ELITE PROPERTIES OF AMERICA, INC. | B= | C | 08/31/2015 | All other required Final inspections are complete. (This is a computer generated result) | ED | ED | | B= | C | 5026899 |
ELITE PROPERTIES OF AMERICA, INC. | B= | P | 07/09/2015 | building side ok, pending other finals. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2). | ED | ED | | B= | P | 4989942 |
ELITE PROPERTIES OF AMERICA, INC. | BFR | C | 07/09/2015 | | ED | ED | | BFR | C | 4989941 |
ELITE PROPERTIES OF AMERICA, INC. | BIN | P | 04/28/2015 | east building ceiling okay on high roofs each side R-38 | BOBF | BOBF | | BIN | P | 4944771 |
ELITE PROPERTIES OF AMERICA, INC. | BIN | P | 04/16/2015 | wall insulation completed, still need top of truss / roof insulation | ED | ED | | BIN | P | 4937247 |
PEAK HEATING & AIR CONDITIONING, INC. | BSP | P | 04/01/2015 | PLAN SPLICE: (No Fee) by: DALEH for Mechanical | DALEH | DALEH | | BSP | P | 4927707 |
ELITE PROPERTIES OF AMERICA, INC. | BFR | P | 03/26/2015 | same inspection for trusses ok | ED | ED | | BFR | P | 4924274 |
ELITE PROPERTIES OF AMERICA, INC. | BSP | P | 03/26/2015 | trusses ok | ED | ED | | BSP | P | 4924250 |
ELITE PROPERTIES OF AMERICA, INC. | BFR | P | 03/16/2015 | walls only ok pending other rough inspections | ED | ED | | BFR | P | 4917864 |
ELITE PROPERTIES OF AMERICA, INC. | BLA | C | 03/16/2015 | | ED | ED | | BLA | C | 4917862 |
ELITE PROPERTIES OF AMERICA, INC. | BTR | C | 03/10/2015 | | BOBF | BOBF | | BTR | C | 4914559 |
ELITE PROPERTIES OF AMERICA, INC. | BSP | T | 03/05/2015 | PAID (REC#1249066): PLAN SPLICE FEE: $50 by: SHELLEY for Construction: Changes type of construction to VB | SHELLEY | SHELLEY | | BSP | T | 4912183 |
ELITE PROPERTIES OF AMERICA, INC. | BBB | C | 01/16/2015 | picked up engineering inspection letter for bond beam inspections, from Entech engineering | ED | ED | | BBB | C | 4886290 |
ELITE PROPERTIES OF AMERICA, INC. | BSP | P | 10/27/2014 | Damp proofing OK, no drain required | JOHNP | JOHNP | | BSP | P | 4842334 |
ELITE PROPERTIES OF AMERICA, INC. | BFI | C | 10/27/2014 | | JOHNP | JOHNP | | BFI | C | 4842330 |
ELITE PROPERTIES OF AMERICA, INC. | BFN | C | 10/27/2014 | 1 eufer ground OK, engineer's inspection letter picked up | JOHNP | JOHNP | | BFN | C | 4842329 |
ELITE PROPERTIES OF AMERICA, INC. | BFT | C | 10/27/2014 | Engineer's inspection letter picked up | JOHNP | JOHNP | | BFT | C | 4842326 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 05/29/2015 | see permit j67677 | BRET | BRET | | E= | C | 4963811 |
FOUNTAIN VALLEY ELECTRICAL, LLC | EUG | C | 05/23/2015 | site lighting not in fve scope of work | BRET | BRET | | EUG | C | 4960033 |
FOUNTAIN VALLEY ELECTRICAL, LLC | E= | C | 05/23/2015 | | BRET | BRET | | E= | C | 4960032 |
FOUNTAIN VALLEY ELECTRICAL, LLC | EUG | C | 05/23/2015 | site lighting not in fve scope of work | BRET | BRET | | EUG | C | 4960030 |
FOUNTAIN VALLEY ELECTRICAL, LLC | E= | R | 05/13/2015 | will need all exterior lighting installed for final. see eug notes, center pole base not even poured at this time not ready for final. have all lighting on at time of final. | BRET | BRET | | E= | R | 4953868 |
FOUNTAIN VALLEY ELECTRICAL, LLC | EUG | R | 05/13/2015 | eug covered, pot hole every 10'. only eug that was inspected was for the lights on front sidewalk. | BRET | BRET | | EUG | R | 4953858 |
FOUNTAIN VALLEY ELECTRICAL, LLC | ES | C | 04/29/2015 | Commercial Service: 2000 amp 4/w 3 phase 6 runs of 500 mcm cu ok to 7 set meters for units 2710, 2714, 2718, 2722, 2726, and 2730 and 2710 house panel | CRAIG | CRAIG | | ES | C | 4945162 |
FOUNTAIN VALLEY ELECTRICAL, LLC | ER | C | 04/29/2015 | units 2710 thur 2730 and 2710 house panel for all panel in each units ok | CRAIG | CRAIG | | ER | C | 4945161 |
TYCO INTEGRATED SECURITY | E= | C | 04/23/2015 | FIRE ALARM INSPECTION: | BRET | BRET | | E= | C | 4941704 |
FOUNTAIN VALLEY ELECTRICAL, LLC | EUG | P | 03/11/2015 | secondary side of city xfmr to mdp ------------- 6 - 3 1/2" pvc from mdp to units are 9 - 2 1/2" 2 - 1 1/4" 2 - 1" pvc | CRAIG | CRAIG | | EUG | P | 4915138 |
FOUNTAIN VALLEY ELECTRICAL, LLC | ER | P | 02/25/2015 | exterior soffit 3 cans. | BRET | BRET | | ER | P | 4908437 |
FOUNTAIN VALLEY ELECTRICAL, LLC | ER | P | 02/11/2015 | exterior column lighting ok soffit not ready | BRET | BRET | | ER | P | 4900618 |
FOUNTAIN VALLEY ELECTRICAL, LLC | ESL | P | 01/16/2015 | 8 - 2 1/2" pvc / 2 - 1 1/4" pvc / 2 - 1" pvc | CRAIG | CRAIG | | ESL | P | 4886362 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | C | 06/02/2015 | MECHANICAL FINAL OK. | NANCY | NANCY | | H= | C | 4965433 |
KAMPP-L ENTERPRISES, INC. | H= | C | 04/28/2015 | GAS FINAL OK. NOTE: NO METERS SET FOR SHELL BUILDING. METERS WILL BE SET FOR EACH TENANT WHEN SPACE IS LEASED. WILL NEED GAS CONTRACTOR ON EACH TENANT FINISH PERMIT AND LETTER FROM CSPU APPROVING MEDIUM PRESSURE SYSTEM FOR EACH TENANT. | NANCY | NANCY | | H= | C | 4944331 |
KAMPP-L ENTERPRISES, INC. | H16 | C | 04/23/2015 | LETTER FROM CSPU APPROVING MEDIUM PRESSURE GAS FOR THESE ADDRESSES WILL BE REQUIRED WHEN THE TENANT SPACE IS LEASED. NO METERS ARE BEING SET UNTIL SPACES ARE LEASED. | NANCY | NANCY | | H16 | C | 4941154 |
KAMPP-L ENTERPRISES, INC. | H= | P | 04/10/2015 | FOR FINAL INSTALL REGULATORS. NEED LETTER FROM CSPU APPROVING MEDIUM PRESSURE GAS FOR ALL ADDRESSES. | NANCY | NANCY | | H= | P | 4933279 |
KAMPP-L ENTERPRISES, INC. | HC | C | 04/10/2015 | OK TO SET 2 LB METER FOR UNITS 2710, 2714, 2718, 2722, 2726 AND 2730 (ALL METERS AT THIS BUILDING). | NANCY | NANCY | | HC | C | 4933238 |
KAMPP-L ENTERPRISES, INC. | HI | C | 04/10/2015 | ALL GAS LINES INSTALLED AS PER PRINTS. | NANCY | NANCY | | HI | C | 4933236 |
KAMPP-L ENTERPRISES, INC. | H= | P | 04/08/2015 | SEE HI NOTES. | NANCY | NANCY | | H= | P | 4932163 |
KAMPP-L ENTERPRISES, INC. | HI | P | 04/08/2015 | BUILDING LOCKED AT 4:10 PM. 10 LB TEST OK ON ALL UNITS (#'S 2710, 2714, 2718, 2722, 2726, AND 2730). STILL NEED TO SEE INSTALLATION. BY FINAL NEED LETTER FROM CSPU APPROVING 2 LB SYSTEM FOR THESE ADDRESSES. | NANCY | NANCY | | HI | P | 4932161 |
KAMPP-L ENTERPRISES, INC. | P= | C | 05/27/2015 | WATER AND WASTE IN. METER STUBS IN . SHELL ONLY | GABE | GABE | | P= | C | 4961627 |
KAMPP-L ENTERPRISES, INC. | PRD | C | 05/27/2015 | CORRECTIONS MADE , 4INCH TO 6 INCH AS PER PLAN AND ON TEST | GABE | GABE | | PRD | C | 4961622 |
KAMPP-L ENTERPRISES, INC. | P= | P | 05/01/2015 | SEE PRD | LEE | LEE | | P= | P | 4947774 |
KAMPP-L ENTERPRISES, INC. | PRD | P | 05/01/2015 | NO TEST -- ROOF DRAINS UNDERSIZED | LEE | LEE | | PRD | P | 4947768 |
KAMPP-L ENTERPRISES, INC. | PTO | C | 03/18/2015 | DWV AND H20 ON TEST FOR SHELL ONLY | GABE | GABE | | PTO | C | 4919285 |
KAMPP-L ENTERPRISES, INC. | PRD | P | 01/12/2015 | BASE PIPING ONLY . | GABE | GABE | | PRD | P | 4883546 |
KAMPP-L ENTERPRISES, INC. | PB | C | 01/12/2015 | GREASE LINES AND SEWER OK . | GABE | GABE | | PB | C | 4883543 |