HOMEOWNER | B= | C | 01/05/2017 | | DALE | DALE | | B= | C | 5382982 |
HOMEOWNER | BFR | C | 01/05/2017 | letter for beam bearing received / corrections complete | BRIANB | BRIANB | | BFR | C | 5382732 |
HOMEOWNER | BFR | P | 12/30/2016 | still need letter addressing beams not in beam pockets per frame inspection dated 26JUL16 / engineering for trusses from John Wheeler on file | BRIANB | BRIANB | | BFR | P | 5379728 |
HOMEOWNER | B= | R | 12/29/2016 | need to complete other final inspections / need to complete frame inspection / missing code compliant numeric address posted on home / missing gypsum at garage to house wall at garage stairs / metal roof incomplete in spots at rear (North) side of home / weather-resistant exterior wall envelope incomplete / missing landing at rear kitchen door to deck and at GSD / mbr rear door barricaded off - no deck installed off of master bedroom / unfinished basement | BRIANB | BRIANB | | B= | R | 5379026 |
HOMEOWNER | BIN | P | 12/28/2016 | pending completed frame inspection / 3rd party insulation certificate on file | BRIANB | BRIANB | | BIN | P | 5377486 |
HOMEOWNER | BFR | P | 12/27/2016 | still need engineer observation letter for truss modifications and beam pocket modifications - no observation letters onsite at time of inspection | BRIANB | BRIANB | | BFR | P | 5377276 |
HOMEOWNER | BIN | R | 08/02/2016 | using approved third party energy inspection / still need to complete frame inspection - homeowner to provide engineer observation letter for truss modifications and beam pocket modifications - no observation letters onsite at time of inspection / no insulation inspection done | BRIANB | BRIANB | | BIN | R | 5260154 |
HOMEOWNER | BFR | P | 07/26/2016 | OK to insulate -- Glue shims at beam pockets in basement and crawl space -- Need engineering for beams not in beam pockets -- Need engineering for damaged roof trusses | DAKOTAB | DAKOTAB | | BFR | P | 5254212 |
HOMEOWNER | BLA | C | 07/26/2016 | Bert W spoke to stucco Tom Simard and flashing not required here 6-9-16 | DAKOTAB | DAKOTAB | | BLA | C | 5254108 |
HOMEOWNER | BLA | R | 06/30/2016 | Still need to flash ledger at back patio/Bert W spoke to stucco Tom Simart and flashing not required here 6-9-16 | DAKOTAB | DAKOTAB | | BLA | R | 5235507 |
HOMEOWNER | BLA | P | 06/15/2016 | flash ledger at patio | DALE | DALE | | BLA | P | 5223276 |
HOMEOWNER | BSP | P | 05/13/2016 | shear not required | DALE | DALE | | BSP | P | 5199282 |
HOMEOWNER | BSP | P | 03/22/2016 | SIP panel nailing for exterior, interior and roof panels okay | BOBF | BOBF | | BSP | P | 5160612 |
HOMEOWNER | BFD | C | 02/22/2016 | | DALE | DALE | | BFD | C | 5138738 |
HOMEOWNER | BFN | C | 02/12/2016 | eng. on file | DALE | DALE | | BFN | C | 5133827 |
HOMEOWNER | BFT | C | 02/11/2016 | footing under front door ok / eng. inspection report on file | DALE | DALE | | BFT | C | 5132696 |
HOMEOWNER | BFD | P | 12/10/2015 | complete bft and bfn | DALE | DALE | | BFD | P | 5096367 |
HOMEOWNER | BFT | P | 12/10/2015 | need eng. inspection report | DALE | DALE | | BFT | P | 5096364 |
HOMEOWNER | BFN | P | 12/10/2015 | need eng. report / foundation design and soils on file | DALE | DALE | | BFN | P | 5096362 |
HOMEOWNER | BFD | R | 12/03/2015 | need letter for ice and water on wall | DALE | DALE | | BFD | R | 5090859 |
HOMEOWNER | BFN | R | 12/03/2015 | need stamped eng. letter | DALE | DALE | | BFN | R | 5090858 |
HOMEOWNER | BFT | R | 12/03/2015 | need stamped letter fom eng. | DALE | DALE | | BFT | R | 5090854 |
HOMEOWNER | BFT | P | 10/19/2015 | ok to use RMG to do footing and foundation inspections with observation letters to be picked up at drain inspection | BERTW | BERTW | | BFT | P | 5060903 |
HOMEOWNER | E= | C | 12/29/2016 | | MATTHEW | MATTHEW | | E= | C | 5379471 |
BLUE MOUNTAIN ELECTRIC, INC. | E= | C | 12/28/2016 | | MATTHEW | MATTHEW | | E= | C | 5378253 |
HOMEOWNER | E= | R | 12/28/2016 | install inter-system bond terminal, protect nm in garage, can't have gfci test behind washer, install breaker lock for oven, bond heater and motor at spa, need tr outlet at sub-panel, guard crawler lights, AFCI per 2011 NEC; check AFCI at re-inspect------------ no a/c | MATTHEW | MATTHEW | | E= | R | 5378249 |
BLUE MOUNTAIN ELECTRIC, INC. | ES | C | 07/27/2016 | Residential Overhead: 200 amp 3/w: new res------ meter is set; need seal ---- blue mountain permit is for service only | MATTHEW | MATTHEW | | ES | C | 5254876 |
BLUE MOUNTAIN ELECTRIC, INC. | ES | R | 07/25/2016 | call me in the am 327-2952 200 amp 3/w oh | MATTHEW | MATTHEW | | ES | R | 5254875 |
HOMEOWNER | ER | C | 07/22/2016 | | MATTHEW | MATTHEW | | ER | C | 5252134 |
HOMEOWNER | ER | P | 07/18/2016 | interior wiring ok----------- still need to check exterior soffit lighting | MATTHEW | MATTHEW | | ER | P | 5247923 |
HOMEOWNER | ER | R | 07/12/2016 | need 4 wire to dryer, 20 amp dedicated for bath outlets, dining room needs to be a 20 amp circuit, pigtail all grounds (lights and smokes), need (2) 20 amp circuits for island (dish/disp and small appliance), install master bath ex-fan and lights, install can lights on deck, verify metal boxes are fan rated boxes, run power out to well head, install mech room gfci below 5 1/2', add outlet in east bedroom and verify wall space at master door----------- unfinished basement, ufer not connected at this time, no vac, check mcc's at time of service inspection------------------- partial rough inspection ; garage was not inspected | MATTHEW | MATTHEW | | ER | R | 5243314 |
BLUE MOUNTAIN ELECTRIC, INC. | EUG | C | 06/23/2016 | 3/w 350 mcm al service lateral | CRAIG | CRAIG | | EUG | C | 5254874 |
FRONTIER MECHANICAL SYSTEMS INC | H= | C | 12/23/2016 | Correction made. | JEFFL | JEFFL | | H= | C | 5375886 |
FRONTIER MECHANICAL SYSTEMS INC | H= | P | 12/13/2016 | Missing make up air to laundry, rest ok. Note: HWP system with direct vent. | MARK | MARK | | H= | P | 5366759 |
HOMEOWNER | HC | C | 09/30/2016 | RELEASE METER | JEFFL | JEFFL | | HC | C | 5307353 |
HOMEOWNER | HRR | C | 09/30/2016 | Bath exhausts, boiler vent, and dryer vent ok. | JEFFL | JEFFL | | HRR | C | 5307347 |
HOMEOWNER | HRR | L | 09/22/2016 | Need to research in morning intended inspection. | JEFFL | JEFFL | | HRR | L | 5300010 |
FRONTIER MECHANICAL SYSTEMS INC | HV | C | 07/25/2016 | Boiler vent ok. | JEFFL | JEFFL | | HV | C | 5253241 |
FRONTIER MECHANICAL SYSTEMS INC | HWP | P | 06/01/2016 | Pressure test ok on two zones for main level. | JEFFL | JEFFL | | HWP | P | 5212587 |
FRONTIER MECHANICAL SYSTEMS INC | HWP | L | 05/31/2016 | Home is locked. | JEFFL | JEFFL | | HWP | L | 5211100 |
FRONTIER MECHANICAL SYSTEMS INC | HI | C | 05/23/2016 | 10 lb test is good. 1 1/2" main. Boiler, cook top future bbq and future garage heater. | MARK | MARK | | HI | C | 5205669 |
FRONTIER MECHANICAL SYSTEMS INC | HWP | P | 04/11/2016 | Pressure test ok on lower level. Ok to cover. | JEFFL | JEFFL | | HWP | P | 5174134 |
HOMEOWNER | P= | C | 12/19/2016 | received potable water cert | TIM | TIM | | P= | C | 5371113 |
FRONTIER MECHANICAL SYSTEMS INC | P= | P | 12/13/2016 | need potable water cert | TIM | TIM | | P= | P | 5366866 |
FRONTIER MECHANICAL SYSTEMS INC | PTO | C | 06/08/2016 | tubs on backorder can verify drains and tempering valve on final | TIM | TIM | | PTO | C | 5217843 |
FRONTIER MECHANICAL SYSTEMS INC | PTO | P | 06/07/2016 | set main bath tub and test thru overflow, install trap for master tub and test, temper valve for master tub??? | TIM | TIM | | PTO | P | 5216850 |
FRONTIER MECHANICAL SYSTEMS INC | PB | C | 04/11/2016 | | TIM | TIM | | PB | C | 5174046 |