DOUBLE DIAMOND HOMES, INC. | B= | C | 06/13/2014 | | CHRISM | CHRISM | | B= | C | 4757607 |
DOUBLE DIAMOND HOMES, INC. | B= | R | 06/11/2014 | Additional Inspections Required: External Agency Inspection HD= by HEALTHDEPT is not Completed yet. handrail at garage steps, step off landing at service door, secure egress ladder, CO detector at south basement bedrooms | CHRISM | CHRISM | | B= | R | 4755791 |
DOUBLE DIAMOND HOMES, INC. | BLA | C | 03/17/2014 | | CHRISM | CHRISM | | BLA | C | 4703698 |
DOUBLE DIAMOND HOMES, INC. | BIN | C | 03/12/2014 | | CHRISM | CHRISM | | BIN | C | 4700911 |
DOUBLE DIAMOND HOMES, INC. | BFR | C | 03/12/2014 | | CHRISM | CHRISM | | BFR | C | 4700909 |
DOUBLE DIAMOND HOMES, INC. | BFR | P | 03/11/2014 | firestop top of chase in corner of kitchen , card board is not firestop material | CHRISM | CHRISM | | BFR | P | 4700484 |
DOUBLE DIAMOND HOMES, INC. | BFR | P | 03/10/2014 | ok to insulate, strap stair landing to floor above, finish draftstop | CHRISM | CHRISM | | BFR | P | 4699890 |
DOUBLE DIAMOND HOMES, INC. | BSP | P | 03/07/2014 | met with contractor about electric panel in common wall | CHRISM | CHRISM | | BSP | P | 4699012 |
DOUBLE DIAMOND HOMES, INC. | BSP | P | 01/09/2014 | deck piers ok | CHRISM | CHRISM | | BSP | P | 4668926 |
DOUBLE DIAMOND HOMES, INC. | BSP | P | 01/07/2014 | front and rear porch roofs ok, no posts | CHRISM | CHRISM | | BSP | P | 4667400 |
DOUBLE DIAMOND HOMES, INC. | BFI | C | 12/16/2013 | R-10 at walkout wall | CHRISM | CHRISM | | BFI | C | 4657407 |
DOUBLE DIAMOND HOMES, INC. | BFD | C | 12/16/2013 | soils on file drain usable isolate and float | CHRISM | CHRISM | | BFD | C | 4657411 |
DOUBLE DIAMOND HOMES, INC. | BFN | C | 12/16/2013 | design and eng report on file | CHRISM | CHRISM | | BFN | C | 4657410 |
DOUBLE DIAMOND HOMES, INC. | BFT | C | 12/16/2013 | eng report on file | CHRISM | CHRISM | | BFT | C | 4657403 |
POLARIZED ELECTRIC INC | E= | C | 06/06/2014 | correction made | CRAIG | CRAIG | | E= | C | 4753387 |
POLARIZED ELECTRIC INC | E= | R | 06/04/2014 | gfci protect all outlets within 6' of laundry sink (hall and check washer), ground cut-in box at island, afci master closet outlet, cord ran behind kitchen cabinets at disposal | MATTHEW | MATTHEW | | E= | R | 4751478 |
POLARIZED ELECTRIC INC | ER | C | 03/07/2014 | | MATTHEW | MATTHEW | | ER | C | 4698985 |
POLARIZED ELECTRIC INC | ES | C | 03/07/2014 | Residential Underground: 200 amp 3/w: new res---- meter is set; need seal | MATTHEW | MATTHEW | | ES | C | 4698974 |
POLARIZED ELECTRIC INC | ER | R | 03/06/2014 | need to box non-ic can, sub-panel and it panel in garage separation wall, need stackers where nm in ty-wraped to nm, inter-system bond needs to originate from service equipment, ufer ran to sub-panel and landed on neutral bar, 4/0 al to main sub-panel needs to be derated to 150 amps, 4/0 al ran outside wall above main sub-panel------------ verify correct circuits ran to island and dish/disp-------------- complete re-inspect------------------- finished basement, 6-3 nm to cooking equipment | MATTHEW | MATTHEW | | ER | R | 4698084 |
POLARIZED ELECTRIC INC | EUG | P | 02/18/2014 | existing service lateral ----------------- install observation conduit at 20' and 35' from house to verify depth after backfill | MATTHEW | MATTHEW | | EUG | P | 4688572 |
POLARIZED ELECTRIC INC | EUG | R | 12/17/2013 | NOT DEEP ENOUGH ----LOOKS LIKE EVEN WITH GRADE?????? | BRIAN | BRIAN | | EUG | R | 4658783 |
BRUNO'S HEATING & COOLING | H= | C | 05/29/2014 | Notes-- louver door to mech room. AC complete. | JEFFL | JEFFL | | H= | C | 4747855 |
CORNERSTONE PLUMBING INC | HC | C | 03/05/2014 | RELEASE METER | TED | TED | | HC | C | 4697742 |
CORNERSTONE PLUMBING INC | HI | C | 03/05/2014 | 1 1/2'' furnace, w/h, range, outlet for detached garage, bbq | TED | TED | | HI | C | 4697741 |
CORNERSTONE PLUMBING INC | HO | C | 02/18/2014 | 10# test ok. 2" repair of 20'. Total length is 600'. | MICHAELS | MICHAELS | | HO | C | 4688646 |
BRUNO'S HEATING & COOLING | HRR | C | 02/18/2014 | Rough ok. Note: duct design, FB, 6" osa, a/c rough(coil and lineset), direct vent furnace. | MICHAELS | MICHAELS | | HRR | C | 4688634 |
CORNERSTONE PLUMBING INC | P= | C | 06/11/2014 | POTABLE WATER CERTIFICATE TO SCANNING . | GABE | GABE | | P= | C | 4755375 |
CORNERSTONE PLUMBING INC | P= | P | 06/09/2014 | PENDING POTABLE WATER CERT . NOTE : FINISHED BASEMENT . | GABE | GABE | | P= | P | 4753859 |
CORNERSTONE PLUMBING INC | PTO | C | 03/05/2014 | | TIM | TIM | | PTO | C | 4697037 |
CORNERSTONE PLUMBING INC | PTO | P | 03/04/2014 | NEED TO COMPLETE WATER LINE AND TEST. LOW TEST DWV. | DICK | DICK | | PTO | P | 4696507 |
CORNERSTONE PLUMBING INC | PB | C | 03/04/2014 | UPPER LEVEL DRAINS TO ORIGINAL SEPTIC TANK. LOWER LEVEL DRAINS TO NEW TANK WITH LIFT TO ORIGINAL TANK. | DICK | DICK | | PB | C | 4696503 |
HOMEOWNER | PWO | C | 01/22/2014 | | TIM | TIM | | PWO | C | 4675967 |
CORNERSTONE PLUMBING INC | PB | R | 01/02/2014 | no 3'' riser for main level | TED | TED | | PB | R | 4665475 |