BLUSKY RESTORATION CONTRACTORS, LLC | B= | C | 05/21/2015 | All other required Final inspections are complete. (This is a computer generated result) | NATHAN | NATHAN | | B= | C | 4958415 |
BLUSKY RESTORATION CONTRACTORS, LLC | B= | P | 05/18/2015 | with all completed required inspections B= okay. Additional Inspections Required (computer generated): AIR TECH MECHANICAL INC Mechanical Final Inspection is not Completed yet, ANYTIME SEWER AND DRAIN Plumbing Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 4956046 |
BLUSKY RESTORATION CONTRACTORS, LLC | BFR | C | 05/18/2015 | per conversations with RBD and Fire department sprinkler is for parking structure only . all items are corrected. | NATHAN | NATHAN | | BFR | C | 4956040 |
BLUSKY RESTORATION CONTRACTORS, LLC | BFR | P | 03/19/2015 | all holes are corrected per UL listing. | NATHAN | NATHAN | | BFR | P | 4919736 |
BLUSKY RESTORATION CONTRACTORS, LLC | BFR | P | 03/17/2015 | need mechanical inspection at dampers and heat / missing 2 penetrations at corridor and floor in chase back room / plans have been corrected / exterior OSB has been removed and replaced with cement backing board / penetrations sealed at walls and ceiling per listings. | NATHAN | NATHAN | | BFR | P | 4918356 |
BLUSKY RESTORATION CONTRACTORS, LLC | BIN | C | 03/17/2015 | | NATHAN | NATHAN | | BIN | C | 4918848 |
BLUSKY RESTORATION CONTRACTORS, LLC | BSP | T | 03/03/2015 | PAID (REC#1250702): PLAN SPLICE FEE: $50 by: DANM for Construction: Bldg is not sprinklered - drawings changed accordingly | DANM | DANM | | BSP | T | 4911185 |
BLUSKY RESTORATION CONTRACTORS, LLC | BFR | R | 02/26/2015 | Per phone conversation with James Rohr project manager plans need to be addressed for existing doors remaining at entry, Sprinkler system not in scope but in our stamped plan and code study the sprinkler is used for Occupancy need clarification through Fire Dept for plan / still need penetrations at corridor and floor addressed. | NATHAN | NATHAN | | BFR | R | 4908665 |
BLUSKY RESTORATION CONTRACTORS, LLC | BFR | R | 02/18/2015 | OSB is not allowed per type 1A construction at exterior wall you will need non combustible sheeting at exterior wall / plan calls for sprinkler system that is not installed. | NATHAN | NATHAN | | BFR | R | 4904083 |
BLUSKY RESTORATION CONTRACTORS, LLC | BFR | R | 02/17/2015 | need all penetrations at corridor 1 hour separation wall sealed per a UL listed design seal all ceiling penetrations per listed UL horizontal 2hr listing / Type 1A building with OSB at exterior / need all MEP's completed / will do more research on type of building / interior walls frame okay | NATHAN | NATHAN | | BFR | R | 4903944 |
FRONT RANGE ELECTRIC, INC. | E= | C | 05/06/2015 | | CRAIGS | CRAIGS | | E= | C | 4949766 |
FRONT RANGE ELECTRIC, INC. | ER | C | 05/06/2015 | | CRAIGS | CRAIGS | | ER | C | 4949755 |
FRONT RANGE ELECTRIC, INC. | ER | P | 04/21/2015 | ceilings ok | TOMC | TOMC | | ER | P | 4939709 |
FRONT RANGE ELECTRIC, INC. | ER | P | 01/26/2015 | walls only | TOMC | TOMC | | ER | P | 4890400 |
AIRTECH MECHANICAL, INC. | H= | C | 05/21/2015 | TAB REPORT RECEIVED - ALL COMPLETE | JERRYF | JERRYF | | H= | C | 4958414 |
AIRTECH MECHANICAL, INC. | H= | P | 05/14/2015 | CORRECTIONS MADE. | LUKE | LUKE | | H= | P | 4954465 |
AIRTECH MECHANICAL, INC. | H= | P | 05/11/2015 | PARTIAL PENDING CONSULT ON SEMI RIGID DUCT AT FLOOR AT PEDI. CHAIRS MAY NEED TO USE RIGID PIPE AND TAB REPORT | JERRYF | JERRYF | | H= | P | 4952502 |
AIRTECH MECHANICAL, INC. | H= | P | 04/20/2015 | Training with Mark Bush, Do not see plan revision for fire damper at existing wall location, Plan shows motorized damper at supply trunk (none installed), arch. pages A2 shows fire/smoke damper (only has fire installed - all framing covered before inspection), need exhaust grills installed and tab report. | JERRYF | JERRYF | | H= | P | 4938984 |
AIRTECH MECHANICAL, INC. | HD | L | 03/26/2015 | CANCELED AT CALL BY CONTRACTOR | JERRYF | JERRYF | | HD | L | 4923815 |
AIRTECH MECHANICAL, INC. | HD | P | 03/12/2015 | NEED THE FOLLOWING - MECH. PLANS APPROVED PLANS ONSITE HAD NO MECH OR PLUMBING PAGES - CRIPPLES AT NEW FIRE DAMPERS - QUESTION ON EXISTING FIRE DAMPER AT SUPPLY - RE INSPECT ALL | JERRYF | JERRYF | | HD | P | 4916375 |
ANYTIME SEWER AND DRAIN | P= | C | 05/18/2015 | | JOEL | JOEL | | P= | C | 4956266 |
ANYTIME SEWER AND DRAIN | P= | R | 05/15/2015 | cancelled at call ahead | JOEL | JOEL | | P= | R | 4955256 |
ANYTIME SEWER AND DRAIN | P= | P | 05/14/2015 | ped chairs need to have indirect connection with traps and stand pipes, no hot h2o to fixtures, backflow protection for ped chairs | JOEL | JOEL | | P= | P | 4954434 |
ANYTIME SEWER AND DRAIN | PTO | C | 02/12/2015 | | JOEL | JOEL | | PTO | C | 4901366 |
ANYTIME SEWER AND DRAIN | PB | C | 02/12/2015 | | JOEL | JOEL | | PB | C | 4901362 |
ANYTIME SEWER AND DRAIN | PB | R | 02/11/2015 | see notes | JOEL | JOEL | | PB | R | 4900594 |
ANYTIME SEWER AND DRAIN | PTO | R | 02/11/2015 | waive trip fee, no contact number, no one on job site, no direction on what needs to be inspected, add scope of all work to permit details | JOEL | JOEL | | PTO | R | 4900590 |