J. E. DUNN CONSTRUCTION COMPANY | B= | C | 07/25/2014 | All phases of work under this permit complete | JEREMYA | JEREMYA | | B= | C | 4784304 |
J. E. DUNN CONSTRUCTION COMPANY | B= | P | 07/24/2014 | Need to provide call ahead number for inspection -- Schedule a new Building Final when above items are complete. | JEREMYA | JEREMYA | | B= | P | 4783261 |
COLORADO SHEET METAL CO., INC. | BSP | P | 07/16/2014 | PLAN SPLICE: (No Fee) by: DALEH for Mechanical: Added fire damper. | DALEH | DALEH | | BSP | P | 4777700 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 06/23/2014 | Firecaulk over OR double doors OK | JOHNP | JOHNP | | BSP | P | 4763123 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 06/23/2014 | Shaft liner on hard lid OK for next layer | JOHNP | JOHNP | | BFR | P | 4763122 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 06/20/2014 | above grid firecaulking ok in smoke walls/area above double doors to OR not ready | BERTW | BERTW | | BSP | P | 4762015 |
COLORADO SHEET METAL CO., INC. | BSP | T | 06/18/2014 | PAID (REC#1201911): PLAN SPLICE FEE: $50 by: RUSSELL for Mechanical: Moved around ductwork. | RUSSELL | RUSSELL | | BSP | T | 4760125 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 06/17/2014 | Walls OK, shaft liner in soils room OK | JOHNP | JOHNP | | BFR | P | 4759388 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 06/09/2014 | Walls OK | JOHNP | JOHNP | | BFR | P | 4753648 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 05/23/2014 | inspections assigned to bert | BLAKE | BLAKE | | BSP | P | 4744459 |
GREEN ELECTRIC INC | E= | C | 07/21/2014 | | CRAIGS | CRAIGS | | E= | C | 4780870 |
GREEN ELECTRIC INC | E= | C | 07/21/2014 | FIRE ALARM INSPECTION: | CRAIGS | CRAIGS | | E= | C | 4780869 |
GREEN ELECTRIC INC | ER | C | 07/21/2014 | FIRE ALARM INSPECTION: | CRAIGS | CRAIGS | | ER | C | 4780860 |
GREEN ELECTRIC INC | ER | C | 07/02/2014 | | CRAIGS | CRAIGS | | ER | C | 4770489 |
GREEN ELECTRIC INC | ER | C | 07/02/2014 | FIRE ALARM INSPECTION: | CRAIGS | CRAIGS | | ER | C | 4770487 |
GREEN ELECTRIC INC | ER | P | 06/09/2014 | walls ok, f.a wall stubs ok call fire alarm inspection with electrical rough | BRET | BRET | | ER | P | 4753662 |
COLORADO SHEET METAL CO., INC. | H= | C | 07/17/2014 | MECHANICAL FINAL OK. | NANCY | NANCY | | H= | C | 4778593 |
COLORADO SHEET METAL CO., INC. | H16 | C | 07/17/2014 | LETTER FROM ENGINEER APPROVING TEST AND BALANCE REPORT RECEIVED AND SCANNED. | NANCY | NANCY | | H16 | C | 4778463 |
COLORADO SHEET METAL CO., INC. | H= | P | 07/15/2014 | TEST AND BALANCE REPORT RECEIVED. SEE NOTE REGARDING TB-13. TB-13 READINGS OUTSIDE OF THE +/- 10 % ALLOWED. NEED REVISED BALANCE REPORT OR LETTER FROM ENGINEER APPROVING THESE READINGS. STILL NEED TO SEE GREASE DUCT WRAP COMPLETED AND WRAP ON ACCESS DOORS. REVISED PRINTS SHOWING GREASE DUCT? | NANCY | NANCY | | H= | P | 4777219 |
COLORADO SHEET METAL CO., INC. | H= | P | 06/25/2014 | QUESTION REGARDING 1 HOUR RATED ENCLOSURE AROUND GREASE DUCT. PROVIDE GREASE WRAP INSTALLATION INSTRUCTIONS. TAKE WRAP ALL THE WAY TO BOTTOM OF ROOF DECK. NEED REVISED/APPROVED PRINTS SHOWING GREASE DUCT AND ENCLOSURE. EXHAUST TRUNK LINE IN CORRIDOR OK. | NANCY | NANCY | | H= | P | 4764970 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 06/24/2014 | MECHANICAL PIPING FINAL OK. | NANCY | NANCY | | H= | C | 4764080 |
COLORADO SHEET METAL CO., INC. | H= | P | 06/24/2014 | GREASE DUCT OK, OK TO WRAP. NEED TO SEE WRAP BEFORE SHAFT WALLS ARE IN PLACE. WILL NEED INSTRUCTIONS TO VERIFY INSTALLATION OF WRAP ON ACCESS DOORS. AREAS SERVED BY VAV'S 1 - 13: FINAL ABOVE CEILING INSPECTION ON SUPPLY AND EXHAUST ALL OK. | NANCY | NANCY | | H= | P | 4764078 |
COLORADO SHEET METAL CO., INC. | HD | P | 06/23/2014 | REPAIR HOLE IN CORNER OF GREASE DUCT. REMOVE PLASTIC PLUGS AND WELD HOLES CLOSED. | NANCY | NANCY | | HD | P | 4763184 |
COLORADO SHEET METAL CO., INC. | HD | P | 06/19/2014 | MAIN CORRIDOR SUPPLY TRUNK AND VAV-12 OK. OK TO WRAP. | NANCY | NANCY | | HD | P | 4761434 |
OLSON PLUMBING & HEATING COMPANY | HWP | C | 06/16/2014 | 50 LB TEST OK ON HOT WATER SUPPLY/RETURN MAINS AND BRANCHES TO VAV'S. OK TO INSULATE. FOR FINAL COMPLETE HOOK UP AT VAV'S. LABEL PIPING. | NANCY | NANCY | | HWP | C | 4758404 |
COLORADO SHEET METAL CO., INC. | HD | P | 06/11/2014 | VAV'S 1 - 11 AND 13: MEDIUM AND LOW PRESSURE SUPPLY DUCTS OK, OK TO WRAP. EXHAUST ABOVE ICU ROOMS OK. BY FINAL NEED REVISED/APPROVED PRINTS SHOWING NEW LOCATION OF TB-13. NO MAIN TRUNK LINE OR HALLWAY YET. | NANCY | NANCY | | HD | P | 4755475 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 07/09/2014 | | JOEL | JOEL | | P= | C | 4773363 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 06/16/2014 | restroom walls and above ceiling o.k, still need below floor inspections | JOEL | JOEL | | PTO | P | 4758571 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 06/10/2014 | 7 sinks o.k | JOEL | JOEL | | PTO | P | 4754628 |