SEVEN SUMMITS CONSTRUCTION LLC | B= | C | 08/25/2015 | | BRIANB | BRIANB | | B= | C | 5021993 |
ADVANTAGE HEATING AND COOLING | BSP | P | 08/12/2015 | PLAN SPLICE: (No Fee) by: RUSSELL for Mechanical: relocated the furnace and changed the efficiency | RUSSELL | RUSSELL | | BSP | P | 5012754 |
SEVEN SUMMITS CONSTRUCTION LLC | BSP | T | 08/06/2015 | PAID (REC#1279175) ADDITIONAL PLAN REVIEW TIME: $50 From: SHELBY | SHELBY | SHELBY | | BSP | T | 5008956 |
SEVEN SUMMITS CONSTRUCTION LLC | BLA | C | 05/27/2015 | | JEREMYA | JEREMYA | | BLA | C | 4961053 |
SEVEN SUMMITS CONSTRUCTION LLC | BFR | P | 05/21/2015 | reviewed with job rep____walls ok____restroom layouts ok____need mech contractor attachment to permit.ok pending other roughs completed ok | BERTW | BERTW | | BFR | P | 4959123 |
SEVEN SUMMITS CONSTRUCTION LLC | BLA | R | 05/21/2015 | nailing attachments on block walls >6' OC-lath pulls off easily______staples > 6" also | BERTW | BERTW | | BLA | R | 4959122 |
SAWYER ELECTRIC, INC | E= | C | 08/20/2015 | CORRECTIONS MADE--- | BRIAN | BRIAN | | E= | C | 5019092 |
SAWYER ELECTRIC, INC | ES | C | 08/19/2015 | Commercial Service: 1609= 100 AMP 3-W -------16091/2 = 200 AMP 3-W------OK NO ACTION NEEDED--- | BRIAN | BRIAN | | ES | C | 5018027 |
SAWYER ELECTRIC, INC | E= | P | 08/19/2015 | NEED TO GFCI PROTECT THE DRINKING FOUNTAIN----HANDEL TIES ON HALL PANEL------HARD WIRE HOT WATER HEATER----NEED PLACARDS ON THE SERVICE DISCONNECTS 1 OF 2----2 OF 2-----BRASS TAGS ON METERS-------- | BRIAN | BRIAN | | E= | P | 5018026 |
SAWYER ELECTRIC, INC | E= | R | 08/05/2015 | not ready | TOMC | TOMC | | E= | R | 5008245 |
SAWYER ELECTRIC, INC | ER | P | 08/05/2015 | drop ceiling ( low volt wire needs to be raised off of grid ) | TOMC | TOMC | | ER | P | 5008223 |
SAWYER ELECTRIC, INC | ES | P | 05/13/2015 | Residential Underground: pre-release------------ schedule shut down with CSU | MATTHEW | MATTHEW | | ES | P | 4953489 |
SAWYER ELECTRIC, INC | ER | P | 05/06/2015 | NEW WALLS SEE PLANE----- | BRIAN | BRIAN | | ER | P | 4950067 |
SEVEN SUMMITS CONSTRUCTION LLC | FP= | C | 08/25/2015 | | KEITH | KEITH | BDA | FP= | C | 5021321 |
ADVANTAGE HEATING AND COOLING | H= | C | 08/19/2015 | MECHANICAL FINAL OK. TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 5018457 |
ADVANTAGE HEATING AND COOLING | H= | P | 08/19/2015 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5017728 |
ADVANTAGE HEATING AND COOLING | HD | C | 08/11/2015 | BY FINAL REVISE PLAN SHOWING 90% FURNACE - INSTALL BACK DRAFT DAMPERS AT RELIEF HOODS - TEST AND BALANCE REPORT ON DISPENSARY AREA AND OSA REQUIREMENTS - REST OK | JERRYF | JERRYF | | HD | C | 5012013 |
BILL ESTES PLUMBING & HEATING LLC | P= | C | 08/14/2015 | correction made. | DICK | DICK | | P= | C | 5014883 |
BILL ESTES PLUMBING & HEATING LLC | P= | P | 08/13/2015 | need mixing valves at lavs. | DICK | DICK | | P= | P | 5014364 |
BILL ESTES PLUMBING & HEATING LLC | PTO | P | 05/26/2015 | bathrooms and drinking fountain DWV and water in walls only ok, laundry tub DWV in wall only ok. | DICK | DICK | | PTO | P | 4960268 |
BILL ESTES PLUMBING & HEATING LLC | PB | C | 04/08/2015 | PER PLAN, NOTE, LAUNDRY TUB INSTEAD OF SLOP/MOP SINK. | DICK | DICK | | PB | C | 4931820 |