MAHLER GC GENERAL CONTRACTING COMPANY | B= | C | 12/09/2014 | All other required Final inspections are complete. (This is a computer generated result) | BERTW | BERTW | | B= | C | 4867514 |
MAHLER GC GENERAL CONTRACTING COMPANY | B= | P | 12/04/2014 | Additional Inspections Required. | BERTW | BERTW | | B= | P | 4865063 |
MAHLER GC GENERAL CONTRACTING COMPANY | B= | R | 12/04/2014 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), PRESTIGE MECHANICAL CONTRACTORS,INC Plumbing Final Inspection is not Completed yet, RYBA ELECTRIC, INC. Electrical Final Inspection is not Completed yet (This is a computer generated result) | SYSTEM | SYSTEM | | B= | R | 4865064 |
MAHLER GC GENERAL CONTRACTING COMPANY | BSP | T | 12/04/2014 | PAID (REC#1235563) ADDITIONAL PLAN REVIEW TIME: $50 From: TCRIPPEN new splice added sprinkler head | TCRIPPEN | TCRIPPEN | | BSP | T | 4864807 |
MAHLER GC GENERAL CONTRACTING COMPANY | BSP | P | 10/28/2014 | mech chase @ med gas room penetrations firecaulked ok | BERTW | BERTW | | BSP | P | 4843090 |
MAHLER GC GENERAL CONTRACTING COMPANY | BSP | P | 09/22/2014 | med gas vent chase framing ok | BERTW | BERTW | | BSP | P | 4820230 |
MAHLER GC GENERAL CONTRACTING COMPANY | BSP | P | 09/19/2014 | med gas room vent chase partial framing ok/need 1 more inspection for balance of framing/pick up detail sheet @ next inspection/pending mech inspection | BERTW | BERTW | | BSP | P | 4819314 |
MAHLER GC GENERAL CONTRACTING COMPANY | BSP | P | 09/05/2014 | through penetrations @ floor firecaulked ok | BERTW | BERTW | | BSP | P | 4810578 |
MAHLER GC GENERAL CONTRACTING COMPANY | BFR | P | 08/21/2014 | tunnel construction of corridor ok/upper layer lid sheetrock ok/remove full sheet of plywood from rated wall @ doctors office for cabinet backing/med gas room need detail for vent chase framing and section drawing of hardlid with vents protected type 2-A construction firecaulk all new floor through penetrations | BERTW | BERTW | | BFR | P | 4801279 |
MAHLER GC GENERAL CONTRACTING COMPANY | BFR | P | 08/14/2014 | request was to get approval to drywall top of corridor only, ok to do that | BLAKE | BLAKE | | BFR | P | 4797355 |
RYBA ELECTRIC, INC. | E= | C | 12/05/2014 | | BRET | BRET | | E= | C | 4866483 |
RYBA ELECTRIC, INC. | E= | P | 12/04/2014 | issue with lighting wiring method, gfci protect all receptacles within 6' of sinks. ex-ray room must comply with nec 517 redundant ground and hospital grade receptacles. | BRET | BRET | | E= | P | 4865323 |
RYBA ELECTRIC, INC. | ER | C | 12/02/2014 | all lighting mc must comply with 517,13 a. 517, 13b exception 2 refers you back to 517.13 a where the armor cable itself has to qualify as a equipment grounding conductor | BRET | BRET | | ER | C | 4862987 |
RYBA ELECTRIC, INC. | ER | P | 11/25/2014 | ceiling ok except corridor | BRET | BRET | | ER | P | 4860267 |
RYBA ELECTRIC, INC. | ER | P | 09/05/2014 | walls see plans for locations | BRET | BRET | | ER | P | 4810844 |
RYBA ELECTRIC, INC. | ER | P | 08/21/2014 | WALLS SEE PLANS | MIKEC | MIKEC | | ER | P | 4801705 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | C | 12/03/2014 | MECHANICAL FINAL OK. TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 4864467 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 11/12/2014 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4852108 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 11/07/2014 | LABEL GRID FOR FIRE DAMPER LOCATIONS. REVISE PRINTS OR PROVIDE LETTER FROM ENGINEER DELETING SOUND BOOTS. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4850948 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 11/07/2014 | CORRECTION MADE ON EXHAUST FAN DUCT | JERRYF | JERRYF | | HD | P | 4850245 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 09/19/2014 | NEED MINIMUM 26 GAUGE PIPE ON EXHAUST FAN CONNECTION | JERRYF | JERRYF | | HD | P | 4819488 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HC | L | 09/19/2014 | WRONG INSPECTION | JERRYF | JERRYF | | HC | L | 4819485 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 09/10/2014 | NEED TO SEE MED GAS EXHAUST AND INTAKE CHASE FRAMING BEFORE CONCEAL - 3 FIRE DAMPER FRAMING OK ON 1 SIDED RETAINAGE - NEED ALL PLASTIC PIPE IN RETURN PLENUM PROTECTED FOR 25/50 FLAME SPREAD - LABEL ALL GRID AT FIRE DAMPER ACCESS POINTS | JERRYF | JERRYF | | HD | P | 4813555 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 08/20/2014 | ALL SUPPLY DUCT OK TO WRAP - HP'S 1 THROUGH 7 OK - STILL NEED ALL DRAINS COMPLETED - NEED ALL FIRE DAMPERS INSTALLED TO VERIFY GAP AND RETAINAGE - NEED TO VERIFY MED GAS INTAKE CAP AND EXHAUST CAP INSTALLED BEFORE COVER - AT FINAL CONFIRM MED GAS INTAKE TO BE WITHIN 12" OF FLOOR - | JERRYF | JERRYF | | HD | P | 4800989 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 08/15/2014 | FIRE DAMPER FRAMING OK ON 3 CORRIDOR DAMPERS - LEAVE BOTTOM RETAINING ANGLE OFF TO VERIFY GAP AND SHEET ROCK IN CORRIDOR ONLY - 2 SUPPLYS AND 1 RETURN | JERRYF | JERRYF | | HD | P | 4797610 |
PRESTIGE MECHANICAL CONTRACTORS,INC | P= | C | 12/09/2014 | | JOEL | JOEL | | P= | C | 4867513 |
PRESTIGE MECHANICAL CONTRACTORS,INC | P= | P | 12/04/2014 | pending splice for sprinkler head in med gas room | JOEL | JOEL | | P= | P | 4864713 |
PRESTIGE MECHANICAL CONTRACTORS,INC | PTO | P | 09/11/2014 | revise plan to show sprinkler head tied into domestic h2o | JOEL | JOEL | | PTO | P | 4814181 |
PRESTIGE MECHANICAL CONTRACTORS,INC | PTO | P | 09/10/2014 | walls and ceiling o.k less mop sink vent. ? sprinkler head tied into domestic | JOEL | JOEL | | PTO | P | 4813573 |