HORIZON RETAIL CONSTRUCTION, INC | B= | C | 12/30/2015 | All other required Final inspections are complete. (This is a computer generated result) | TOMG | TOMG | | B= | C | 5107734 |
HORIZON RETAIL CONSTRUCTION, INC | B= | P | 08/21/2015 | Building final ok pending fire and mechanical approval. Ok for TCO pending fire approval. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), MAGNUM EDGE,INC. Mechanical Final Inspection is not Completed yet. | TOMG | TOMG | | B= | P | 5019638 |
HORIZON RETAIL CONSTRUCTION, INC | BFR | P | 08/01/2015 | Partial frame for walls, soffits, and hard lid areas | TOMG | TOMG | | BFR | P | 5006089 |
HORIZON RETAIL CONSTRUCTION, INC | BFR | P | 07/28/2015 | columns at store entries and exterior walls and inside of bathroom framing OK pending other roughs / NOTE: shut off valve access is left of toilet / all ceilings, interior walls (except bathroom) and horizontal assembly need inspection still. | DANE | DANE | | BFR | P | 5002972 |
EL PASO ELECTRIC, LLC. | E= | C | 08/17/2015 | | GARYL | GARYL | | E= | C | 5016425 |
EL PASO ELECTRIC, LLC. | ER | P | 07/30/2015 | ceilings only | GARYL | GARYL | | ER | P | 5004651 |
EL PASO ELECTRIC, LLC. | ER | P | 07/29/2015 | all walls, | GARYL | GARYL | | ER | P | 5003682 |
EL PASO ELECTRIC, LLC. | ER | P | 07/27/2015 | marked on plans | CRAIG | CRAIG | | ER | P | 5001232 |
MAGNUM EDGE,INC. | H= | C | 12/28/2015 | MECHANICAL FINAL OK. PER CONTRACTOR VENT CAP ON ROOF IS NOT FROM KAY JEWELERS. | NANCY | NANCY | | H= | C | 5105768 |
MAGNUM EDGE,INC. | H= | P | 12/23/2015 | PROPERLY TRAP CONDENSATE ON UNIT. VERIFY IF THAT NEW EXHAUST CAP COMES FROM KAY JEWELERS, IF YES, SCREEN AND INSTALL RAIN COLLAR. | NANCY | NANCY | | H= | P | 5105122 |
MAGNUM EDGE,INC. | H= | P | 12/14/2015 | TEST AND BALANCE REPORT RECEIVED. STILL NEED TO SEE NEW UNIT. IF SMOKE DETECTOR IS IN RETURN AIR DROP WILL NEED TO SEE DETECTOR. PROVIDE A CALL AHEAD NUMBER AND A CONTACT PERSON TO MEET ME ON SITE TO PROVIDE ROOF ACCESS FOR NEXT INSPECTION. | NANCY | NANCY | | H= | P | 5097865 |
MAGNUM EDGE,INC. | H= | P | 08/20/2015 | INSTALL NEW UNIT. LABEL UNIT WITH SPACE 439. INSTALL SMOKE DETECTOR. VERIFY IF SMOKE DETECTOR IS BEING MONITORED BY MALL, IF NOT NEED REMOTE INDICATOR. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5019313 |
MAGNUM EDGE,INC. | HD | P | 07/27/2015 | REMOVE OLD SMOKE DETECTOR IN RETURN AIR DROP, INSTALL NEW SMOKE DETECTOR IN UNIT OR IN CORRECT LOCATION IN DROP. IF INSTALLING ABOVE CEILING WILL NEED ACCESS AT FINAL. VERIFY DETECTOR IS BEING MONITORED BY MALL SYSTEM. VERIFY IF SEISMIC INSTALLATION IS REQUIRED FOR CEILING GRID. ROUGH SUPPLIES, RETURNS AND FLEX ABOVE CEILING OK. NO DIFFUSERS, BATH EXHAUST OR ROOF YET. | NANCY | NANCY | | HD | P | 5001683 |
WRIGHT-JONES PLUMBING & HEATING | P= | C | 08/13/2015 | TO PLAN , ISOLATION VALVE IN BATH ROOM | GABE | GABE | | P= | C | 5014586 |
WRIGHT-JONES PLUMBING & HEATING | PTO | C | 07/28/2015 | TOILET , MOP SINK . ALL DWV AND WATER OK , CHECK WATER HEATER AT FINAL | GABE | GABE | | PTO | C | 5002954 |
WRIGHT-JONES PLUMBING & HEATING | PB | R | 07/22/2015 | SHOULD BE TRIP FEE , NO ACCESS ALL DOORS LOCKED , LADDER NOT TALL ENOUGH TO ACCESS PLUMBING WORK . RE INSPECT ALL | GABE | GABE | | PB | R | 4998945 |