INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | B= | C | 12/18/2015 | | BERTW | BERTW | | B= | C | 5101587 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BFR | C | 12/18/2015 | welds and bolt connection observation letters on file | BERTW | BERTW | | BFR | C | 5101555 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | B= | P | 11/18/2015 | Temp CO: All paritlas ( Expires: 12/18/2015 12:00:00 AM) | JANE | JANE | | B= | P | 5081025 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | B= | P | 11/18/2015 | All thrid party soils engineering on file / Weld inspections on file, but they need to be stamped. TJ will have stamped copy at final / Still need all handrails extensions / Need to install all walk platforms required for egress -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), OLSON PLUMBING & HEATING CO Plumbing Final Inspection is not Completed yet, VISION AIR HVAC, INC. Mechanical Final Inspection is not Completed yet. | JEREMYA | JEREMYA | | B= | P | 5080878 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BFN | C | 11/18/2015 | Third party engineering on file | JEREMYA | JEREMYA | | BFN | C | 5080871 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BFT | C | 11/18/2015 | Third party engineering on file / Soils on file | JEREMYA | JEREMYA | | BFT | C | 5080870 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BSP | T | 11/12/2015 | PAID (REC#1299382) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Re-route egress. | MICHAELA | MICHAELA | | BSP | T | 5077456 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BFR | P | 11/12/2015 | walked job with TJ and Inspector Lindsey to review building final conditions/still need all paperwork for bft,bfn,open hole,bfr structural connections observation/Need handrail extensions @ top and bottom of all stairways rails | BERTW | BERTW | | BFR | P | 5077428 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BSP | P | 10/26/2015 | reviewed with TJ job super all required inspections need for a possible TCO application | BERTW | BERTW | | BSP | P | 5065316 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BFR | P | 10/14/2015 | walked job with TJ job super,reviewed final inspection requirements and observation letters needed. | BERTW | BERTW | | BFR | P | 5057677 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BFR | P | 05/01/2015 | walked job with TJ job super/reviewed what letters of observation are required for completion of BFT/BFN/BFR and final items | BERTW | BERTW | | BFR | P | 4947318 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BSP | P | 01/21/2015 | Weathercraft is doing the roof and inspections will be done @ the final inspection per conversation with TJ | BERTW | BERTW | | BSP | P | 4888078 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BSP | P | 12/04/2014 | met with TJ and reviewed job progress | BERTW | BERTW | | BSP | P | 4865430 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BSP | P | 12/03/2014 | talked to job superTJ 1-719-240-1297 about job progress | BERTW | BERTW | | BSP | P | 4863577 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BFN | P | 09/02/2014 | On-site visit with GC. Just a progress update. GC will have engineer letter for all welding and structural concrete wall panels by final. | JEREMYA | JEREMYA | | BFN | P | 4807640 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BFN | P | 07/08/2014 | Holding tank foundation OK / Ramp OK / Equipment lift foundation OK | JEREMYA | JEREMYA | | BFN | P | 4772262 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BFN | P | 07/01/2014 | tall walls lines 2-3 thru A-B.1 | BERTW | BERTW | | BFN | P | 4768997 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BFN | P | 06/30/2014 | B1-E between 2 and 1 ok | BERTW | BERTW | | BFN | P | 4767867 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BFN | P | 06/16/2014 | Foundation walls at gridline 4 from D.5-F, E from 3-4, 3A from E-F, 3 from E-F. 3 from D-F, D from 1A-3, 1A from D-D1 and diagonal wall from gridline D1 to 2A | JEREMYA | JEREMYA | | BFN | P | 4758427 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BFN | P | 06/09/2014 | Foundation walls, Pour 2 OK, Gridlines A/1-3.5, B/1-3, 2/A-B and 3/A-B | JEREMYA | JEREMYA | | BFN | P | 4753656 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BFN | P | 06/02/2014 | Grade beams at gridline 4 from A-D.5 and gridline A from 3.5-4 OK | JEREMYA | JEREMYA | | BFN | P | 4749071 |
INDUSTRIAL CONSTRUCTORS/MANAGERS, INC. | BSP | P | 05/06/2014 | inspections assigned to jeremy a or bert | BLAKE | BLAKE | | BSP | P | 4733367 |
MCDADE-WOODCOCK, INC. | E= | C | 10/27/2015 | | BRIAN | BRIAN | | E= | C | 5066102 |
MCDADE-WOODCOCK, INC. | E= | P | 08/17/2015 | NEED LABELS ON THE PUMPS---PANELS----STARTERS------NEED WR TYPE GFCI FOR OUTSIDE USE-------- | BRIAN | BRIAN | | E= | P | 5015849 |
MCDADE-WOODCOCK, INC. | EP | C | 07/25/2015 | | BRIAN | BRIAN | | EP | C | 5000898 |
MCDADE-WOODCOCK, INC. | EP | T | 07/24/2015 | PAID (REC#1276563) AFTER-HOURS INSPECTION: $200 From: DEAN EP for Saturday July 25th | DEAN | DEAN | | EP | T | 5000702 |
MCDADE-WOODCOCK, INC. | EP | P | 07/24/2015 | SEE PLANS--- | BRIAN | BRIAN | | EP | P | 5000472 |
MCDADE-WOODCOCK, INC. | EP | P | 07/09/2015 | NEED TO INSTALL COMMON GROUNDING BAR/LUGS ON TRANSFORMERS----LABELS----- | BRIAN | BRIAN | | EP | P | 4989452 |
MCDADE-WOODCOCK, INC. | EP | R | 07/08/2015 | GOING TO START EP INSPECTIONS THURSDAY----- | BRIAN | BRIAN | | EP | R | 4988455 |
MCDADE-WOODCOCK, INC. | ER | P | 07/08/2015 | WALKED SITE --SURFACE MOUNT CONDUIT----- | BRIAN | BRIAN | | ER | P | 4988449 |
SPECIAL SYSTEMS DESIGN,LLC | E= | C | 04/23/2015 | FIRE ALARM INSPECTION: | BRIAN | BRIAN | | E= | C | 4941498 |
SPECIAL SYSTEMS DESIGN,LLC | ER | C | 04/23/2015 | FIRE ALARM INSPECTION: | BRIAN | BRIAN | | ER | C | 4941497 |
MCDADE-WOODCOCK, INC. | EUG | P | 11/03/2014 | 3-2" conduits from signal man hole to building -- concrete encased | BRET | BRET | | EUG | P | 4846692 |
MCDADE-WOODCOCK, INC. | EUG | P | 09/24/2014 | slab cs electric building ok | BRET | BRET | | EUG | P | 4822436 |
MCDADE-WOODCOCK, INC. | ESL | P | 07/21/2014 | sbs tank building slab lighting circuit | BRET | BRET | | ESL | P | 4780351 |
MCDADE-WOODCOCK, INC. | ESL | P | 07/10/2014 | corrections made --grc wrapped | BRIAN | BRIAN | | ESL | P | 4773941 |
MCDADE-WOODCOCK, INC. | EUG | R | 07/09/2014 | NEED TO TAPE ALL OF THE GRC IN CONTACT OF EARTH---OK TO SEND PIC. | BRIAN | BRIAN | | EUG | R | 4773077 |
MCDADE-WOODCOCK, INC. | EUG | P | 06/27/2014 | sps building, area a dock ramp only | BRET | BRET | | EUG | P | 4766720 |
MCDADE-WOODCOCK, INC. | EUG | P | 06/04/2014 | ufer ok | BRET | BRET | | EUG | P | 4751465 |
VISION AIR HVAC, INC. | H= | C | 12/16/2015 | TAB REPORT RECEIVED | JERRYF | JERRYF | | H= | C | 5099566 |
VISION AIR HVAC, INC. | H= | P | 12/04/2015 | NEED NEW TAB REPORTS FOR EACH SEPARATE PERMIT NUMBER AND ALL OUTSIDE AIR READINGS LISTED - ATTACH NEW TAB REPORT WITH NEXT INSPECTION REQUEST | JERRYF | JERRYF | | H= | P | 5091624 |
VISION AIR HVAC, INC. | H= | P | 12/03/2015 | PARTIAL PENDING REVIEW OF TAB REPORT | JERRYF | JERRYF | | H= | P | 5091095 |
VISION AIR HVAC, INC. | H= | P | 10/16/2015 | CALLED AND LEFT INSPECTOR PHONE NUMBER TO DISCUSS PROJECT, PREVIOUS INSPECTOR OR THIS INSPECTOR HAS NOT RECEIVED REPORTS AS PREVIOUSLY NOTED. | JON | JON | | H= | P | 5059126 |
VISION AIR HVAC, INC. | H= | L | 08/18/2015 | CANCELED IN FIELD - NEED PREVIOUS NOTES ADDRESSED FOR TEST AND BALANCE REPORT AND SMOKE SHUTDOWN LETTER | JERRYF | JERRYF | | H= | L | 5016800 |
VISION AIR HVAC, INC. | HD | P | 04/14/2015 | BUILDINGS A AND C COMPLETE PENDING LETTER VERIFYING THAT SMOKE DETECTORS WILL BE MONITORED BY ALARM COMPANY AND TAB REPORTS ON BOTH BUILDINGS - WILL FINAL WHEN COMPLETE
| JERRYF | JERRYF | | HD | P | 4935379 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 11/18/2015 | SPS building--piping labeled, roof drains complete, eye wash/shower stations complete | TED | TED | | P= | C | 5080966 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 07/16/2014 | 6" just inside foundation | MARTY | MARTY | | PRD | P | 4777683 |
OLSON PLUMBING & HEATING COMPANY | PWO | P | 07/16/2014 | 2" non pot,6" pot.just inside foundation | MARTY | MARTY | | PWO | P | 4777682 |