WELLS & WEST GENERAL CONTRACTORS, INC. | B= | C | 11/24/2014 | All other required Final inspections are complete. (This is a computer generated result) | BERTW | BERTW | | B= | C | 4859647 |
WELLS & WEST GENERAL CONTRACTORS, INC. | B= | P | 10/03/2014 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982). | BERTW | BERTW | | B= | P | 4828028 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | C | 10/03/2014 | | BERTW | BERTW | | BFR | C | 4827999 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BSP | P | 07/08/2014 | firecaulking ok @ storage room walls new work only ok | BERTW | BERTW | | BSP | P | 4772271 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 06/23/2014 | tech storage room walls ok | BERTW | BERTW | | BFR | P | 4763001 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BSP | T | 05/20/2014 | PAID (REC#1195990) ADDITIONAL PLAN REVIEW TIME: $50 From: TCRIPPEN moved crack units added fire damper green rated wall | TCRIPPEN | TCRIPPEN | | BSP | T | 4741931 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 04/29/2014 | ramp ok | BERTW | BERTW | | BFR | P | 4729028 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BIN | C | 04/29/2014 | | BERTW | BERTW | | BIN | C | 4729027 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BSP | R | 04/29/2014 | firecaulking not completed per previous comments-reviewed with Derrick | BERTW | BERTW | | BSP | R | 4729024 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 03/26/2014 | finish drywall patches at firebarrier and firecaulk new conduits and recall inspection | BERTW | BERTW | | BFR | P | 4708904 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 03/20/2014 | Room 100 new wall framing OK, need to fire caulk penetrations in new wall as well as in CMU wall / Column framing in room 102 OK / Room 103 door infill framing OK | JEREMYA | JEREMYA | | BFR | P | 4705590 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BSP | T | 03/05/2014 | PAID (REC#1184739) PLAN SPLICE FEE: $50 by: MICHAEL for Construction: Add fird wall | MICHAELA | MICHAELA | | BSP | T | 4697116 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 02/13/2014 | walls inspected see sheet A1 pending other roughs completed and damper framing/will need firecaulking inspection on rated wall penetrations/infill 2hr firebarrier wall in IT room where duct removed | BERTW | BERTW | | BFR | P | 4686726 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BSP | P | 12/30/2013 | inspections assigned to bert | BLAKE | BLAKE | | BSP | P | 4664485 |
KENNY ELECTRIC SERVICE, INC. | E= | C | 06/12/2014 | | BRET | BRET | | E= | C | 4757166 |
KENNY ELECTRIC SERVICE, INC. | E= | P | 06/10/2014 | ok except pdu's cover plates open wiring in electric room | BRET | BRET | | E= | P | 4754519 |
KENNY ELECTRIC SERVICE, INC. | EP | P | 03/25/2014 | data room equipment ok | BRET | BRET | | EP | P | 4707907 |
KENNY ELECTRIC SERVICE, INC. | ER | P | 03/24/2014 | ceiling ok except at walls that are to be demo'd and leave tiles out at all old fire alarm runs to verify demo. | BRET | BRET | | ER | P | 4707651 |
KENNY ELECTRIC SERVICE, INC. | EP | P | 03/17/2014 | partial panel, switch gear and equipment marked on electricians set of plans. remove bond jumper at dc-mdp | BRET | BRET | | EP | P | 4703875 |
KENNY ELECTRIC SERVICE, INC. | ER | P | 03/05/2014 | race ways floor and ceiling | BRET | BRET | | ER | P | 4697475 |
KENNY ELECTRIC SERVICE, INC. | ER | P | 02/07/2014 | conduit run from electric room to data center ok not made to equipment on both ends. dry system piping over equipment not an issue. | BRET | BRET | | ER | P | 4684252 |
KENNY ELECTRIC SERVICE, INC. | ER | P | 01/22/2014 | conduit from j-box south room b38, note handles for service disconnects must be group together remove wall between handles. | BRET | BRET | | ER | P | 4675894 |
KENNY ELECTRIC SERVICE, INC. | ER | P | 01/03/2014 | 4-2" emt conduits to roof ok | BRIAN | BRIAN | | ER | P | 4666394 |
KENNY ELECTRIC SERVICE, INC. | ER | P | 12/30/2013 | conduit run from first floor to second floor OK --- need to install a support above ceiling on first floor check on next visit | CRAIGS | CRAIGS | | ER | P | 4663804 |
AMERICAN MECHANICAL SERVICES | H= | C | 05/21/2014 | SPLICE HAS BEEN REVIEWED, THIS CONTRACTOR SCOPE OF WORK COMPLETE | ROBERTV | ROBERTV | | H= | C | 4742693 |
AMERICAN MECHANICAL SERVICES | H= | P | 04/14/2014 | COMPLETION PENDING MECH PLAN REVISION AND SPLICE SHOWING 2 - NEW FIRE DAMPERS | ROBERTV | ROBERTV | | H= | P | 4720102 |
AMERICAN MECHANICAL SERVICES | HD | C | 03/18/2014 | SHEETROCK GAP AND RETAINING ANGLES ON EAST FIRE DAMPER OK, WEST FIRE DAMPER COMPLETED, REST OF DUCT OK. PERMIT SCOPE OF WORK NEEDS TO MATCH PLANS OR ADDITIONAL MECHANICAL CONTRACTORS RESPONSIBLE NEED ATTACHED TO PERMIT CLAIMING REMAINDER OF SCOPE. NEED PLANS SPLICED BY FINAL | ROBERTV | ROBERTV | | HD | C | 4704452 |
AMERICAN MECHANICAL SERVICES | HRP | P | 03/14/2014 | CONDENSATE DRAINS COMPLETE, ALL REFRIGERATION PIPING COMPLETE EXCEPT ROOF. CHECK INSULATION BEFORE TILES AND FINAL CONNECTIONS TO FAN UNITS ON ROOF WHEN READY. LABEL ALL EQUIPMENT PER PLANS. | ROBERTV | ROBERTV | | HRP | P | 4702682 |
AMERICAN MECHANICAL SERVICES | HD | P | 03/14/2014 | WEST FIRE DAMPER NEEDS SLEEVE EXTENSION FIRE CAULKED, EAST FIRE DAMPER NEEDS SHEET ROCK CUT BACK TO MAINTAIN THERMAL GAP ON STORAGE ROOM SIDE BEFORE RETAINING ANGLES ARE INSTALLED, NEED NEW DUCT CONNECTION TO EXISTING DUCT COMPLETED. NEED SPLICED PLANS REFLECTING AS BUILT BY FINAL | ROBERTV | ROBERTV | | HD | P | 4702676 |
AMERICAN MECHANICAL SERVICES | HD | P | 02/25/2014 | WEST OUT OF THE WALL EXHAUST FIRE DAMPER FRAMING OK, EAST 8X10 FIRE DAMPER ONE SIDE SHEETROCK AND RETAINAGE OK, NEED TO INSPECT ADJACENT STORAGE ROOM SIDE WHEN READY. | ROBERTV | ROBERTV | | HD | P | 4692913 |
AMERICAN MECHANICAL SERVICES | HD | P | 02/20/2014 | EAST RATED WALL 8X10 FIRE DAMPER FRAMING OK, NEED INSPECTION AFTER SHEETROCK IS COMPLETED, BEFORE RETAINING ANGLES ARE INSTALLED. STILL NEED INSPECTION ON WEST EXHAUST FIRE DAMPER FRAMING. PLANS NEED TO REFLECT ACTUAL FIRE DAMPERS AND LOCATIONS AS WELL AS REVISION TO NON-EXISTENT FIRE DAMPER SHOWN IN TRANSFER DUCT BY FINAL. | ROBERTV | ROBERTV | | HD | P | 4690481 |
AMERICAN MECHANICAL SERVICES | HD | R | 02/18/2014 | FIRE DAMPER FRAMING IS INCORRECT, DISCUSSED DETAILS WITH FRAMER AND GENERAL CONTRACTOR | ROBERTV | ROBERTV | | HD | R | 4688821 |
AMERICAN MECHANICAL SERVICES | H16 | C | 12/30/2013 | NEED PROPER FIRE DAMPER FRAMING INSPECTIONS TO INCLUDE ROUGH FRAMING WITHOUT SHEETROCK ATTACHED, AFTER SHEETROCK BEFORE RETAINING ANGLES, AND FINAL RETAINAGE. PLEASE COORDINATE THIS CORRECTLY TO AVOID EXPOSURE IF ANY ITEMS ARE CONCEALED. PLEASE ENSURE PERMIT WORK SCOPE MATCHES INSTALLATION BY FINAL | ROBERTV | ROBERTV | | H16 | C | 4664327 |
AMERICAN MECHANICAL SERVICES | HRP | P | 12/30/2013 | HRP PIPING OK TO CONCEAL WHEN FIRESTOPPING INSPECTION COMPLETED BY BUILDING INSPECTOR, WILL NEED TO CHECK ROOF CONNECTIONS AND LIEBERT CONNECTION AT SOME POINT. | ROBERTV | ROBERTV | | HRP | P | 4664317 |