GERALD H PHIPPS INC | B= | C | 02/04/2015 | All other required Final inspections are complete. (This is a computer generated result) | JEREMYA | JEREMYA | | B= | C | 4896319 |
GERALD H PHIPPS INC | B= | P | 01/15/2015 | Additional Inspections Required. Correction from previous inspection complete | JEREMYA | JEREMYA | | B= | P | 4885717 |
GERALD H PHIPPS INC | B= | R | 01/15/2015 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), NIELSEN MECHANICAL CONTRACTORS, INC. Mechanical Final Inspection is not Completed yet (This is a computer generated result) | SYSTEM | SYSTEM | | B= | R | 4885718 |
GERALD H PHIPPS INC | B= | P | 01/14/2015 | Additional Inspections Required. Signs at accessible restrooms to be ANSI compliant, currently they are paper. Install ANSI compliant signs at each restroom and recall inspection -- Schedule a new Building Final when above items are complete. | JEREMYA | JEREMYA | | B= | P | 4885111 |
GERALD H PHIPPS INC | B= | R | 01/14/2015 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), NIELSEN MECHANICAL CONTRACTORS, INC. Mechanical Final Inspection is not Completed yet (This is a computer generated result) | SYSTEM | SYSTEM | | B= | R | 4885112 |
NIELSEN MECHANICAL CONTRACTORS, INC. | BSP | T | 01/13/2015 | PAID (REC#1240722) PLAN SPLICE FEE: $50 by: DALEH for Mechanical | DALEH | DALEH | | BSP | T | 4884043 |
MATRIX ELECTRIC, INC. | BSP | T | 12/23/2014 | PAID (REC#1238670) PLAN SPLICE FEE: $50 by: SHELBY for Electrical | SHELBY | SHELBY | | BSP | T | 4877157 |
GERALD H PHIPPS INC | BSP | P | 12/05/2014 | floor penitrations ok | ED | ED | | BSP | P | 4865787 |
NIELSEN MECHANICAL CONTRACTORS, INC. | BSP | T | 12/02/2014 | PAID (REC#1236358) PLAN SPLICE FEE: $50 by: RUSSELL for Mechanical: Eliminated new dampers where not required | RUSSELL | RUSSELL | | BSP | T | 4862858 |
GERALD H PHIPPS INC | BFR | P | 11/25/2014 | provide UL listing for floor penitrations, walls and hard lid framing ok | ED | ED | | BFR | P | 4860230 |
MATRIX ELECTRIC, INC. | E= | C | 01/13/2015 | water heater elements changed to 3000w | MATTHEW | MATTHEW | | E= | C | 4884343 |
MATRIX ELECTRIC, INC. | E= | R | 01/12/2015 | need tr outlets per art 517, no power to gfci in break room, gfci can't be behind fridge in break room, need #10 at 480v water heater, need 30 amp circuit for 6000w 277v water heater in ceiling, install metering for x-ray panel | MATTHEW | MATTHEW | | E= | R | 4883773 |
MATRIX ELECTRIC, INC. | E= | C | 01/07/2015 | FIRE ALARM INSPECTION: fire alarm rough ok | MATTHEW | MATTHEW | | E= | C | 4881748 |
MATRIX ELECTRIC, INC. | ER | P | 01/07/2015 | over 6' total length of flex at can lights in x-ray room | MATTHEW | MATTHEW | | ER | P | 4881735 |
MATRIX ELECTRIC, INC. | ER | P | 12/10/2014 | hard lids marked on plans------------------- need to call fire alarm inspections | MATTHEW | MATTHEW | | ER | P | 4868699 |
MATRIX ELECTRIC, INC. | ER | P | 12/02/2014 | walls in x-ray room and x-ray control room--------- x-ray disconnect not installed at this time (surface mount), pendant lights at reception desk ok | MATTHEW | MATTHEW | | ER | P | 4862913 |
MATRIX ELECTRIC, INC. | ER | P | 11/25/2014 | WALLS SEE DRAWINGS---------FIRE ALARM BOXES AND STUBS------- | BRIAN | BRIAN | | ER | P | 4860184 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | C | 01/16/2015 | MECHANICAL FINAL OK. TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 4885991 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 01/13/2015 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4884496 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 01/05/2015 | RETURN AIR FOR ROOM 236? MISSING 20 X 24 TRANSFER AIR, SEE KEYED NOTE 15. AUDIO BOOTH BEING INSTALLED? SEE KEYED NOTE 19. PROVIDE TEST AND BALANCE REPORT.I | NANCY | NANCY | | HD | P | 4880511 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 11/18/2014 | MEDIUM/LOW PRESSURE TRUNK LINES AND LATERALS OK, OK TO WRAP. NO VAV'S OR DUCTS THROUGH HALL YET. NEED REVISED/APPROVED PRINTS DELETING FIRE DAMPERS AT HALL WAY. | NANCY | NANCY | | HD | P | 4855706 |
ROCKY MOUNTAIN PIPING & PLUMBING, INC. | P= | C | 01/09/2015 | TEMPERING IN AT EXAM SINKS , TRAP GUARDS IN AT ALL FLOOR DRAINS . | GABE | GABE | | P= | C | 4883035 |
ROCKY MOUNTAIN PIPING & PLUMBING, INC. | PTO | C | 12/17/2014 | DWV AND H20 UNDERBELLY OK . TO COMPLETE TOP OUT | GABE | GABE | | PTO | C | 4873276 |
ROCKY MOUNTAIN PIPING & PLUMBING, INC. | PTO | P | 12/04/2014 | DWV AND WATER ON TEST UPPER LEVEL , UNDER BELLY NOT READY | GABE | GABE | | PTO | P | 4864798 |