ANDREW WOMMACK MINISTRIES | HE16 | C | 03/28/2024 | CORRECTION MADE VIA PICTURE. | MATTM | MATTM | | HE16 | C | 8036714 |
ANDREW WOMMACK MINISTRIES | H03 | C | 03/22/2024 | 30 DAY RED TAG NOTICE POSTED. ELEVATOR SCHEDULED TO BE REMOVED FROM SERVICE 4/22/24 IF THE FOLLOWING HAS NOT BEEN ADDRESSED: NON-ELEVATOR RELATED CONDUIT AND WIRING MUST FIND AN ALTERNATE ROUTE. CANNOT PASS THROUGH ELEVATOR MACHINE ROOM. / ELEVATOR MACHINE ROOM FIRE DAMPER CANNOT BE BLOCKED OPEN. / PHONE IS NOW OPERATIONAL. (Receipt #2045385) | MATTM | MATTM | | H03 | C | 8030085 |
ANDREW WOMMACK MINISTRIES | H01 | C | 01/22/2024 | ANNUAL 3/23 - SCHINDLER AND SERVICE - EMERGENCY PHONE IS NONFUNCTIONAL ON BATTERY POWER / EMERGENCY PHONE DOES NOT DIAL TO AN APPROPRIATE LOCATION / EMT IS BLOCKING FIRE DAMPER FROM CLOSING PROPERLY. NON-ELEVATOR WIRES WILL NEED TO FIND AN ALTERNATE ROUTE / BUILDING IS NOT KEEPING UP WITH FIRE FIGHTER AND PHONE LOGS.......60 DAYS TO ADDRESS TO AVOID SERVICE INTERRUPTION. (Receipt #2026817) | MATTM | MATTM | | H01 | C | 7974155 |
ANDREW WOMMACK MINISTRIES | H01 | C | 01/05/2023 | ANNUAL 10/2022 -- SCHINDLER AND SERVICE --/ EMERGENCY LIGHT AND BELL ARE NON-FUNCTIONAL WITHOUT THE 110v CAB CIRCUIT --/ MONTHLY FIRE FIGHTERS SERVICE TESTING AND QUARTERLY EMERGENCY PHONE TESTING LOGS NOT BEING MAINTAINED --/ PERMIT TO OPERATE WILL NOT BE ISSUED UNTIL ITEMS ARE ADDRESSED (Receipt #1924607) | MIKEM | MIKEM | | H01 | C | 7626344 |
ANDREW WOMMACK MINISTRIES | H01 | C | 01/27/2022 | ANNUAL 06/2021-- SCHINDLER AND SERVICE-- NO CODE ISSUES (Receipt #1839592) (Cat1 -- 8/2022) | MIKEM | MIKEM | | H01 | C | 7252771 |
ANDREW WOMMACK MINISTRIES | H06 | C | 06/16/2021 | WITNESSED ANNUAL SAFETY TESTING W/ SCHINDLER | RANDYB | RANDYB | | H06 | C | 7004099 |
ANDREW WOMMACK MINISTRIES | H01 | C | 01/13/2021 | 5 YEAR 6/2016 - ANNUAL 9/2020 -- SCHINDLER & SERVICE -- / EMERGENCY PHONE NONFUNCTIONAL ON BATTERY POWER / EMERGENCY PHONE DOES NOT CONNECT TO AN APPROPRIATE LOCATION (Receipt #1742586) | RANDYB | RANDYB | | H01 | C | 6834247 |
ANDREW WOMMACK MINISTRIES | H01 | C | 01/09/2020 | RP 6/19--SCHINDLER--EMERGENCY PHONE IN CAB NOT WORKING (Receipt #1654727) | CALE | CALE | | H01 | C | 6447956 |
ANDREW WOMMACK MINISTRIES | H01 | C | 01/25/2019 | RP--6--18--SCHINDLER --PHONE IN CAB NOT WORKING (Receipt #1571838) | JOHNW | JOHNW | | H01 | C | 6087941 |
ANDREW WOMMACK MINISTRIES | H01 | C | 01/31/2018 | RP--6--17--SCHINDLER AND LOCKBOX (Receipt #1479425) | JOHNW | JOHNW | | H01 | C | 5753188 |
ANDREW WOMMACK MINISTRIES | H01 | C | 01/27/2017 | RP--6--16--SCHINDLER --SEE SCOTT 499-8899 (Receipt #1398074) | JOHNW | JOHNW | | H01 | C | 5400172 |
ANDREW WOMMACK MINISTRIES | H06 | C | 06/14/2016 | WITNESSED 5 YEAR TEST COMPLETE. MISSING DOOR RESTRICTOR. RBD NOTE---EMERGENCY PHONE GOES TO WOODLAND PARK POLICE DEPARTMENT | ERIC | ERIC | | H06 | C | 5221945 |
ANDREW WOMMACK MINISTRIES | H01 | C | 01/28/2016 | RP--3--15--SCHINDLER --SEE SCOTT FOR ACCESS (Receipt #1310665) | JOHNW | JOHNW | | H01 | C | 5125057 |
ANDREW WOMMACK MINISTRIES | H02 | C | 07/07/2015 | H02 | ROBERTV | ROBERTV | | H02 | C | 4987392 |
ANDREW WOMMACK MINISTRIES | H01 | C | 02/27/2015 | RP--2--14--SCHINDLER --PRESSURE RELIEF TEST EXPIRED --COULD NOT TEST EMERGENCY LIGHT/ALARM --MISSING DOOR GIBB 4TH FLOOR--FIRE SIGNS MISSING ALL FLOORS MISSING SIGNAGE FOR PH2 FIRE SERVICE --DOOR RESTRICTOR NOT WORKING (Receipt #1248996) | ROBERTV | ROBERTV | | H01 | C | 4912035 |