STAN LEWIS, INC | B= | C | 12/03/2014 | All other required Final inspections are complete. (This is a computer generated result) | JEREMYA | JEREMYA | | B= | C | 4863772 |
STAN LEWIS, INC | B= | P | 11/26/2014 | Additional Inspections Required. Building final is complete / Partial pending other final inspections / No return trip needed | JEREMYA | JEREMYA | | B= | P | 4861464 |
STAN LEWIS, INC | B= | R | 11/26/2014 | Additional Inspections Required: EL PASO COUNTY ELECTRIC CO. Electrical Final Inspection is not Completed yet (This is a computer generated result) | SYSTEM | SYSTEM | | B= | R | 4861465 |
ADVANTAGE HEATING AND COOLING | BSP | P | 11/24/2014 | PLAN SPLICE: (No Fee) by: DALEH for Mechanical | DALEH | DALEH | | BSP | P | 4859758 |
EL PASO COUNTY ELECTRIC CO. | BSP | T | 11/24/2014 | PAID (REC#1233886) PLAN SPLICE FEE: $50 by: SHELBY for Electrical | SHELBY | SHELBY | | BSP | T | 4859299 |
STAN LEWIS, INC | BSP | P | 11/21/2014 | PLAN SPLICE: (No Fee) by: MICHAEL for Construction: Add rooftop RTU | MICHAELA | MICHAELA | | BSP | P | 4858828 |
STAN LEWIS, INC | BFR | P | 11/17/2014 | Need other roughs / Pending framing splice for RTU's | JEREMYA | JEREMYA | | BFR | P | 4854749 |
MARTIN'S PLBG SERVICE, INC | BSP | T | 08/19/2014 | PAID (REC#1214788) ADDITIONAL PLAN REVIEW TIME: $50 From: TCRIPPEN new splice pages see clouds | TCRIPPEN | TCRIPPEN | | BSP | T | 4799977 |
STAN LEWIS, INC | BFR | P | 08/01/2014 | Need detail for top of wall to concrete deck attachment. Business owner cannot attach to concrete ceiling due to thickness of concrete / Complete all other rough inspections | JEREMYA | JEREMYA | | BFR | P | 4788358 |
STAN LEWIS, INC | BSP | P | 05/12/2014 | inspections assigned to john p | BLAKE | BLAKE | | BSP | P | 4736721 |
EL PASO COUNTY ELECTRIC CO. | E= | C | 12/03/2014 | | CRAIGS | CRAIGS | | E= | C | 4863767 |
EL PASO COUNTY ELECTRIC CO. | E= | P | 11/25/2014 | splice plans - see EP inspection | CRAIGS | CRAIGS | | E= | P | 4860266 |
EL PASO COUNTY ELECTRIC CO. | EP | P | 11/25/2014 | splice plans so the ballasts match what was installed --------- change #4 cu to #2 cu for 100 amp panel | CRAIGS | CRAIGS | | EP | P | 4860264 |
EL PASO COUNTY ELECTRIC CO. | E= | P | 11/17/2014 | 4 RTU'S 50 amp each OK | CRAIGS | CRAIGS | | E= | P | 4854522 |
EL PASO COUNTY ELECTRIC CO. | ER | P | 07/18/2014 | WALLS SEE SUPER | MIKEC | MIKEC | | ER | P | 4779333 |
EL PASO COUNTY ELECTRIC CO. | ER | P | 07/18/2014 | WALLS SEE SUPER | MIKEC | MIKEC | | ER | P | 4779330 |
ADVANTAGE HEATING AND COOLING | H= | C | 11/26/2014 | TEST AND BALANCE REPORT RECEIVED | JERRYF | JERRYF | | H= | C | 4861031 |
ADVANTAGE HEATING AND COOLING | H= | P | 11/25/2014 | NEED TEST AND BALANCE REPORT - PLAN SPLICE COMPLETE - ALL OK | JERRYF | JERRYF | | H= | P | 4860306 |
ADVANTAGE HEATING AND COOLING | H= | P | 11/24/2014 | NEED PLANS REVISED SHOWING ALL EXHAUST AND FRESH AIR INTAKES DELETED OR COMPLETE INSTALLATION - REST OK PENDING TEST AND BALANCE ON DISPENSARY | JERRYF | JERRYF | | H= | P | 4859516 |
ADVANTAGE HEATING AND COOLING | H= | P | 11/19/2014 | NOT READY FOR FINAL - ALL RTU'S ARE COOLING ONLY | JERRYF | JERRYF | | H= | P | 4856438 |
ADVANTAGE HEATING AND COOLING | HD | P | 11/19/2014 | PARTIAL PENDING REVISED PLAN AND INSPECTION OF INSTALLED PLAN REVISIONS - NEED ALL SMOKE SHUTDOWN INSTALLED AND INSPECTED - NEED SCREENS IN ALL EXHAUST AND INTAKES THESE ARE FOR FUTURE INSTALLATION - NEED ALL CONDENSATE DRAINS - NEED TEST AND BALANCE REPORT FOR DISPENSARY AREA ONLY | JERRYF | JERRYF | | HD | P | 4856436 |
MARTIN'S PLBG SERVICE, INC | P= | C | 08/25/2014 | | JOEL | JOEL | | P= | C | 4803013 |
MARTIN'S PLBG SERVICE, INC | P= | P | 08/19/2014 | pending revised plumbing plan showing water tanks and deleted hose bibbs | JOEL | JOEL | | P= | P | 4799466 |
MARTIN'S PLBG SERVICE, INC | PTO | C | 08/07/2014 | per plan. | DICK | DICK | | PTO | C | 4792104 |