STAN LEWIS, INC | B= | C | 03/20/2015 | letter for wall construction on file ok | BERTW | BERTW | | B= | C | 4921050 |
STAN LEWIS, INC | B= | R | 03/13/2015 | Fire barriers are not built per code. Contractor claims to have a letter from the architect to allow construction as is, but, is not on-site to provide letter. Will need to see letter and get the required approval to accept the letter prior to final inspection completion. Additional Inspections Required (computer generated): CUSTOM CLIMATE DBA WEAVER MECHANICAL Mechanical Final Inspection is not Completed yet. | JEREMYA | JEREMYA | | B= | R | 4917232 |
STAN LEWIS, INC | BSP | T | 03/12/2015 | PAID (REC#1250132) PLAN SPLICE FEE: $50 by: SHELBY for Electrical | SHELBY | SHELBY | | BSP | T | 4916013 |
CUSTOM CLIMATE | BSP | T | 03/11/2015 | PAID (REC#1250131) PLAN SPLICE FEE: $50 by: DALEH for Mechanical | DALEH | DALEH | | BSP | T | 4915227 |
STAN LEWIS, INC | B= | T | 03/05/2015 | PAID (REC#1248949) Additional Inspections Required. Called contractor regarding final being call without any framing inspection on permit.; stair enclosures and exit passage ways. bathroom walls all build and covered. | DAN | DAN | | B= | T | 4911937 |
STAN LEWIS, INC | B= | R | 03/05/2015 | Additional Inspections Required: External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), CUSTOM CLIMATE DBA WEAVER MECHANICAL Mechanical Final Inspection is not Completed yet (This is a computer generated result) | SYSTEM | SYSTEM | | B= | R | 4911938 |
STAN LEWIS, INC | BSP | T | 02/27/2015 | PAID (REC#1247985) PLAN SPLICE FEE: $50 by: JIMA for Construction: splice : changing door sizes and closing door off adding cased openings between rooms | JIMA | JIMA | | BSP | T | 4909386 |
SUN ELECTRICAL | BSP | T | 12/24/2014 | PAID (REC#1238754) PLAN SPLICE FEE: $50 by: SHELBY for Electrical | SHELBY | SHELBY | | BSP | T | 4877544 |
SUN ELECTRICAL | E= | C | 02/20/2015 | | BRET | BRET | | E= | C | 4906417 |
SUN ELECTRICAL | E= | P | 02/19/2015 | need the plans splice showing the grow room that the lights are future and has the lighting schedule on it ---- fix or replace the exit light at the top of the stairs that is hanging by the conductors --- basement OK except for drawings | CRAIGS | CRAIGS | | E= | P | 4905539 |
SUN ELECTRICAL | E= | P | 02/17/2015 | basement rooms except mini splits | CRAIGS | CRAIGS | | E= | P | 4904010 |
SUN ELECTRICAL | E= | P | 02/13/2015 | 5 rooms main level OK lights are future | CRAIGS | CRAIGS | | E= | P | 4902246 |
SUN ELECTRICAL | E= | R | 02/12/2015 | CAN NOT USE SELF TAPPING SCREWS TO MOUNT GROUND BAR IN CONTACTOR BOXES-- ---- REMOVE THE PAINT UNDER GROUND LUGS------K.O. PLUG------REMOVE TC CABLE NOT IN USE ANY MORE----GFCI PROTECT THE CONDENSATE PUMPS ----------------- INSPECTED -1ST FLOOR FUTURE GROW ROOMS ONLY - ( 5 ROOMS )------ | BRIAN | BRIAN | | E= | R | 4901928 |
SUN ELECTRICAL | ES | C | 01/06/2015 | Commercial Service: 1200 amp 4/w 480 volt ct in the transformer ---OK | CRAIGS | CRAIGS | | ES | C | 4881385 |
SUN ELECTRICAL | ER | R | 01/06/2015 | main bonding jumper for outside transformers wrong size --- need a grounding electrode system for separately derived system ---- need multi barrel lug for grounds cant rely on transformer case to carry the fault --- complete re inspection required | CRAIGS | CRAIGS | | ER | R | 4881384 |
SUN ELECTRICAL | ER | P | 01/05/2015 | identify all roof top units ---- block all conduits up off the roof surface --- take pictures and have here for next inspection | CRAIGS | CRAIGS | | ER | P | 4880597 |
SUN ELECTRICAL | ER | P | 01/02/2015 | CORRECTIONS MADE TO PANELS GL-1 AND GL-2 | BRIAN | BRIAN | | ER | P | 4879939 |
SUN ELECTRICAL | EP | P | 12/31/2014 | see rough notes | CRAIGS | CRAIGS | | EP | P | 4879488 |
SUN ELECTRICAL | ER | P | 12/31/2014 | NEED TO FIX : proper size ground to the ground bushing in panel GL1 ---- tighten bond lugs on feeder conduits in panel GL1 --- install set screws in EMT connectors at panel GL1 --- change all tc cable to mini splits through out the building ----------- grow rooms in the basement OK | CRAIGS | CRAIGS | | ER | P | 4879487 |
SUN ELECTRICAL | ES | R | 12/12/2014 | Not ready no plans on site | JOSEPH | JOSEPH | | ES | R | 4870543 |
SUN ELECTRICAL | ER | P | 12/12/2014 | Wall receptacles in conduit in 8 grow rooms on 1 st floor only. | JOSEPH | JOSEPH | | ER | P | 4870537 |
CUSTOM CLIMATE | H= | C | 03/18/2015 | MECHANICAL FINAL OK. TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 4918886 |
CUSTOM CLIMATE | H= | P | 03/16/2015 | TEST AND BALANCE REPORT RECEIVED. AS PER PREVIOUS INSPECTION NOTES NEED REPORT FOR SUPPLY AIR, OUTSIDE AIR AND EXHAUST FOR DISPENSARY AND DISPENSARY BATHROOM. SEE PRINTS REGARDING CFM AND OUTSIDE AIR READINGS FOR EXISTING TWINNED FURNACES. ALSO PROVIDE CFM EXHAUST READINGS FOR NEW BATH FAN. BALANCE REPORT RECEIVED ONLY SHOWS READINGS FOR THE MINI-SPLIT INSTALLED IN THAT AREA. | NANCY | NANCY | | H= | P | 4917285 |
CUSTOM CLIMATE | H= | P | 03/13/2015 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT FOR DISPENSARY AND DISPENSARY BATHROOM. | NANCY | NANCY | | H= | P | 4916999 |
CUSTOM CLIMATE | H= | P | 03/05/2015 | PRINTS STILL SHOW TWO AH1'S AND AH2'S AND THE EXTRA MINI-SPLIT IN BASEMENT IS NOT ON PRINTS. REMOVE ALL KINKS FROM CONDENSATE TUBING. PROVIDE TEST AND BALANCE REPORT FOR DISPENSARY. | NANCY | NANCY | | H= | P | 4912034 |
CUSTOM CLIMATE | H= | P | 02/12/2015 | ADD EXHAUST FAN ONTO SCOPE OF WORK. PRINTS SHOW TWO AH1'S AND TWO AH2'S, ONLY ONE OF EACH INSTALLED. THERE'S AN EXTRA MINI- SPLIT INSTALLED IN THE ROOM NEXT TO GROW 10. SECURE CONDENSERS TO PADS. PROPERLY SLOPE ALL CONDENSATE DRAINS. PROVIDE TEST AND BALANCE REPORT FOR DISPENSERY. | NANCY | NANCY | | H= | P | 4901734 |
PEAK PLUMBING & HEATING, INC. | P= | C | 03/03/2015 | | JOEL | JOEL | | P= | C | 4911058 |
PEAK PLUMBING & HEATING, INC. | PTO | C | 02/12/2015 | | JOEL | JOEL | | PTO | C | 4901867 |