J. HAHN CONSTRUCTION, LLC | B= | C | 11/20/2014 | Wrecking permit complete. | ROGER | ROGER | | B= | C | 4857712 |
J. HAHN CONSTRUCTION, LLC | B= | P | 10/06/2014 | still need W= permit | DALE | DALE | | B= | P | 4829123 |
J. HAHN CONSTRUCTION, LLC | B= | P | 09/05/2014 | ballisters spacing (6") between, add graspable handrail, condition crawl space insulation (foam) needs to be covered, insulation not up to top of foundation wall, went this homeowner and contractor -- Schedule a new Building Final when above items are complete. | ED | ED | | B= | P | 4810678 |
J. HAHN CONSTRUCTION, LLC | B= | P | 08/04/2014 | Temp CO: per Dale ( Expires: 9/3/2014 12:00:00 AM) | BPHILLIPS | BPHILLIPS | | B= | P | 4789147 |
J. HAHN CONSTRUCTION, LLC | B= | P | 07/29/2014 | Additional Inspections Required: External Agency Inspection HD= by HEALTHDEPT is not Completed yet, Electrical Final Inspection is not Completed yet, Plumbing Final Inspection is not Completed yet. complete all other inspections / permenant house # / complete poly, insulation and door at crawl space / continous handrail / swale for rain -- Schedule a new Building Final when above items are complete. | DALE | DALE | | B= | P | 4785946 |
J. HAHN CONSTRUCTION, LLC | BFR | C | 05/28/2014 | | CHRISM | CHRISM | | BFR | C | 4746713 |
J. HAHN CONSTRUCTION, LLC | BIN | C | 05/27/2014 | | CHRISM | CHRISM | | BIN | C | 4745653 |
J. HAHN CONSTRUCTION, LLC | BFR | C | 05/27/2014 | | CHRISM | CHRISM | | BFR | C | 4745652 |
J. HAHN CONSTRUCTION, LLC | BFR | P | 05/19/2014 | eng letter on file, complete rafter connections, back rock fan boxes, ok to insulate | CHRISM | CHRISM | | BFR | P | 4741119 |
J. HAHN CONSTRUCTION, LLC | BFR | R | 05/09/2014 | ok to insulate, splice plan change for TJI size, eng letter for three stacked plates and post changes in garage, wrap steel columns in garage, remove fan boxes in garage to house wall, 2x6 header at mudroom door, H2.5s at all rafter bearing, storage over mudroom not on plans, attic access in master bedroom end | CHRISM | CHRISM | | BFR | R | 4735931 |
J. HAHN CONSTRUCTION, LLC | BLA | C | 05/01/2014 | | CHRISM | CHRISM | | BLA | C | 4731065 |
J. HAHN CONSTRUCTION, LLC | BLA | R | 04/24/2014 | not complete at front of garage and inside courtyard rest ok | CHRISM | CHRISM | | BLA | R | 4726736 |
J. HAHN CONSTRUCTION, LLC | BSP | P | 04/11/2014 | main floor framing ok, second floor need eng to approve change from 11 7/8" TJI to 9 1/2" TJI | CHRISM | CHRISM | | BSP | P | 4718947 |
J. HAHN CONSTRUCTION, LLC | BSP | P | 03/25/2014 | deck and porch piers ok | CHRISM | CHRISM | | BSP | P | 4708019 |
J. HAHN CONSTRUCTION, LLC | BFD | C | 12/12/2013 | | CHRISM | CHRISM | | BFD | C | 4655894 |
J. HAHN CONSTRUCTION, LLC | BFN | C | 11/18/2013 | design and soils on file drain usable isolate and float | CHRISM | CHRISM | | BFN | C | 4643929 |
J. HAHN CONSTRUCTION, LLC | BFT | C | 11/06/2013 | 2600# bearing | CHRISM | CHRISM | | BFT | C | 4636548 |
J. HAHN CONSTRUCTION, LLC | BFT | P | 11/05/2013 | footer and pads ok, need open hole | CHRISM | CHRISM | | BFT | P | 4636106 |
SPACCAMONTI ELECTRIC,LLC | E= | C | 08/28/2014 | corrections made | TOMC | TOMC | | E= | C | 4806430 |
SPACCAMONTI ELECTRIC,LLC | E= | P | 08/01/2014 | gfci protect back exterior outlets, add outlet at sink in upper bathroom, remove insulation around 4/0 al ser feeder in crawler or derate breaker to 150 amps, label MAU nameplate, guard crawler lights, 4-3 nm rated 70 amps max at generator------------50 amp a/c ok | MATTHEW | MATTHEW | | E= | P | 4789006 |
SPACCAMONTI ELECTRIC,LLC | E= | R | 07/28/2014 | complete re-inspect------- correct spacing around back door, correct countertop spacing, wire a/c, install arc shields, nm hanging, a/c not wired, ground generator j-box, in-use covers upside down---- this is partial list; complete re-inspect---------- matt must do inspection | MATTHEW | MATTHEW | | E= | R | 4785309 |
SPACCAMONTI ELECTRIC,LLC | ES | C | 06/06/2014 | Residential Underground: 200 amp 3/w new res. seal meter
note couldn't fine ufer, have contractor locate ufer by final | CRAIG | CRAIG | | ES | C | 4753319 |
SPACCAMONTI ELECTRIC,LLC | ES | R | 05/15/2014 | still need wires landed at pedestal and ufer | MATTHEW | MATTHEW | | ES | R | 4739481 |
SPACCAMONTI ELECTRIC,LLC | ER | C | 05/15/2014 | | MATTHEW | MATTHEW | | ER | C | 4739478 |
SPACCAMONTI ELECTRIC,LLC | ER | R | 05/12/2014 | still need outlets in loft and upstairs bedroom, wirenut grounds at lights----------- 2 sub-panles in garage: 3-15 and 2-20 in left sub and 3-15 and 3-20 in right sub----------------- contractor needs to verify spacing in kitchen and at back slider | MATTHEW | MATTHEW | | ER | R | 4736947 |
SPACCAMONTI ELECTRIC,LLC | ES | R | 05/12/2014 | need wires landed in pedestal, need ufer ground------------------ verify 4/0 al will not be in insulation thru crawler | MATTHEW | MATTHEW | | ES | R | 4736942 |
SPACCAMONTI ELECTRIC,LLC | EUG | C | 05/09/2014 | service lateral from pedestal location to house---------- grade needs to be at top of concrete pad by house at final | MATTHEW | MATTHEW | | EUG | C | 4736257 |
SPACCAMONTI ELECTRIC,LLC | ER | R | 05/01/2014 | correct spacing thru out, need sub-panel installed, panels in area separation wall, make up grounds at lights and smokes, ground pan box, wiring removed in kitchen, box not made up in garage -------------- 4/0 al feeder will need to be derated if insulation is installed in crawl space | MATTHEW | MATTHEW | | ER | R | 4731029 |
GENE'S HEATING AND AIR LLC | H= | C | 07/28/2014 | Corrections made. | JEFFL | JEFFL | | H= | C | 4785257 |
BROOKS PLUMBING & HEATING INC. | H= | P | 07/25/2014 | Drain not complete to AC coil. Hole needs sealed by condenser. Rest ok. High/low combustion air from exterior to boiler. | JEFFL | JEFFL | | H= | P | 4784347 |
A#1 BUILDING COMFORT | HWP | C | 07/25/2014 | | JEFFL | JEFFL | | HWP | C | 4784328 |
GENE'S HEATING AND AIR LLC | HC | C | 05/02/2014 | RELEASE METER | MARK | MARK | | HC | C | 4731729 |
GENE'S HEATING AND AIR LLC | HRR | C | 05/02/2014 | HWP system. Boiler not in at time of inspection. Fireplace the same. Will need to check vent and connectors at final check for louver doors at mech closet. Has transfer grill above door to house. | MARK | MARK | | HRR | C | 4731723 |
GENE'S HEATING AND AIR LLC | HRR | R | 05/01/2014 | No approved mechanical plans found on site. There are two places these are to be placed. Either on the mechanical equipment or in the permit pouch. Trip waived this time. | MARK | MARK | | HRR | R | 4730859 |
A#1 BUILDING COMFORT | HWP | P | 04/28/2014 | Low pressure test. Rest ok. Notes-- pex stapled up. | JEFFL | JEFFL | | HWP | P | 4728288 |
A#1 BUILDING COMFORT | HWP | L | 04/25/2014 | GATE LOCKED | JERRYF | JERRYF | | HWP | L | 4727170 |
BROOKS PLUMBING & HEATING INC. | HI | C | 04/14/2014 | 10lb test ok. 1 1/2" main. Boiler, generator, gas stove, grill. | MARK | MARK | | HI | C | 4720152 |
JAZY-FREI PLUMBING & HEATING INC | HO | C | 02/28/2014 | #30 test on #60 gauge ok. Note: 2" new to old PE pipe from riser at house to meter at street. Need 2lb letter??? | MARK | MARK | | HO | C | 4695579 |
MISSION PLUMBING & HEATING | P= | C | 07/30/2014 | POTABLE WATER CERT TO SCANNING . NOTE . CRAWL SPACE NO IRRIGATION | GABE | GABE | | P= | C | 4786885 |
MISSION PLUMBING & HEATING | P= | P | 07/29/2014 | PENDING POTABLE WATER CERT . AND DISHWASHER WASTE TO CODE | GABE | GABE | | P= | P | 4786026 |
MISSION PLUMBING & HEATING | P= | P | 07/28/2014 | dishwasher drain not to code, need potable cert....rest ok no sprinkler | TIM | TIM | | P= | P | 4784982 |
MISSION PLUMBING & HEATING | PTO | C | 04/16/2014 | CORRECTIONS MADE | GABE | GABE | | PTO | C | 4721176 |
MISSION PLUMBING & HEATING | PTO | L | 04/15/2014 | FIELD CANCEL | GABE | GABE | | PTO | L | 4720295 |
HOMEOWNER | PWO | C | 03/17/2014 | need certificate of potable water by final | TED | TED | | PWO | C | 4703800 |