STAN LEWIS, INC | B= | C | 09/16/2014 | All other required Final inspections are complete. (This is a computer generated result) | JEREMYA | JEREMYA | | B= | C | 4816521 |
CUSTOM CLIMATE | BSP | P | 09/12/2014 | PLAN SPLICE: (No Fee) by: DALEH for Mechanical | DALEH | DALEH | | BSP | P | 4815334 |
STAN LEWIS, INC | B= | P | 09/12/2014 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), CUSTOM CLIMATE DBA WEAVER MECHANICAL Mechanical Final Inspection is not Completed yet. Bldg final OK / Partial pending mechanical final | JEREMYA | JEREMYA | | B= | P | 4814826 |
CUSTOM CLIMATE | BSP | P | 09/04/2014 | PLAN SPLICE: (No Fee) by: DALEH for Mechanical | DALEH | DALEH | | BSP | P | 4809829 |
SUN ELECTRICAL | BSP | T | 09/03/2014 | PAID (REC#1217577) PLAN SPLICE FEE: $50 by: DOUG for Electrical: NRTL for type F fixture | DOUG | DOUG | | BSP | T | 4808956 |
STAN LEWIS, INC | BFR | P | 08/27/2014 | Center wall and wall infill framing complete / Partial pending other roughs | JEREMYA | JEREMYA | | BFR | P | 4805002 |
STAN LEWIS, INC | BFR | P | 07/25/2014 | 3 Rooms at SE of building OK / Still one wall remaining to look at | JEREMYA | JEREMYA | | BFR | P | 4784336 |
SUN ELECTRICAL | E= | C | 09/10/2014 | completion of the first phase | CRAIGS | CRAIGS | | E= | C | 4813741 |
SUN ELECTRICAL | E= | R | 09/08/2014 | NOT READY FOR FINAL | MIKEC | MIKEC | | E= | R | 4811999 |
SUN ELECTRICAL | ES | P | 09/08/2014 | Commercial Service: PRE RELEASE | MIKEC | MIKEC | | ES | P | 4811998 |
SUN ELECTRICAL | ES | P | 09/08/2014 | Commercial Service: PRE RELEASE | MIKEC | MIKEC | | ES | P | 4811668 |
SUN ELECTRICAL | ES | P | 09/05/2014 | Commercial Service: pre-release: ok to re-energize once works complete | MATTHEW | MATTHEW | | ES | P | 4810963 |
SUN ELECTRICAL | E= | P | 09/05/2014 | RTU'S OK LIGHTS APPROVED | MIKEC | MIKEC | | E= | P | 4810588 |
SUN ELECTRICAL | ER | P | 08/08/2014 | center wall OK | CRAIGS | CRAIGS | | ER | P | 4793590 |
SUN ELECTRICAL | ER | P | 07/24/2014 | 3 room in the south east of building ------- have approved drawings on site so we can high light what has been looked at | CRAIGS | CRAIGS | | ER | P | 4783675 |
CUSTOM CLIMATE | H= | C | 09/16/2014 | MECHANICAL FINAL OK. NOTE: NO DOOR ON WATER HEATER ROOM. | NANCY | NANCY | | H= | C | 4816520 |
CUSTOM CLIMATE | H= | P | 09/11/2014 | NO GAS METER YET? LABEL ALL MEDIUM PRESSURE GAS LINES EVERY 10 FEET. REVISED PRINTS STILL DO NOT HAVE CORRECT SIZING. MAIN GAS LINE IS 2 INCH NOT 2 1/2. BRANCH LINES TO RTU'S ARE 1 1/2 INCH AND 1 1/4 INCH. | NANCY | NANCY | | H= | P | 4813983 |
CUSTOM CLIMATE | H= | P | 09/02/2014 | FOR FINAL INSTALL GAS REGULATORS, LABEL ALL MEDIUM PRESSURE GAS LINES, INSTALL CONDENSATE DRAINS ON ROOF TOP UNITS, PROVIDE REVISED/APPROVED PRINTS SHOWING 2 INCH GAS LINE INSTALLED INSTEAD OF 2 1/2 INCH. | NANCY | NANCY | | H= | P | 4807644 |
CUSTOM CLIMATE | HC | C | 09/02/2014 | OK TO SET 2 LB METER. FYI: 2 INCH GAS LINE TO METER. | NANCY | NANCY | | HC | C | 4807643 |
CUSTOM CLIMATE | HI | C | 09/02/2014 | 10 LB TEST OK ON NEW MEDIUM PRESSURE GAS. NEED REVISED/APPROVED PRINTS SHOWING 2 INCH GAS LINE INSTALLED. BY FINAL INSTALL REGULATORS, LABEL ALL MEDIUM PRESSURE GAS LINES EVERY 10 FEET. | NANCY | NANCY | | HI | C | 4807641 |
CUSTOM CLIMATE | HD | P | 08/20/2014 | SUPPLY/RETURNS OK. MINI-SPLITS OK. FOR FINAL ON HVAC PORTION OF JOB INSTALL SMOKE DETECTORS, INSTALL CONDENSATE TRAPS ON RTUS AND SECURE WOOD UNDER CONDENSER PADS ON ROOF. STILL NEED GAS INSPECTION. | NANCY | NANCY | | HD | P | 4800409 |
MARTIN'S PLBG SERVICE, INC | P= | C | 08/18/2014 | | JOEL | JOEL | | P= | C | 4798672 |
MARTIN'S PLBG SERVICE, INC | PTO | C | 07/28/2014 | | JOEL | JOEL | | PTO | C | 4784763 |