ELEVATION HOMES, LLC | B= | C | 04/25/2014 | | CHRISM | CHRISM | | B= | C | 4727249 |
ELEVATION HOMES, LLC | BIN | C | 02/26/2014 | | ED | ED | | BIN | C | 4693739 |
ELEVATION HOMES, LLC | BFR | C | 02/24/2014 | | CHRISM | CHRISM | | BFR | C | 4691813 |
ELEVATION HOMES, LLC | BLA | P | 02/13/2014 | ok all but at deck columns not fiinished | CHRISM | CHRISM | | BLA | P | 4686831 |
ELEVATION HOMES, LLC | BSP | P | 02/07/2014 | front and rear porch roofs and posts ok | CHRISM | CHRISM | | BSP | P | 4684110 |
ELEVATION HOMES, LLC | BFI | C | 12/17/2013 | R-10 at walkout walls | CHRISM | CHRISM | | BFI | C | 4658002 |
ELEVATION HOMES, LLC | BFD | C | 12/17/2013 | soils on file drain usable isolate and float | CHRISM | CHRISM | | BFD | C | 4658001 |
ELEVATION HOMES, LLC | BFN | C | 12/17/2013 | design and eng report on file | CHRISM | CHRISM | | BFN | C | 4658000 |
ELEVATION HOMES, LLC | BFT | C | 12/17/2013 | eng report on file | CHRISM | CHRISM | | BFT | C | 4657999 |
ELEVATION HOMES, LLC | BFN | P | 11/20/2013 | AUTHORIZED INSPECTION BY ENGINEER | TERRI | TERRI | TERRI | BFN | P | 4645855 |
ELEVATION HOMES, LLC | BFT | P | 11/20/2013 | AUTHORIZED INSPECTION BY ENGINEER | TERRI | TERRI | TERRI | BFT | P | 4645854 |
HOMERUN ELECTRONICS, INC. | E= | C | 04/18/2014 | | MATTHEW | MATTHEW | | E= | C | 4723283 |
HOMERUN ELECTRONICS, INC. | E= | R | 04/17/2014 | ground island boxes, provide means to check oh doors and x-mas outlets, can't use cord cap on cooktop whip (hard wire and add breaker lock), correct closet light clearance in master closet --------a/c and hot tub pre-wire--------- | MATTHEW | MATTHEW | | E= | R | 4722533 |
HOMERUN ELECTRONICS, INC. | ER | C | 02/20/2014 | | MATTHEW | MATTHEW | | ER | C | 4690519 |
HOMERUN ELECTRONICS, INC. | ES | C | 02/19/2014 | Residential Overhead: 200 amp 3/w: new res------ meter is set; need seal | MATTHEW | MATTHEW | | ES | C | 4689872 |
HOMERUN ELECTRONICS, INC. | ER | R | 02/19/2014 | nail plate theater room top plate, bond equipment ground to sub-panel, hot tub circuit can't be fed from sub-panel (al feeder), staple nm at oven and in basement bath ceiling to keep inside wall, missing wiring to master deck outlet---------------- finished basement, 6-3 nm to double oven, #6al to oven | MATTHEW | MATTHEW | | ER | R | 4689870 |
HOMERUN ELECTRONICS, INC. | EUG | C | 01/02/2014 | service lateral to home | MATTHEW | MATTHEW | | EUG | C | 4665516 |
BRUNO'S HEATING & COOLING | H= | C | 04/16/2014 | Notes-- high/low transfer grills. | JEFFL | JEFFL | | H= | C | 4721674 |
BRUNO'S HEATING & COOLING | HC | C | 02/19/2014 | RELEASE METER | TED | TED | | HC | C | 4689766 |
BRUNO'S HEATING & COOLING | HRR | C | 02/19/2014 | finished basement, a/c rough, outside air to return, duct design | TED | TED | | HRR | C | 4689752 |
DOUBLE J GAS, INC. | HI | C | 02/18/2014 | 1 1/4'' furnace, w/h, 2-fireplaces, range, bbq | TED | TED | | HI | C | 4688426 |
BRUNO'S HEATING & COOLING | HRR | R | 02/18/2014 | no design plan found, waive trip fee, had another inspection at same house | TED | TED | | HRR | R | 4688421 |
PACIFIC PLUMBING, INCORPORATED | P= | C | 04/14/2014 | BASEMENT SHOWER AND TOILET ARE ROUGH ONLY / HOME OWNER TO COMPLETE AT A LATER DATE | GABE | GABE | | P= | C | 4719564 |
PACIFIC PLUMBING, INCORPORATED | P= | P | 04/11/2014 | HI LOOP REQUIRED AT BASEMENT DISH WASHER, SET TOILET AND FINISH SHOWER IN BASEMENT FOR FINAL . NOTE : PVB INSTALLED | GABE | GABE | | P= | P | 4718776 |
HOMEOWNER | PWO | C | 02/10/2014 | | JOEL | JOEL | | PWO | C | 4684921 |
PACIFIC PLUMBING, INCORPORATED | PTO | C | 02/07/2014 | finished basement | JOEL | JOEL | | PTO | C | 4684298 |
PACIFIC PLUMBING, INCORPORATED | PB | C | 12/20/2013 | | TIM | TIM | | PB | C | 4661307 |