | JOEL | JOEL | | P= | C | 4650163 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 11/06/2013 | check tie-ins at final, rest o.k | JOEL | JOEL | | PTO | P | 4636830 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 10/25/2013 | DWV AND WATER IN WALL OK. | DICK | DICK | | PTO | P | 4629307 |