SADDLETREE INC. | B= | C | 10/14/2015 | All other required Final inspections are complete. (This is a computer generated result) | DANE | DANE | | B= | C | 5057849 |
SADDLETREE INC. | B= | P | 10/14/2015 | . Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2). | DANE | DANE | | B= | P | 5057756 |
SADDLETREE INC. | BLA | C | 07/24/2015 | lath OK | DANE | DANE | | BLA | C | 5000326 |
SADDLETREE INC. | BFR | C | 07/17/2015 | | BOBF | BOBF | | BFR | C | 4995258 |
SADDLETREE INC. | BFR | P | 07/15/2015 | OK to insulate / missing lat brace at A2E / plan calls 2 TBE6 and 1 HTS20 each end of B2 / strap header over front door to top plates / nail off joist hanger above wet bar at dropped floor / can not see exterior sheer nailing and hardware because walls have stucco lath on them - please remove lath at sheer sites for inspection | DANE | DANE | | BFR | P | 4993852 |
SADDLETREE INC. | BIN | P | 07/14/2015 | Qualified third party energy inspection documentation must be presented at time of final building (B=) inspection | KENYATTA | KENYATTA | | BIN | P | 4993099 |
SADDLETREE INC. | BSP | P | 06/24/2015 | rear porch columns OK and missing deck hanger has been installed | DANE | DANE | | BSP | P | 4979866 |
SADDLETREE INC. | BSP | T | 06/11/2015 | PAID (REC#1267495) PLAN SPLICE FEE: $50 by: JIMA for Construction: splice : added movie room / rec room in basement | JIMA | JIMA | | BSP | T | 4971903 |
SADDLETREE INC. | BSP | R | 05/29/2015 | rear deck missing a joist hanger inside of the west post / rear deck cover posts and lid OK / front porch lid OK | DANE | DANE | | BSP | R | 4963626 |
SADDLETREE INC. | BSP | T | 04/17/2015 | PAID (REC#1256895) PLAN SPLICE FEE: $50 by: DANM for Construction: Kitchen layout revision and opening revisions | DANM | DANM | | BSP | T | 4938216 |
SADDLETREE INC. | BFI | C | 04/07/2015 | 2" R10 foam installed installed 48" deep at walkout | BRIANB | BRIANB | | BFI | C | 4930593 |
SADDLETREE INC. | BFD | C | 04/07/2015 | drain habitable to daylight at rear walkout and to under drain at street | BRIANB | BRIANB | | BFD | C | 4930592 |
SADDLETREE INC. | BFN | C | 04/07/2015 | engineering letter of inspection received / eufer documented / soils letter received / 2000psf / foundation design received | BRIANB | BRIANB | | BFN | C | 4930587 |
SADDLETREE INC. | BFT | C | 04/07/2015 | engineering letter of inspection received | BRIANB | BRIANB | | BFT | C | 4930579 |
SADDLETREE INC. | BFT | P | 03/30/2015 | AUTHORIZED INSPECTION BY ENGINEER | REBECCA | REBECCA | REBECCA | BFT | P | 4925814 |
SADDLETREE INC. | BFN | P | 03/30/2015 | AUTHORIZED INSPECTION BY ENGINEER | REBECCA | REBECCA | REBECCA | BFN | P | 4925815 |
SAFE HOUSE ELECTRIC | E= | C | 10/07/2015 | | BRET | BRET | | E= | C | 5052768 |
SAFE HOUSE ELECTRIC | E= | R | 10/05/2015 | gfci protect all receptacles with in 6' of laundry sink, install receptacle in cabinet for microwave, receptacle to close to floor in garage,(18" min to bottom of box), install breaker lock for oven unit, gfci protect wet bar dish/disposal receptacle. use listed class 2 transformer for puck lights cannot cord connect that transformer, 100 amp breaker to big for #4 al complete re-inspect | BRET | BRET | | E= | R | 5050973 |
SAFE HOUSE ELECTRIC | E= | R | 10/02/2015 | not ready, intersystem bond, bath receptacles not gfci protected, missing lights thru out, verify breaker size for sub panel, panel schedule,garage receptacle not 18" from floor. complete re-inspect. | BRET | BRET | | E= | R | 5049190 |
SAFE HOUSE ELECTRIC | ES | C | 07/14/2015 | Residential Underground: NEW 200 AMP SERVICE | MIKEC | MIKEC | | ES | C | 4993031 |
SAFE HOUSE ELECTRIC | ES | R | 07/13/2015 | NOT READY | MIKEC | MIKEC | | ES | R | 4991638 |
SAFE HOUSE ELECTRIC | ER | C | 07/13/2015 | NO CEN. VAC | MIKEC | MIKEC | | ER | C | 4991637 |
OLYMPIA HEATING & COOLING INC. | H= | C | 09/29/2015 | A/C complete, high-lows to mechanical open to stairs. | STEVEC | STEVEC | | H= | C | 5046680 |
OLYMPIA HEATING & COOLING INC. | HC | C | 06/01/2015 | RELEASE METER | STEVEC | STEVEC | | HC | C | 4964270 |
OLYMPIA HEATING & COOLING INC. | HRR | C | 06/01/2015 | Note: AC prep, outside air to return, duct design, equipment matches, basement finish, check mantle clearances at final. | STEVEC | STEVEC | | HRR | C | 4964269 |
KAMPP-L ENTERPRISES, INC. | HI | C | 05/29/2015 | 10# test o.k. 1" 1/4 main, fireplace, range, outdoor bbq, furnace and water heater. | STEVEC | STEVEC | | HI | C | 4963488 |
KAMPP-L ENTERPRISES, INC. | P= | C | 09/23/2015 | pvb installed, finished basement. | TAYLOR | TAYLOR | | P= | C | 5042241 |
KAMPP-L ENTERPRISES, INC. | PTO+ | C | 06/26/2015 | | DICK | DICK | | PTO+ | C | 4982017 |
KAMPP-L ENTERPRISES, INC. | PTO | C | 05/29/2015 | NOTE : FINISHED BASEMENT , IRRIGATION STUB | GABE | GABE | | PTO | C | 4962876 |
KAMPP-L ENTERPRISES, INC. | PB | C | 04/14/2015 | | DICK | DICK | | PB | C | 4935823 |