BRYAN CONSTRUCTION, INC. | B= | C | 10/30/2015 | | BERTW | BERTW | | B= | C | 5069818 |
BRYAN CONSTRUCTION, INC. | BFR | C | 10/30/2015 | | BERTW | BERTW | | BFR | C | 5069815 |
BRYAN CONSTRUCTION, INC. | BT= | R | 09/04/2015 | could not reach Chris Lanning, Bryan point of contact after 4 phone calls all went voice mail box. Talked with John Hilbert, OTC ficility person. Still need fire to sign off. Recall inspection. | DAN | DAN | | BT= | R | 5030333 |
GREINER ELECTRIC, LLC. | BSP | P | 04/02/2015 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical | SHELBY | SHELBY | | BSP | P | 4928427 |
COLORADO SHEET METAL CO., INC. | BSP | P | 04/02/2015 | PLAN SPLICE: (No Fee) by: DALEH for Mechanical | DALEH | DALEH | | BSP | P | 4928423 |
BRYAN CONSTRUCTION, INC. | BFR | P | 03/05/2015 | wall framing for offices#202 "A" and 202 "B" | DAN | DAN | | BFR | P | 4911774 |
BRYAN CONSTRUCTION, INC. | BSP | P | 03/05/2015 | SPLICE: floor plan revisions on both floors | SHELLEY | SHELLEY | | BSP | P | 4911722 |
COLORADO SHEET METAL CO., INC. | BSP | T | 03/05/2015 | PAID (REC#1254060) PLAN SPLICE FEE: $50 by: RUSSELL for Mechanical: revised ductwork | RUSSELL | RUSSELL | | BSP | T | 4911709 |
BRYAN CONSTRUCTION, INC. | BFR | P | 02/18/2015 | dining area sign in desk area framing and soffits ok | BERTW | BERTW | | BFR | P | 4904374 |
BRYAN CONSTRUCTION, INC. | B= | P | 01/13/2015 | eating area ok -- Schedule a new Building Final when above items are complete. | BERTW | BERTW | | B= | P | 4884545 |
BRYAN CONSTRUCTION, INC. | B= | P | 01/13/2015 | seating area only ok -- Schedule a new Building Final when above items are complete. | BERTW | BERTW | | B= | P | 4884543 |
BRYAN CONSTRUCTION, INC. | BSP | P | 12/31/2014 | detail for through penetration firestopping of pipes on file ok/Fire safeing spray applied observation reports on file ok | BERTW | BERTW | | BSP | P | 4879562 |
BRYAN CONSTRUCTION, INC. | BFR | P | 12/19/2014 | top of wall headwall detail ok @ shaft/all other framing ok/curtain wall fire safing mineral wool ok-need spray fire stopping inspection/pending other roughs completed | BERTW | BERTW | | BFR | P | 4875816 |
BRYAN CONSTRUCTION, INC. | BFR | P | 12/11/2014 | observation report on file for fire safing and structural framing/met with Scott contractor rep inspected 2hr shaft walls 3 side ok pending HWD detail for head of wall @ top of shaft/pending other roughs completed | BERTW | BERTW | | BFR | P | 4869997 |
BRYAN CONSTRUCTION, INC. | BFT | C | 12/11/2014 | observation report on file | BERTW | BERTW | | BFT | C | 4869992 |
BRYAN CONSTRUCTION, INC. | BFN | C | 12/11/2014 | observation report on file | BERTW | BERTW | | BFN | C | 4869990 |
BRYAN CONSTRUCTION, INC. | BFR | P | 12/01/2014 | framing ok/pending other roughs completed/need monocoat and structural connection observation reports | BERTW | BERTW | | BFR | P | 4862381 |
BRYAN CONSTRUCTION, INC. | BSP | P | 11/13/2014 | met with Chris job super reviewed type 2-A construction and the exception for primary structural fire resistive construction for roofs systems 20' above floor;need all structural observation reports and mono-coat reports | BERTW | BERTW | | BSP | P | 4853220 |
BRYAN CONSTRUCTION, INC. | BFT | P | 10/03/2014 | 1 interior pad ok/pending stamped open hole for 2000psf | BERTW | BERTW | | BFT | P | 4827943 |
GREINER ELECTRIC, LLC. | E= | C | 04/16/2015 | | CRAIGS | CRAIGS | | E= | C | 4936917 |
SPECIAL SYSTEMS DESIGN,LLC | E= | C | 04/01/2015 | FIRE ALARM INSPECTION: | CRAIGS | CRAIGS | | E= | C | 4927736 |
SPECIAL SYSTEMS DESIGN,LLC | ER | C | 04/01/2015 | FIRE ALARM INSPECTION: | CRAIGS | CRAIGS | | ER | C | 4927734 |
GREINER ELECTRIC, LLC. | E= | P | 03/19/2015 | room south of cafeteria | CRAIGS | CRAIGS | | E= | P | 4919770 |
GREINER ELECTRIC, LLC. | ER | P | 03/19/2015 | ABOVE CEILING @ the cafeteria | CRAIGS | CRAIGS | | ER | P | 4919765 |
GREINER ELECTRIC, LLC. | ER | P | 03/05/2015 | walls , office area at entry | BRET | BRET | | ER | P | 4912002 |
GREINER ELECTRIC, LLC. | ER | P | 02/18/2015 | walls , hard lid and under slab at the dining hall entrance OK | CRAIGS | CRAIGS | | ER | P | 4904310 |
SPECIAL SYSTEMS DESIGN,LLC | ER | P | 02/18/2015 | FIRE ALARM INSPECTION: 1 wall strobe at the dining hall entrance OK | CRAIGS | CRAIGS | | ER | P | 4904309 |
SPECIAL SYSTEMS DESIGN,LLC | ER | P | 02/10/2015 | FIRE ALARM INSPECTION: above ceiling in the coke room lower level | CRAIGS | CRAIGS | | ER | P | 4899708 |
GREINER ELECTRIC, LLC. | E= | P | 02/10/2015 | wall and floor receptacles in the main lobby area -------- still need to inspect the high lighting in the south area | CRAIGS | CRAIGS | | E= | P | 4899707 |
GREINER ELECTRIC, LLC. | ER | P | 02/10/2015 | above ceiling in the coke room down stairs | CRAIGS | CRAIGS | | ER | P | 4899704 |
SPECIAL SYSTEMS DESIGN,LLC | ER | P | 01/20/2015 | FIRE ALARM INSPECTION: MAIN LOBBY / ENTRANCE GRID CEILING-------FIRE ALARM ---CABLE AND BOXES--------- | BRIAN | BRIAN | | ER | P | 4887018 |
GREINER ELECTRIC, LLC. | E= | P | 01/14/2015 | dining area-----ok | BRIAN | BRIAN | | E= | P | 4884688 |
GREINER ELECTRIC, LLC. | E= | R | 01/13/2015 | CALLED POC TWICE NO ANSWER-----NO ACCESS TO FRONT DOOR | BRIAN | BRIAN | | E= | R | 4884121 |
GREINER ELECTRIC, LLC. | ER | P | 12/31/2014 | grid ceiling in garden plaza dining room------ | BRIAN | BRIAN | | ER | P | 4879240 |
SPECIAL SYSTEMS DESIGN,LLC | ER | P | 12/29/2014 | FIRE ALARM INSPECTION: Front dining room drop ceiling and one wall box on second floor reception area. | JOSEPH | JOSEPH | | ER | P | 4878223 |
GREINER ELECTRIC, LLC. | ER | P | 12/22/2014 | main level left of entrance doors --- 1 -- horn strobe box and sleeve for F/A | CRAIGS | CRAIGS | | ER | P | 4876000 |
GREINER ELECTRIC, LLC. | ER | P | 12/16/2014 | 2nd floor knee walls both sides of stairs ----- north of stairs knee wall ----- OK | CRAIGS | CRAIGS | | ER | P | 4872368 |
GREINER ELECTRIC, LLC. | ER | P | 12/05/2014 | upper level east column ---- lower level east wall including F/A ----lower level soffits | CRAIGS | CRAIGS | | ER | P | 4865864 |
GREINER ELECTRIC, LLC. | ER | P | 12/01/2014 | north wall lower level OK | CRAIGS | CRAIGS | | ER | P | 4861991 |
COLORADO SHEET METAL CO., INC. | H= | C | 04/07/2015 | OK | JERRYF | JERRYF | | H= | C | 4930930 |
PIPE LINE SPECIALTIES INC. | H= | C | 04/07/2015 | PLAN SPLICE OK | JERRYF | JERRYF | | H= | C | 4930899 |
PIPE LINE SPECIALTIES INC. | H= | P | 03/23/2015 | COULD NOT FIND PLAN SPLICE FOR REVISED PIPING - NEED CONSULT WITH SENIOR INSPECTOR - REST OK | JERRYF | JERRYF | | H= | P | 4921527 |
COLORADO SHEET METAL CO., INC. | H16 | C | 03/03/2015 | TEST AND BALANCE REPORT RECEIVED | JERRYF | JERRYF | | H16 | C | 4910356 |
COLORADO SHEET METAL CO., INC. | HD | P | 01/22/2015 | ABOVE CEILING OK - OK TO WRAP | JERRYF | JERRYF | | HD | P | 4889053 |
COLORADO SHEET METAL CO., INC. | HD | P | 01/20/2015 | ABOVE CEILING OK FOR WRAP ON FTU2-1 AND VAV3-2 RUN OUTS - BY FINAL REVISE PLAN SHOWING VAV3-2 AND VAV3-1 BEING RELOCATED | JERRYF | JERRYF | | HD | P | 4887275 |
COLORADO SHEET METAL CO., INC. | HD | P | 01/14/2015 | OK ON THE FOLLOWING - F/D ANGLES X 2 - SA IN ROOM 206 - EXPOSED SA IN LOUNGE 207 - VERIFY F/D LABELS AT FINAL | JERRYF | JERRYF | | HD | P | 4884876 |
COLORADO SHEET METAL CO., INC. | HD | P | 01/12/2015 | AHU-2: SUPPLY AIR FIRE/SMOKE DAMPER AT SHAFT, FRAMING AND SPACING OK. OK TO COVER, OK FOR ANGLES. FTU-2-2: LOW PRESSURE SUPPLY OK, OK TO WRAP. VAV3-1: LOW/MEDIUM PRESSURE SUPPLY OK ,OK TO WRAP. | NANCY | NANCY | | HD | P | 4883442 |
COLORADO SHEET METAL CO., INC. | HD | P | 01/05/2015 | ABOVE CEILING OK IN 202 - 242 - BY FINAL REVISE PLAN SHOWING NEW DUCT ROUTING | JERRYF | JERRYF | | HD | P | 4880403 |
PIPE LINE SPECIALTIES INC. | HWP | P | 12/30/2014 | TWO 60 LB TESTS OK ON HOT WATER SUPPLY/RETURN TO FTU-1, FTU-2 AND FIN TUBE. OK TO INSULATE, OK TO COVER. | NANCY | NANCY | | HWP | P | 4878707 |
COLORADO SHEET METAL CO., INC. | H= | P | 12/30/2014 | PLAZA LEVEL DINING ROOM ABOVE CEILING OK. | NANCY | NANCY | | H= | P | 4878706 |
PIPE LINE SPECIALTIES INC. | HWP | P | 12/29/2014 | HOT WATER SUPPLY/RETURN TO FTU-1, FTU-2 AND FIN TUBE: INSTALLATION OK. INSULATE AND COVER AT OWN RISK, STILL NEED TWO PRESSURE TESTS. BY FINAL NEED REVISED/APPROVED PRINTS WITH NEW PIPING LAYOUT. | NANCY | NANCY | | HWP | P | 4878235 |
COLORADO SHEET METAL CO., INC. | HD | P | 12/18/2014 | 2ND FLOOR RA F/S DAMPER FRAMING OK - VERIFY 1 SIDED RETAINAGE AND SCREWS AT FUTURE INSPECTION | JERRYF | JERRYF | | HD | P | 4874493 |
COLORADO SHEET METAL CO., INC. | HD | P | 12/11/2014 | M2.20: RETURN AIR RISER IN SHAFT OK, OK TO ENCLOSE. NO DAMPER OR DAMPER FRAMING YET. SUPPLY AIR TRUNK LINE OK, OK TO WRAP. M2.10: SUPPLY AIR TRUNK LINE OK, OK TO WRAP. | NANCY | NANCY | | HD | P | 4869511 |
COLORADO SHEET METAL CO., INC. | HD | P | 12/04/2014 | ABOVE CEILING OK ON 14" ROUND - BY FINAL REVISE PLAN SHOWING RELOCATED | JERRYF | JERRYF | | HD | P | 4865040 |
COLORADO SHEET METAL CO., INC. | HD | P | 11/26/2014 | OK TO CONCEAL SUPPLY IN SOFFIT ON LOWER LEVEL DINING - STILL NEED TIE IN AT MAIN TRUNK | JERRYF | JERRYF | | HD | P | 4861410 |