STAN LEWIS, INC | B= | C | 02/20/2015 | Sign off | JEREMYA | JEREMYA | | B= | C | 4905827 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | BSP | P | 02/12/2015 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical | SHELBY | SHELBY | | BSP | P | 4901316 |
STAN LEWIS, INC | B= | P | 12/16/2014 | Temp CO: Extend TCO for electrical issues ( Expires: 1/15/2015 12:00:00 AM) | MINDY | MINDY | | B= | P | 4872714 |
STAN LEWIS, INC | B= | P | 11/21/2014 | Temp CO: All partials ( Expires: 12/21/2014 12:00:00 AM) | JANE | JANE | | B= | P | 4858716 |
STAN LEWIS, INC | B= | P | 11/21/2014 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), EL PASO COUNTY ELECTRIC CO. Electrical Final Inspection is not Completed yet. Building final complete / Partial pending electric final | JEREMYA | JEREMYA | | B= | P | 4858605 |
ADVANTAGE HEATING AND COOLING | BSP | P | 11/20/2014 | PLAN SPLICE: (No Fee) by: DALEH for Mechanical | DALEH | DALEH | | BSP | P | 4857813 |
STAN LEWIS, INC | B= | L | 11/20/2014 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), ADVANTAGE HEATING & COOLING Mechanical Final Inspection is not Completed yet, EL PASO COUNTY ELECTRIC CO. Electrical Final Inspection is not Completed yet. Called number provided. Spoke with Stan Lewis. He informed me that the proprietors of the business were on-site. Upon arrival, all doors were locked and there was no answer when I knocked. Please provide a number to somebody that will be at the site for access and recall inspection. | JEREMYA | JEREMYA | | B= | L | 4857485 |
ADVANTAGE HEATING AND COOLING | BSP | T | 10/23/2014 | PAID (REC#1228204) PLAN SPLICE FEE: $50 by: RUSSELL for Mechanical: revised gas and added exhast fan | RUSSELL | RUSSELL | | BSP | T | 4840946 |
STAN LEWIS, INC | BFR | P | 08/25/2014 | New framing OK / Partial pending other rough inspections | JEREMYA | JEREMYA | | BFR | P | 4803086 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 02/18/2015 | | CRAIGS | CRAIGS | | E= | C | 4904619 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | L | 02/12/2015 | not ready , still hanging lights | CRAIGS | CRAIGS | | E= | L | 4901326 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 02/09/2015 | panels OK need all the lights and ballasts installed and match the lighting schedule or plans revised to show them as future | CRAIGS | CRAIGS | | E= | P | 4899060 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ES | P | 01/27/2015 | Commercial Service: 600 amp 120 / 208 4 wire -- needs CT'S and CT'S wired ---OK to set meter NOTE : MADE TO THE MAIN NEED TO INSPECT SUB PANELS AND FEEDERS /// CHECK THE BRASS TAG ON METER ON FINAL | CRAIGS | CRAIGS | | ES | P | 4891135 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 01/27/2015 | cultivation room # 3 OK | CRAIGS | CRAIGS | | ER | P | 4891111 |
EL PASO COUNTY ELECTRIC CO. | E= | P | 11/06/2014 | rtu 4--3--2 OK | CRAIGS | CRAIGS | | E= | P | 4849825 |
EL PASO COUNTY ELECTRIC CO. | E= | P | 10/20/2014 | all grow rooms OK--------- still need to see panels and rtu's | CRAIGS | CRAIGS | | E= | P | 4837842 |
EL PASO COUNTY ELECTRIC CO. | E= | R | 10/13/2014 | ballast has to be above the light and the outlet no more than 2' away from the ballast | CRAIGS | CRAIGS | | E= | R | 4833483 |
EL PASO COUNTY ELECTRIC CO. | EUG | P | 08/08/2014 | All PVC at MDP going into building | JOSEPH | JOSEPH | | EUG | P | 4793745 |
ADVANTAGE HEATING AND COOLING | H= | C | 11/21/2014 | PLAN SPLICE APPROVED | JERRYF | JERRYF | | H= | C | 4857879 |
ADVANTAGE HEATING AND COOLING | H= | P | 11/20/2014 | PARTIAL PENDING REVISED PLAN SPLICE - REST OK | JERRYF | JERRYF | | H= | P | 4857761 |
ADVANTAGE HEATING AND COOLING | H= | P | 11/06/2014 | NEED THE FOLLOWING ITEMS ADDRESS BEFORE COMPLETION OF FINAL - SMOKE DETECTOR SENSING TUBES MUST BE INSTALLED TO COVER ENTIRE RETURN DUCT - MISSING TRANSFER AIR FROM WOMENS RESTROOM - MISSING RETURN AIR GRILLES IN FOLLOWING ROOMS GROW ROOMS 3 &4 - WORK AREA #1 - REST OK - ROOF INSPECTION OK | JERRYF | JERRYF | | H= | P | 4849845 |
ADVANTAGE HEATING AND COOLING | HI | C | 11/06/2014 | ALL CORRECTIONS MADE | JERRYF | JERRYF | | HI | C | 4849841 |
ADVANTAGE HEATING AND COOLING | HC | C | 11/05/2014 | RELEASE METER | JERRYF | JERRYF | | HC | C | 4848453 |
ADVANTAGE HEATING AND COOLING | HI | P | 11/04/2014 | NEED ALL REGS. PROTECTED - 10# OK ON ALL OTHER GAS PIPING | JERRYF | JERRYF | | HI | P | 4847782 |
ADVANTAGE HEATING AND COOLING | HI | P | 10/23/2014 | NEED PIPING EXTENDED TO METER LOCATION PER PLAN AND PRESSURE TEST RECALLED- NEED ALL PIPING PROPERLY SUPPORTED PER IFGC 415.1 - NEED ALL MEDIUM PRESSURE REGS., LABELS AND FINAL CONNECTIONS INSTALLED - ALL GAS WORK INSTALLED INSIDE OR ON ROOF IS CONSIDERED HI | JERRYF | JERRYF | | HI | P | 4840632 |
ADVANTAGE HEATING AND COOLING | HI | R | 10/09/2014 | NO ONSITE PERSONNEL - NEED LADDER FOR ACCESS TO ROOF - NEED 2# APPROVAL LETTER FROM CSU | JERRYF | JERRYF | | HI | R | 4832110 |
ADVANTAGE HEATING AND COOLING | HD | P | 10/01/2014 | ROUGH DUCTS OK. NEED REVISED/APPROVED PRINTS FOR NEW EXHAUST FAN AND DUCT IN MMIP AREA 2. ADD GAS TO SCOPE OF WORK. NEED GAS LINE INSPECTION. NO ROOF YET. | NANCY | NANCY | | HD | P | 4826031 |
ADVANTAGE HEATING AND COOLING | HD | P | 09/30/2014 | ROUGH DUCTS ALL OK. INSTALL SMOKE DETECTION AS PER PRINTS. NEED REVISED/APPROVED PRINTS SHOWING EXHAUST FAN FROM MMIP AREA 2. ADD GAS ONTO SCOPE OF WORK. | NANCY | NANCY | | HD | P | 4827000 |
MARTIN'S PLBG SERVICE, INC | P= | C | 09/04/2014 | | JOEL | JOEL | | P= | C | 4809742 |
MARTIN'S PLBG SERVICE, INC | PTO | C | 07/25/2014 | | JOEL | JOEL | | PTO | C | 4783900 |
MARTIN'S PLBG SERVICE, INC | PTO | P | 07/24/2014 | no approved plan on site | JOEL | JOEL | | PTO | P | 4783095 |