COLARELLI CONSTRUCTION, INC. | B= | C | 09/03/2014 | All other required Final inspections are complete. (This is a computer generated result) | BERTW | BERTW | | B= | C | 4808976 |
COLARELLI CONSTRUCTION, INC. | B= | P | 08/01/2014 | Additional Inspections Required: EL PASO ELECTRIC, LLC. Electrical Final Inspection is not Completed yet, ENVIRONMENTAL HTG & AIR COND Mechanical Final Inspection is not Completed yet, LANDMARK PLUMBING & HTG, INC. Plumbing Final Inspection is not Completed yet. | BERTW | BERTW | | B= | P | 4788357 |
COLARELLI CONSTRUCTION, INC. | BFR | C | 08/01/2014 | | BERTW | BERTW | | BFR | C | 4788334 |
COLARELLI CONSTRUCTION, INC. | BFR | P | 06/23/2014 | walls ok pending other roughs completed | BERTW | BERTW | | BFR | P | 4763094 |
COLARELLI CONSTRUCTION, INC. | BSP | P | 05/20/2014 | inspections assigned to bert | BLAKE | BLAKE | | BSP | P | 4741771 |
EL PASO ELECTRIC, LLC. | E= | C | 08/19/2014 | | BRET | BRET | | E= | C | 4799245 |
EL PASO ELECTRIC, LLC. | E= | R | 08/18/2014 | gfci disposal receptacle see note 14, if vending machine is going in coffee room gfci protection required gfci cannot be behind appliance or vending machine note fire permit needs to be called for final | BRET | BRET | | E= | R | 4798683 |
EL PASO ELECTRIC, LLC. | E= | P | 07/31/2014 | receptacles on east wall---bathrooms---office next to break room--lounge---small meeting room ok | SHELBY | SHELBY | | E= | P | 4787520 |
EL PASO ELECTRIC, LLC. | E= | C | 07/31/2014 | FIRE ALARM INSPECTION: | SHELBY | SHELBY | | E= | C | 4787517 |
EL PASO ELECTRIC, LLC. | ER | P | 07/17/2014 | leave tiles out at all wall fire devices | BRET | BRET | | ER | P | 4778788 |
EL PASO ELECTRIC, LLC. | ER | P | 07/17/2014 | FIRE ALARM INSPECTION: leave tile out at all wall devices | BRET | BRET | | ER | P | 4778786 |
EL PASO ELECTRIC, LLC. | ER | R | 07/15/2014 | fixtures need clips or screws -----support fire alarm off grid ----OK to close up the conference room except where the 6x6 box is open | CRAIGS | CRAIGS | | ER | R | 4776709 |
EL PASO ELECTRIC, LLC. | ER | P | 06/23/2014 | walls | BRET | BRET | | ER | P | 4763399 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | C | 08/06/2014 | TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 4791998 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | C | 06/17/2014 | ABOVE CEILING ALL OK. FOR FINAL PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | HD | C | 4759260 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 09/03/2014 | | JOEL | JOEL | | P= | C | 4808974 |
LANDMARK PLUMBING AND HEATING, INC. | P= | P | 08/01/2014 | install ice maker | JOEL | JOEL | | P= | P | 4788320 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 07/08/2014 | need pan drain for wh to approved location | JOEL | JOEL | | PTO | C | 4772178 |