STAUFFER AND SONS CONSTRUCTION | B= | C | 12/18/2015 | | BOBF | BOBF | | B= | C | 5102004 |
STAUFFER AND SONS CONSTRUCTION | B= | R | 12/16/2015 | complete all decks / need 18
complete all decks / need 18" non-combustable hearth
'" | DALE | DALE | | B= | R | 5099920 |
STAUFFER AND SONS CONSTRUCTION | BFR | C | 12/08/2015 | stair ok | DALE | DALE | | BFR | C | 5094191 |
STAUFFER AND SONS CONSTRUCTION | BFR | P | 10/05/2015 | stairs to upper level still not installed , will need to inspect after installed with landing prior to covering up / eng letter for hardware substitution and 6 member plate on file / all other items complete | BOBF | BOBF | | BFR | P | 5050984 |
STAUFFER AND SONS CONSTRUCTION | BIN | C | 10/05/2015 | | BOBF | BOBF | | BIN | C | 5050977 |
STAUFFER AND SONS CONSTRUCTION | BFR | R | 09/30/2015 | 45 brace truss laterials / foam and firestop / strap top plates thru-out / no stairs in to upper floor / hanger at front hip not per plans / need eng. on built up plates by front door / clip porch rafters / cannot see post to beam at porch columns / ok to insulate | DALE | DALE | | BFR | R | 5047666 |
STAUFFER AND SONS CONSTRUCTION | BLA | C | 09/30/2015 | rear only | DALE | DALE | | BLA | C | 5047660 |
STAUFFER AND SONS CONSTRUCTION | BLA | R | 09/29/2015 | no lath, siding | DALE | DALE | | BLA | R | 5046467 |
STAUFFER AND SONS CONSTRUCTION | BSP | T | 09/22/2015 | PAID (REC#1289829) PLAN SPLICE FEE: $50 by: RUSSELL for Mechanical: New furnace change out of supplier | RUSSELL | RUSSELL | | BSP | T | 5041716 |
STAUFFER AND SONS CONSTRUCTION | BSP | P | 08/25/2015 | deck piers ok | DALE | DALE | | BSP | P | 5021835 |
STAUFFER AND SONS CONSTRUCTION | BSP | P | 07/30/2015 | drain reinstalled / exterior entire foundation except at walkout level | BOBF | BOBF | | BSP | P | 5004296 |
STAUFFER AND SONS CONSTRUCTION | BFD | C | 07/17/2015 | | DALE | DALE | | BFD | C | 4995694 |
STAUFFER AND SONS CONSTRUCTION | BFI | C | 07/17/2015 | | DALE | DALE | | BFI | C | 4995690 |
STAUFFER AND SONS CONSTRUCTION | BFN | C | 07/08/2015 | all paperwork on file / float / drain usable | DALE | DALE | | BFN | C | 4988843 |
STAUFFER AND SONS CONSTRUCTION | BFT | C | 07/06/2015 | including interior pads | DALE | DALE | | BFT | C | 4986950 |
STAUFFER AND SONS CONSTRUCTION | BFT | P | 06/04/2015 | AUTHORIZED INSPECTION BY ENGINEER | JANE | JANE | JANE | BFT | P | 4967104 |
STAUFFER AND SONS CONSTRUCTION | BFN | P | 06/04/2015 | AUTHORIZED INSPECTION BY ENGINEER | JANE | JANE | JANE | BFN | P | 4967103 |
ROWAN ELECTRIC LLC | E= | C | 12/10/2015 | | JOSEPH | JOSEPH | | E= | C | 5096338 |
ROWAN ELECTRIC LLC | E= | R | 12/09/2015 | front outlet loose and seal around ------------ label panel -------- afci wet bar and dining room ---------- install class 2 xfmr -------- deck outlet up stair not wr type ----------- gfi outlet by furnace wired wrong ----------- a/c pre wire | CRAIG | CRAIG | | E= | R | 5095763 |
ROWAN ELECTRIC LLC | ES | C | 12/09/2015 | Residential Underground: 200 amp 3/w new res seal meter | CRAIG | CRAIG | | ES | C | 5095759 |
ROWAN ELECTRIC LLC | ES | P | 09/29/2015 | Residential Underground: 200 amp 3/w: new res--------------- contractor is not ready to remove temp power (feeds rv that homeowners are living in) contractor will recall service with final---- service ok | MATTHEW | MATTHEW | | ES | P | 5046998 |
ROWAN ELECTRIC LLC | ER | C | 09/29/2015 | | MATTHEW | MATTHEW | | ER | C | 5046995 |
ROWAN ELECTRIC LLC | ER | R | 09/28/2015 | add outlet in rec room, basement bedroom, left of slider in nook and verify spacing at basement slider (slider not installed)---------deck outlet can't be on small appliance circuit, seal return air------- finished basement, 6-3nm to cooking, no mcc's, no vac | MATTHEW | MATTHEW | | ER | R | 5045713 |
ROWAN ELECTRIC LLC | EUG | C | 09/23/2015 | 3/w 350 mcm al from pedestal to house | CRAIG | CRAIG | | EUG | C | 5043000 |
ROWAN ELECTRIC LLC | EUG | P | 09/08/2015 | 10-3 uf from well head to home | MATTHEW | MATTHEW | | EUG | P | 5031958 |
THE FURNACE GUY HEATING & COOLING | H= | C | 12/09/2015 | Notes-- AC rough. Direct vent furnace x 2. | JEFFL | JEFFL | | H= | C | 5095137 |
UNIQUE RADIANT HTG. & PLBG. | HC | C | 10/27/2015 | RELEASE METER | JEFFL | JEFFL | | HC | C | 5066739 |
UNIQUE RADIANT HTG. & PLBG. | HO | C | 10/27/2015 | 10 LB. test ok. | JEFFL | JEFFL | | HO | C | 5066734 |
SPRINGS GAS, INC. | HI | C | 09/24/2015 | 10# GAS TEST GOOD. 1 1/4'' MAIN. TWO FURNACES WATER HEATER BBQ FUTURE FIREPLACE. RANGE FUTURE 3/4'' TEE MECHANICAL ROOM.. | LUKE | LUKE | | HI | C | 5043796 |
UNIQUE RADIANT HTG. & PLBG. | HO | P | 09/24/2015 | WHERE IS THE METER GOING TO BE? HIGH PRESSURE PIPELINE IS UNDER CONSTRUCTION AT THE STREET.. 60 # GAS TEST ON 3/4'' POLY FROM HOUSE TO 2'' MAIN OK . MAIN FROM STREET NOT TIED TOGETHER AT THIS TIME. TO NEW 3/4'' HOUSE LINE. ADDED NOTE 9-25-15 OK TO COVER UNDER GROUND 3/4'' POLY FROM HOUSE TO 2'' MAIN.. STILL NEED TEST FROM METER TO 2X3/4'' CONNECTION. HO | LUKE | LUKE | | HO | P | 5043795 |
THE FURNACE GUY HEATING & COOLING | HRR | C | 09/24/2015 | A/C AIR TEST GOOD.. | LUKE | LUKE | | HRR | C | 5043794 |
THE FURNACE GUY HEATING & COOLING | HRR | P | 09/23/2015 | LOW TEST ON A/C LINE, NEED TO SEAL PLUMBING RUNNING THROUGH RETURN AIR BASEMENT ABOVE BATH ROOM. REST GOOD. FINISHED BASEMENT, NO OUTSIDE AIR, A/C ROUGH LINE SET AND COIL MAIN LEVEL FURNACE ONLY, FUTURE FIREPLACE VENT GOOD.. | LUKE | LUKE | | HRR | P | 5042523 |
THE FURNACE GUY HEATING & COOLING | HRR | R | 09/21/2015 | No plans on site. Line-set will need to be on test and finished at re-inspect, seal upper RA blocking at master bedroom main floor, nail protection at line-set, is there a fireplace set in basement? Re-check all RA's/panning, in basement, not ready re-inspect all. | STEVEC | STEVEC | | HRR | R | 5040893 |
UNIQUE RADIANT HTG. & PLBG. | P= | C | 12/09/2015 | pvb installed | TIM | TIM | | P= | C | 5095611 |
UNIQUE RADIANT HTG. & PLBG. | P= | P | 12/07/2015 | received potable water cert | TIM | TIM | | P= | P | 5092666 |
UNIQUE RADIANT HTG. & PLBG. | PTO | C | 09/29/2015 | | TIM | TIM | | PTO | C | 5046731 |
UNIQUE RADIANT HTG. & PLBG. | PTO | R | 09/28/2015 | complete house dwv main to outside footer, install and connect sewage ejector pit piping to 4'' and retest all, complete well piping inside basement ceiling, note: finished basement | TED | TED | | PTO | R | 5045615 |
UNIQUE RADIANT HTG. & PLBG. | PWO | C | 09/14/2015 | | TIM | TIM | | PWO | C | 5035603 |
UNIQUE RADIANT HTG. & PLBG. | PWO | R | 09/09/2015 | not ready need tie in at well upload pics on re-call | TIM | TIM | | PWO | R | 5032650 |
UNIQUE RADIANT HTG. & PLBG. | PB | C | 08/27/2015 | basement drains to sewage ejector pit | TED | TED | | PB | C | 5023563 |
UNIQUE RADIANT HTG. & PLBG. | PB | T | 08/26/2015 | PAID (REC#1283444): low test/ bad gage | TED | TED | | PB | T | 5022917 |
UNIQUE RADIANT HTG. & PLBG. | PB | P | 08/05/2015 | low test piping needs to be on a solid base | TIM | TIM | | PB | P | 5008614 |