HAMMER HOMES, INC. | B= | C | 10/23/2014 | All other required Final inspections are complete. (This is a computer generated result) | DALE | DALE | | B= | C | 4840790 |
HAMMER HOMES, INC. | B= | P | 10/23/2014 | Additional Inspections Required: External Agency Inspection HD= by HEALTHDEPT is not Completed yet. | DALE | DALE | | B= | P | 4840514 |
HAMMER HOMES, INC. | BSP | C | 10/01/2014 | | DALE | DALE | | BSP | C | 4826932 |
HAMMER HOMES, INC. | BLA | C | 07/15/2014 | | DALE | DALE | | BLA | C | 4777235 |
HAMMER HOMES, INC. | BIN | C | 07/11/2014 | | CHRISM | CHRISM | | BIN | C | 4774998 |
HAMMER HOMES, INC. | BFR | P | 07/02/2014 | ok to insulate, need access to crawl space | CHRISM | CHRISM | | BFR | P | 4769831 |
HAMMER HOMES, INC. | BIN | P | 07/02/2014 | Qualified third party energy inspection documentation must be presented at time of final building (B=) inspection | CHRISM | CHRISM | | BIN | P | 4769661 |
HAMMER HOMES, INC. | BFD | C | 04/14/2014 | stamped soils and foundation design on file | JOHN | JOHN | | BFD | C | 4719672 |
HAMMER HOMES, INC. | BFN | C | 04/14/2014 | eng insp letter on file | JOHN | JOHN | | BFN | C | 4719671 |
HAMMER HOMES, INC. | BFT | C | 04/14/2014 | eng insp letter on file / 2400 / 10% final | JOHN | JOHN | | BFT | C | 4719668 |
HAMMER HOMES, INC. | BFT | P | 03/13/2014 | AUTHORIZED INSPECTION BY ENGINEER | BPHILLIPS | BPHILLIPS | BPHILLIPS | BFT | P | 4702104 |
HAMMER HOMES, INC. | BFN | P | 03/13/2014 | AUTHORIZED INSPECTION BY ENGINEER | BPHILLIPS | BPHILLIPS | BPHILLIPS | BFN | P | 4702105 |
FOUNTAIN VALLEY ELECTRICAL, LLC | E= | C | 09/30/2014 | | MATTHEW | MATTHEW | | E= | C | 4825868 |
FOUNTAIN VALLEY ELECTRICAL, LLC | E= | R | 09/29/2014 | 2 circuits on the same yoke requires handle ties, tub paperwork shows 15 amp circuits, ufer has been covered (needs to be accessible)------------- need permit for barn before house permit can be completed | MATTHEW | MATTHEW | | E= | R | 4824814 |
FOUNTAIN VALLEY ELECTRICAL, LLC | E= | R | 09/25/2014 | no power to bath outlets, need dedicated circuit for bath heat/ ex-fan, bond heater and motor at spa, only 1 circuit ran to spa (provide paperwork showing circuit requirements), finish house fan wiring------------------ need permit for wiring barn-- can't have 4 circuits to barn | MATTHEW | MATTHEW | | E= | R | 4823260 |
FOUNTAIN VALLEY ELECTRICAL, LLC | ES | C | 06/26/2014 | Residential Underground: 200 AMP 3-W NEW RES ------OK TO RESEAL METER---- | BRIAN | BRIAN | | ES | C | 4766211 |
FOUNTAIN VALLEY ELECTRICAL, LLC | ER | C | 06/26/2014 | NOTES---2 6-3AL --2-30 --- 2-20 --- | BRIAN | BRIAN | | ER | C | 4766205 |
MILLER HEATING & AIR CONDITIONING, INC. | H= | C | 10/22/2014 | Radiant heating, fireplace is wood burning. | MICHAELS | MICHAELS | | H= | C | 4839859 |
UNIQUE RADIANT HTG. & PLBG. | HWP | C | 10/02/2014 | No leaks detected. | MICHAELS | MICHAELS | | HWP | C | 4827510 |
UNIQUE RADIANT HTG. & PLBG. | HWP | R | 10/01/2014 | NO CORRECTIONS MADE | GABE | GABE | | HWP | R | 4826614 |
MILLER HEATING & AIR CONDITIONING, INC. | H= | P | 09/30/2014 | No HWP inspection done, do not pipe T&P from side arm and boiler into drain-need to terminate between 1" and 6" above floor. | MICHAELS | MICHAELS | | H= | P | 4825894 |
MILLER HEATING & AIR CONDITIONING, INC. | HC | C | 09/24/2014 | RELEASE METER | TED | TED | | HC | C | 4822008 |
MILLER HEATING & AIR CONDITIONING, INC. | HRR | C | 09/24/2014 | correction made | TED | TED | | HRR | C | 4822003 |
DOUBLE J GAS, INC. | HI+ | C | 07/07/2014 | 10 lb test ok. Note: dryer and bbq added mto system. | MARK | MARK | | HI+ | C | 4771573 |
DOUBLE J GAS, INC. | HI+ | C | 07/07/2014 | 10 lb test ok. Note: Dryer and BBQ added to system. | MARK | MARK | | HI+ | C | 4771570 |
MILLER HEATING & AIR CONDITIONING, INC. | HRR | P | 07/07/2014 | This house will have a hot water piping system in the crawl space. (Yet to be installed and inspected) For HHR there are 5 bath fans, 1 dryer vent pipe and vent pipe to circulate from attic to crawl space with fan. All ok. Partial is due to vent pipe for boiler/water heater, and vent pipe not being installed yet. Ok to drywall, but leave access for vent inspection. | MARK | MARK | | HRR | P | 4771555 |
DOUBLE J GAS, INC. | HI | C | 07/02/2014 | 10 lb test ok. Note: This is a 2' pipe system. From back of house it penetrates exterior wall and terminates at 3/4" gas valve just inside of interior wall in laundry room. No gas on property, no tank for propane. | MARK | MARK | | HI | C | 4770136 |
UNIQUE RADIANT HTG. & PLBG. | P= | C | 10/21/2014 | received potable water cert | TIM | TIM | | P= | C | 4838594 |
UNIQUE RADIANT HTG. & PLBG. | P= | P | 09/30/2014 | NEED POTABLE WATER CERT FOR COMPLETION . REST OK . NOTE : CRAWL SPACE . NO IRRIGATION | GABE | GABE | | P= | P | 4825643 |
UNIQUE RADIANT HTG. & PLBG. | PTO | C | 06/27/2014 | correction made | DICK | DICK | | PTO | C | 4767284 |
UNIQUE RADIANT HTG. & PLBG. | PTO | P | 06/26/2014 | NAIL PROTECTION NEEDED . LOW TEST . NOTE : CRAWL SPACE . NO IRRIGATION WATER OK | GABE | GABE | | PTO | P | 4766011 |