J. E. DUNN CONSTRUCTION COMPANY | B= | C | 11/03/2014 | All other required Final inspections are complete. (This is a computer generated result) | DAN | DAN | | B= | C | 4847575 |
J. E. DUNN CONSTRUCTION COMPANY | B= | P | 06/04/2014 | Additional Inspections Required: BERWICK ELECTRIC CO Electrical Final Inspection is not Completed yet, COLORADO SHEET METAL CO., INC. Mechanical Final Inspection is not Completed yet. 2nd floor locker room locker rooms, storage room and 2 offices OK | DAN | DAN | | B= | P | 4751122 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 05/07/2014 | above grid ok in office and locker rooms | CHRISM | CHRISM | | BSP | P | 4734222 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 04/22/2014 | walls ok pending other roughs | CHRISM | CHRISM | | BFR | P | 4724422 |
J. E. DUNN CONSTRUCTION COMPANY | B= | P | 04/01/2014 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), BERWICK ELECTRIC CO Electrical Final Inspection is not Completed yet, COLORADO SHEET METAL CO., INC. Mechanical Final Inspection is not Completed yet. partail for PREOP area ok pending other finals | CHRISM | CHRISM | | B= | P | 4712399 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 03/06/2014 | above grid ok, periop area | CHRISM | CHRISM | | BFR | P | 4698005 |
COLORADO SHEET METAL CO., INC. | BSP | T | 01/31/2014 | PAID (REC#1180588) PLAN SPLICE FEE: $50 by: DALEH for Mechanical | DALEH | DALEH | | BSP | T | 4681275 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 01/27/2014 | wall framing / floor penitrations ok | ED | ED | | BFR | P | 4677917 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 01/22/2014 | shaft framing ok, see sheet A111 for area inspected | ED | ED | | BSP | P | 4675794 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 09/22/2014 | FIRE ALARM INSPECTION: fire alarm rough ok | MATTHEW | MATTHEW | | E= | C | 4820056 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 06/06/2014 | | MATTHEW | MATTHEW | | E= | C | 4753099 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 05/30/2014 | offices and locker room--------- still need to final dictation room------------ dictation room wall rough inspected by brian under permit J06002 | MATTHEW | MATTHEW | | E= | P | 4748482 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 05/12/2014 | ceilings marked on plans ok | MATTHEW | MATTHEW | | ER | P | 4736706 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 04/28/2014 | CORRECTIONS TO LIGHTS SWITCHES--- | BRIAN | BRIAN | | ER | P | 4728363 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 04/22/2014 | walls in 2 offices and locker room-------- missing switches in office furthest from locker room | MATTHEW | MATTHEW | | ER | P | 4724496 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 04/22/2014 | FIRE ALARM INSPECTION: strobe in locker room | MATTHEW | MATTHEW | | ER | P | 4724484 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 04/02/2014 | CORRECTION MADE-- | BRIAN | BRIAN | | E= | P | 4713034 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 04/02/2014 | FIRE ALARM INSPECTION: OK PER MATT TO PARTIAL 1ST PHASE | BRIAN | BRIAN | | E= | P | 4713029 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 04/02/2014 | FIRE ALARM INSPECTION: OK PER MATT TO PARTIAL 1ST PHASE | BRIAN | BRIAN | | ER | P | 4713028 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 03/31/2014 | all corrections made----cry rooms designated critical bed locations-------------- need fire alarm permit pulled ---fire alarm rough ok | MATTHEW | MATTHEW | | E= | P | 4711816 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | R | 03/24/2014 | gfci 6' from nurses sink, replace cord with approved wiring in ceiling for light booms, can't have multi conductor circuits at bed locations------ need bed locations defined as general or critical (emergency circuits supply more than one bed location), label ups panel | MATTHEW | MATTHEW | | E= | R | 4707132 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 03/11/2014 | grid and above grid OK---Wiring for two booms needs to be checked on final (branch circuit and interconnection) | SHELBY | SHELBY | | ER | P | 4700675 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 01/27/2014 | walls and hard lid 2nd floor Perioperative service | TOMC | TOMC | | ER | P | 4678110 |
COLORADO SHEET METAL CO., INC. | H= | C | 11/03/2014 | TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 4847574 |
COLORADO SHEET METAL CO., INC. | H= | P | 05/23/2014 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4744489 |
COLORADO SHEET METAL CO., INC. | HD | P | 05/15/2014 | Phase 2: Above ceiling all ok except need to install VAV above OR. | NANCY | NANCY | | HD | P | 4739811 |
COLORADO SHEET METAL CO., INC. | HD | P | 05/05/2014 | PHASE 2: ROUGH DUCTS AND LATERALS ALL OK, OK TO WRAP. NO FLEX OR DIFFUSERS YET, HARD PIPE ONLY TO BE INSTALLED IN STORAGE ROOM. PHASE 1: ALL COMPLETE. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | HD | P | 4732708 |
COLORADO SHEET METAL CO., INC. | HD | P | 02/26/2014 | ISOLATION EXHAUST INSTALLED AS PER MECHANICAL SPLICE DATED 1/31/14. | NANCY | NANCY | | HD | P | 4693832 |
COLORADO SHEET METAL CO., INC. | HD | P | 02/25/2014 | SHEET M402.3D. CIRCLED AREA ALL OK EXCEPT NEED HARD PIPE INSTALLED IN CLEAN ROOM 2009. INSTALL ACCESS DOOR AND LABEL GRID FOR ISOLATION EXHAUST SMOKE DAMPER. BY FINAL NEED REVISED/APPROVED PRINTS FOR ISOLATION EXHAUST. | NANCY | NANCY | | HD | P | 4692785 |
COLORADO SHEET METAL CO., INC. | HD | P | 01/16/2014 | SHEET M402.3D. ABOVE CEILING ALL OK. QUESTION REGARDING DUCT PENETRATIONS THROUGH FIRE BARRIERS WITH NO PROTECTION. | NANCY | NANCY | | HD | P | 4673211 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 03/14/2014 | | TIM | TIM | | P= | C | 4702511 |
OLSON PLUMBING & HEATING COMPANY | PTO | C | 03/06/2014 | | DICK | DICK | | PTO | C | 4698136 |
OLSON PLUMBING & HEATING COMPANY | PTO | L | 02/28/2014 | cancelled by Randy. | DICK | DICK | | PTO | L | 4694891 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 01/24/2014 | 3-SINKS ON 2ND FLOOR O.K. CHANGE PERMIT DETAILS TO 5 SINKS | JOEL | JOEL | | PTO | P | 4677490 |