ERIK R. ADAMS CONSTRUCTION | BSP | T | 11/03/2015 | PAID (REC#1307976) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: enlarge deck | MICHAELA | MICHAELA | | BSP | T | 5071638 |
ERIK R. ADAMS CONSTRUCTION | BLA | C | 09/08/2015 | | BOBF | BOBF | | BLA | C | 5032151 |
ERIK R. ADAMS CONSTRUCTION | BIN | C | 07/28/2015 | | BOBF | BOBF | | BIN | C | 5002909 |
ERIK R. ADAMS CONSTRUCTION | BFR | C | 07/28/2015 | | BOBF | BOBF | | BFR | C | 5002898 |
ERIK R. ADAMS CONSTRUCTION | BIN | P | 07/27/2015 | insulation okay pending completion of frame inspection | BOBF | BOBF | | BIN | P | 5001882 |
ERIK R. ADAMS CONSTRUCTION | BFR | P | 07/27/2015 | eng letter for B1 and 2 trusses on file / still need 4 kings each end of 2 car garage / provide hard copy of eng letter for rear garage opening / draftstop interior walls / screws not allowed to secure monoposts to LVL beams | BOBF | BOBF | | BFR | P | 5001881 |
ERIK R. ADAMS CONSTRUCTION | BFR | R | 07/09/2015 | add king studs to garage door openings, need engineering on all B1 -B2 trusses that had vertical webs cut ,draft stop fire place, missing roof jacks, attic insulation rulers missing, nail off tops of mono posts to beams -- front / rear porch lids ok (posts not installed, deck not inspected (not completed) | ED | ED | | BFR | R | 4990159 |
ERIK R. ADAMS CONSTRUCTION | BFR | R | 07/08/2015 | not ready for inspection, call inspector at 491-7643 | ED | ED | | BFR | R | 4989174 |
ERIK R. ADAMS CONSTRUCTION | BIN | P | 07/07/2015 | Qualified third party energy inspection documentation must be presented at time of final building (B=) inspection | CHERYL | CHERYL | | BIN | P | 4987336 |
ERIK R. ADAMS CONSTRUCTION | BFT | C | 02/06/2015 | | DALE | DALE | | BFT | C | 4898209 |
ERIK R. ADAMS CONSTRUCTION | BFN | C | 02/06/2015 | | DALE | DALE | | BFN | C | 4898208 |
ERIK R. ADAMS CONSTRUCTION | BFD | C | 02/05/2015 | all paperwork on file / float | DALE | DALE | | BFD | C | 4897301 |
ERIK R. ADAMS CONSTRUCTION | BFD | R | 01/30/2015 | open hole not on site , no drain design available for inspection | BOBF | BOBF | | BFD | R | 4894288 |
ERIK R. ADAMS CONSTRUCTION | BFT | R | 01/30/2015 | no stamped open hole on site | BOBF | BOBF | | BFT | R | 4894287 |
ERIK R. ADAMS CONSTRUCTION | BFN | R | 01/30/2015 | no engineer letter for observation of Footing forms, steel or rebar on site | BOBF | BOBF | | BFN | R | 4894285 |
ERIK R. ADAMS CONSTRUCTION | BFN | P | 10/14/2014 | AUTHORIZED INSPECTION BY ENGINEER | JANE | JANE | JANE | BFN | P | 4833765 |
ERIK R. ADAMS CONSTRUCTION | BFT | P | 10/14/2014 | AUTHORIZED INSPECTION BY ENGINEER | JANE | JANE | JANE | BFT | P | 4833764 |
SPRINGS FAMILY ELECTRIC | ER | C | 07/07/2015 | check well pit at final | MATTHEW | MATTHEW | | ER | C | 4988151 |
SPRINGS FAMILY ELECTRIC | ER | R | 07/01/2015 | FIGURE -- 210.52 C 1 FOR BEHIND KITCHEN SINK ----------- INSTALL WELL DISCONNECT AND FEEDER TO WELL ---------- NO MCC 10/3 FINISHED BASEMENT NO CEN VAC | CRAIG | CRAIG | | ER | R | 4985230 |
SPRINGS FAMILY ELECTRIC | ES | C | 06/30/2015 | Residential Overhead: 200 amp 3/w: new res----- need meter set | MATTHEW | MATTHEW | | ES | C | 4984042 |
SPRINGS FAMILY ELECTRIC | ER | R | 06/30/2015 | correct spacing behind sink (pop up's), remove micro from small appliance circuit and install dedicated circuit, land nm in master closet box, ------------------ finished basement, no mcc's, no cen vac | MATTHEW | MATTHEW | | ER | R | 4984039 |
C & C ELECTRIC, LLC | EUG | C | 02/18/2015 | feeder from pole to home-------- per contractor notes a disconnect will be installed on pole | MATTHEW | MATTHEW | | EUG | C | 4904665 |
C & C ELECTRIC, LLC | EUG | R | 02/10/2015 | mark grade on foundation (conductors at same level as bottom of the styrofoam), back fill to bottom of service conductors where they go thru sleeve, why is there an equipment ground ran with service conductors? | MATTHEW | MATTHEW | | EUG | R | 4900202 |
COLORADO GAS SYSTEMS | HO | C | 11/24/2015 | 10# test ok. 1" 2lb. poly from road to structure. BY FINAL: need letter on file, reg and labels in place. | MICHAELS | MICHAELS | | HO | C | 5086595 |
HOMEOWNER | HWP | P | 07/20/2015 | 70 lb test. Ok. Main / Upper lvl. Ok to cover | MARK | MARK | | HWP | P | 4997002 |
HOMEOWNER | HC | C | 07/06/2015 | RELEASE METER | DICK | DICK | | HC | C | 4987201 |
HOMEOWNER | HRR | C | 07/06/2015 | corrections made. | DICK | DICK | | HRR | C | 4987199 |
HOMEOWNER | HI | C | 06/30/2015 | 10# test ok. Sizing ok if meter at house. 1 1/4" main to boiler, range, fp, bbq. | MICHAELS | MICHAELS | | HI | C | 4983868 |
HOMEOWNER | HRR | R | 06/30/2015 | Dryer vent not installed, fp not vented, bath exhausts must terminate with exterior hood(not into soffit), seal all bath exhaust connections. Re-inspect all. | MICHAELS | MICHAELS | | HRR | R | 4983863 |
HOMEOWNER | HWP | P | 03/06/2015 | 60 POUND TEST OK , BASEMENT SLAB ONLY OK . | GABE | GABE | | HWP | P | 4912654 |
HOMEOWNER | PTO | C | 07/06/2015 | correction made. | DICK | DICK | | PTO | C | 4987202 |
HOMEOWNER | PTO | P | 06/30/2015 | NAIL PROTECT ALL WATER ON BAR WALL , SET ALL TUBS AND TEST THROUGH TRAPS , HARD CAP 2 INCH DWV ACROSS FROM BAR , REST OK . NEED POTABLE WATER CERT BY FINAL | GABE | GABE | | PTO | P | 4983996 |
HOMEOWNER | PWO | P | 02/19/2015 | OK TO COVER FROM PRESSURE TANK PIT TO HOUSE, H/O USING EXISTING PIPE FROM WELL HEAD TO PRESSURE TANK PIT, NEED TO SEE HDPE TIE IN INSIDE PIT BY FINAL | LEE | LEE | | PWO | P | 4905679 |
HOMEOWNER | PB | P | 02/09/2015 | NEED TO TEST THROUGH TRAP AT TUBS , REST OK . NO WATER IN | GABE | GABE | | PB | P | 4898893 |