COLARELLI CONSTRUCTION, INC. | B= | C | 12/22/2016 | All other required Final inspections are complete. (This is a computer generated result) | JEREMYA | JEREMYA | | B= | C | 5374476 |
FOSTER ELECTRIC CORPORATION | BSP | T | 12/16/2016 | PAID (REC#1389801) PLAN SPLICE FEE: $50 by: BERTHA for Electrical: New electrical plans to address inspector's comments. | BERTHA | BERTHA | | BSP | T | 5370346 |
COLARELLI CONSTRUCTION, INC. | B= | P | 12/15/2016 | Building final complete pending electric final // No return trip needed. Additional Inspections Required (computer generated): FOSTER ELECTRIC CORP Electrical Final Inspection is not Completed yet. | JEREMYA | JEREMYA | | B= | P | 5369230 |
FOSTER ELECTRIC CORPORATION | BSP | T | 12/13/2016 | PAID (REC#1389199) PLAN SPLICE FEE: $50 by: BERTHA for Electrical: As-built electrical plans - No electrical submitted initially. | BERTHA | BERTHA | | BSP | T | 5366337 |
COLARELLI CONSTRUCTION, INC. | BE | L | 12/13/2016 | Renewed at 12/13/2016 9:20:43 AM | JOHN | JOHN | | BE | L | 5366276 |
COLARELLI CONSTRUCTION, INC. | B= | P | 12/16/2015 | Pending electric final. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), FOSTER ELECTRIC CORP Electrical Final Inspection is not Completed yet. | JEREMYA | JEREMYA | | B= | P | 5100274 |
COLARELLI CONSTRUCTION, INC. | BE | L | 12/15/2015 | Renewed at 12/15/2015 11:42:23 AM | RITA | RITA | | BE | L | 5099111 |
COLARELLI CONSTRUCTION, INC. | BFR | P | 05/12/2015 | All interior wall framing OK / Partial pneding electric rough | JEREMYA | JEREMYA | | BFR | P | 4952777 |
FOSTER ELECTRIC CORPORATION | E= | C | 12/22/2016 | | MATTHEW | MATTHEW | | E= | C | 5374475 |
FOSTER ELECTRIC CORPORATION | E= | P | 12/20/2016 | new outlets on plans not installed, panel schedules incorrect, floor plan does not match | MATTHEW | MATTHEW | | E= | P | 5372600 |
FOSTER ELECTRIC CORPORATION | E= | P | 12/15/2016 | need gfci protection within 6' of sinks in rooms 405 and 406, panel schedules don't match circuit numbers on plans, outlets shown on plans either not installed or I can't verify if they're installed because if furniture, floor plan does not match existing conditions | MATTHEW | MATTHEW | | E= | P | 5369241 |
FOSTER ELECTRIC CORPORATION | EE | L | 12/13/2016 | Renewed at 12/13/2016 9:22:44 AM | JOHN | JOHN | | EE | L | 5366277 |
FOSTER ELECTRIC CORPORATION | E= | L | 12/16/2015 | plans need to be revised, ceiling opened and contractor on site | MATTHEW | MATTHEW | | E= | L | 5099935 |
FOSTER ELECTRIC CORPORATION | EE | L | 12/15/2015 | Renewed online for 1/2 Fee at 12/15/2015 12:15:41 PM (RECEIPT #: 1304255) | WEBSITE | WEBSITE | | EE | L | 5099172 |
FOSTER ELECTRIC CORPORATION | ER | P | 05/13/2015 | Hospital grade mc cable used thru out, walls in 2-locations | GARYL | GARYL | | ER | P | 4954227 |