GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 10/11/2016 | All other required Final inspections are complete. (This is a computer generated result) | DANE | DANE | | B= | C | 5314974 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 07/27/2016 | damper has been spliced into plans / OK pending other finals. UPDATE: 9/20/16 after review of permit with Jerry F. no splice for damper can be found./After further review 10-10-16 Bert spoke with Ryan damper is on sheet M103-5. ok to sign off/changed to a completion on 10-10-16 Additional Inspections Required (computer generated): MECH ONE, INC. Mechanical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 5254695 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 04/15/2016 | Room 3538 needs damper on plans all else ok. Additional Inspections Required (computer generated): MECH ONE, INC. Mechanical Final Inspection is not Completed yet. | BERTW | BERTW | | B= | P | 5177693 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BE | L | 04/14/2016 | Renewed at 4/14/2016 3:44:33 PM | KENYATTA | KENYATTA | | BE | L | 5177608 |
MECHONE, INC. | BSP | T | 03/02/2016 | PAID (REC#1315974) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: revised to add TB-32 and an additional t-stat | DALEH | DALEH | | BSP | T | 5146099 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 09/25/2015 | need a listing for 18x6" duct penetration in fire barrier wall above door in room #3538 all else ok -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), MECH ONE, INC. Mechanical Final Inspection is not Completed yet. | BERTW | BERTW | | B= | P | 5044770 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | C | 09/25/2015 | | BERTW | BERTW | | BFR | C | 5044537 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 09/16/2015 | above grid firecaulikng inspection on smoke barriers ok/need mech inspection for possible damper install @ room #3538 for duct on my previous comments in fire barrier wall/reviewed with Chris and Ryan job supers | BERTW | BERTW | | BSP | P | 5037450 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 08/28/2015 | 3-5 floors soffits corridors ok/pending other roughs completed | BERTW | BERTW | | BFR | P | 5024666 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 08/14/2015 | Rooms 35 and 38 Fire barrier walls ok,need vertical wall 3 layers inspected/all other sheetrocking ok/need a listing for 18x6" duct penetration above door and firecaulking inspections | BERTW | BERTW | | BFR | P | 5015389 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 07/28/2015 | reviewed mech damper installation and removal with job super Chris/need mech inspections on these areas | BERTW | BERTW | | BSP | P | 5002318 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 07/13/2015 | floors 3 and 5 ok pending other roughs completed,room 3538 on the 3rd floor calls for rated wall using U465 listing,there are conduits and other items that create a continuity issue to the deck above-the walls are called out as partitions but there is a non-rated ceiling in this room-need stamped detail for how to build this wall | BERTW | BERTW | | BFR | P | 4991497 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 03/25/2016 | | CRAIGS | CRAIGS | | E= | C | 5162233 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 09/25/2015 | FIRE ALARM INSPECTION: | CRAIGS | CRAIGS | | E= | C | 5044180 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | R | 09/24/2015 | For patient rooms on 3rd floor boxes must be flush with bed wall---room 3516 receptacle top left of bed wall circuit EL3N2-36 reverse polarity----room 3530 receptacle left hand side bed wall under rail circuit L3N1-18 reverse polarity---nurses station west 3rd floor ok----nurses station 5th floor ok as marked on plan
| SHELBY | SHELBY | | ER | R | 5043497 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 09/23/2015 | 5th floor east OK | CRAIGS | CRAIGS | | E= | P | 5042268 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 09/22/2015 | 5th floor bed area receps checked OK | CRAIGS | CRAIGS | | E= | P | 5041191 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 09/21/2015 | corridors on 3rd and 5th----ABOVE CEILINGS--------AND FIRE ALARM---------STILL NEED TO SEE THE DOOR OPENERS CONNECTIONS ON NEXT INSPECTION------- | BRIAN | BRIAN | | ER | P | 5040284 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 09/17/2015 | FIRE ALARM INSPECTION: ceiling and walls marked on plan this date | SHELBY | SHELBY | | ER | P | 5038389 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 09/17/2015 | bedwalls and ceiling as marked on plans this date | SHELBY | SHELBY | | ER | P | 5038374 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 09/15/2015 | 3ard and 5th floor above ceiling electrical OK --- all low voltage needs to be supported off the grid | CRAIGS | CRAIGS | | ER | P | 5036875 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 09/15/2015 | FIRE ALARM INSPECTION: 3ard and 5th floor rooms above ceiling OK | CRAIGS | CRAIGS | | ER | P | 5036874 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 09/04/2015 | WALLS 3RD AND 5TH------BED LOCATIONS----SEE PLANS------ | BRIAN | BRIAN | | ER | P | 5030456 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 08/31/2015 | hard rock ceiling in nurses area 3rd floor and head walls 3rd floor | CRAIGS | CRAIGS | | ER | P | 5025424 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 08/27/2015 | soffits 3rd and 5th floor see approved drawings | CRAIGS | CRAIGS | | ER | P | 5023489 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | R | 08/25/2015 | no more than 6' of flex in the circuit to maintain the redundant ground ---- head wall 3rd floor | CRAIGS | CRAIGS | | ER | R | 5021348 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 08/24/2015 | 3ard and 5th floor bathroom hard lids | CRAIGS | CRAIGS | | ER | P | 5020454 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 08/11/2015 | 3rd floor icu walls except head board walls. | BRET | BRET | | ER | P | 5011963 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 08/05/2015 | 5TH floor bath room walls OK high lighted in red on the approved drawings NOTE told the contractor he needs a stand alone fire alarm permit | CRAIGS | CRAIGS | | ER | P | 5008193 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 08/03/2015 | 3536,3538 wall, 3rd floor bathrooms except icu area bathrooms. | BRET | BRET | | ER | P | 5006384 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 07/30/2015 | as marked on the plan 3rd and fifth floor this date walls OK | SHELBY | SHELBY | | ER | P | 5005063 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 07/28/2015 | walls 3ard and 5th floor -- see approved drawings | CRAIGS | CRAIGS | | ER | P | 5002043 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 07/24/2015 | toe walls and switches at the room door high lighted in dark blue , see approved drawings | CRAIGS | CRAIGS | | ER | P | 5000161 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 07/22/2015 | 5th floor head walls --- high lighted in green on the approved drawings | CRAIGS | CRAIGS | | ER | P | 4998203 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 07/20/2015 | walls high lighted in pink see approved drawings | CRAIGS | CRAIGS | | ER | P | 4996217 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 07/14/2015 | 3rd floor bed areas high lighted on page e 303.5---OK still need to inspect head board and toe board walls when ready | CRAIGS | CRAIGS | | ER | P | 4992391 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 07/10/2015 | walls 3rd and 5th floor, patient bed locations. Areas are marked on the approved set of plans. Ok to pre-rock headboard walls. Will still need to see headboard wiring when ready. | DEAN | DEAN | | ER | P | 4990617 |
MECHONE, INC. | H= | C | 10/11/2016 | all ok | JERRYF | JERRYF | | H= | C | 5314973 |
MECHONE, INC. | H= | P | 09/01/2016 | TAB REPORT RECEIVED - NEED OTHER NOTES ADDRESSED | JERRYF | JERRYF | | H= | P | 5282930 |
MECHONE, INC. | HD | C | 07/07/2016 | 2 6x6 dampers complete for phone room 3rd floor room 3524 complete. See all notes for final inspection. still need balance report as well. | JON | JON | | HD | C | 5239653 |
MECHONE, INC. | HD | P | 07/06/2016 | FRAMING FOR 2 6X6 DAMPERS OK 3RD FLOOR ROOM 3524 | JON | JON | | HD | P | 5238776 |
MECHONE, INC. | HD | P | 03/21/2016 | NEED PLAN REVISION COMPLETED TO VERIFY DAMPER TYPE | JERRYF | JERRYF | | HD | P | 5159547 |
MECHONE, INC. | HD | P | 03/15/2016 | FIRE DAMPER AT ROOM 3538 FRAMING OK.. NEED TO GET WITH BUILDING AND PREVIOUS MECHANICAL INSPECTOR TO SEE IF PLANS WERE REVISED FOR THIS DAMPER. FRAMING OK, NO DAMPER YET. | JON | JON | | HD | P | 5155779 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 03/08/2016 | PLAN HAS BEEN REVISED - ALL OK | JERRYF | JERRYF | | H= | C | 5149668 |
OLSON PLUMBING & HEATING COMPANY | H= | P | 10/01/2015 | NEED PLAN REVISED SHOWING FCU 3-2 AS BEING DELETED - 3TD FLOOR FCU 3-1 AND VAV3-1 PIPING ABOVE CEILING AND FINAL CONNECTIONS OK - ALL CONDENSATE DRAINS ARE ROUTED TO MOP SINKS - 5TH FLOOR FCU 5-1 AND 5-2 PIPING ABOVE CEILING OK AND CONDENSATE DRAINS ARE ROUTED TO MOP SINKS | JERRYF | JERRYF | | H= | P | 5048809 |
MECHONE, INC. | H= | P | 09/23/2015 | PENDING BALANCE REPORT AND CONVERSATION WITH PREVIOUS INSPECTOR. ALSO NEED PERMIT AND INSPECTION FOR CHILLED WATER TO NEW FAN COILS FOR it ROOM BOTH 3RD AND 5TH FLOORS NEAR COLUMN LINES 2 AND 3. STILL NEED SPLICES FOR ADDING FIRE DAMPERS PER PREVIOUS NOTES. | JON | JON | | H= | P | 5042658 |
MECHONE, INC. | HD | P | 09/15/2015 | 2 F/SD FRAMING ON 3TD FLOOR CART STORAGE OK - BY FINAL NEED PLAN REVISED SHOWING NEW F/SD X2 | JERRYF | JERRYF | | HD | P | 5036152 |
MECHONE, INC. | HD | P | 09/02/2015 | F/DS DAMPER AND RETAINAGE OK ON THE FOLLOWING 5TH FLOOR 5510 - 5507 - 5508 - 5506 - 5539 - 5532 - 5530 - 5562 - 5556 - 3TD FLOOR - 3506 - SOUTH CORRIDOR - 3516 - 3531 - 3527 - 3508 - 3532 | JERRYF | JERRYF | | HD | P | 5028838 |
MECHONE, INC. | HD | P | 08/25/2015 | F/SD FRAME OK AT DOOR 5506A OK F/SD DOOR 3527A FRAME OK | JERRYF | JERRYF | | HD | P | 5021848 |
MECHONE, INC. | HD | P | 08/21/2015 | INSPECTED DAMPER FRAMING FOR KING STUDS AT "5506 A" SMOKE BARRIER DOORS AND "3527 A" ONLY.. NEED TO FINISH WORK ON KING STUDS AND SECURE TO EACH OTHER. ALSO FRAMING ABOVE DAMPER OPENINGS ARE TO BE COMPLETE ON FRAMING TO SUPPORT STRUCTURE ON BOTH OPENINGS. | JON | JON | | HD | P | 5019780 |
MECHONE, INC. | HD | P | 08/18/2015 | THE FOLLOWING DAMPER FRAMING IS OK = 5TH FLOOR - NORTH CORRIDOR TRANSFER AIR AND 12X10 TRANSFER - 3TD FLOOR NORTH CORRIDOR CONTROL DOOR 24X12 - SOUTH CORRIDOR 8X8 TRANSFER - 34X12 TRANSFER - 8X8 AND 14X14 AT DOOR 3509 - NORTH CORRIDOR 3530 12X8 TRANSFER - 3527A 12X6 TRANSFER - | JERRYF | JERRYF | | HD | P | 5017229 |
MECHONE, INC. | HD | P | 08/17/2015 | Fire damper Framing for rooms 5506, 5520, 3531, and 3508 ok. Smoke Barrier damper framing for 5506a and 3527a ok. Need to verify max opening square inches allowed as smoke barrier openings are greater than 36". Also question smoke detection at return air shaft openings. | JON | JON | | HD | P | 5015924 |
MECHONE, INC. | HD | P | 08/06/2015 | 11 F/D FRAMING OK ON 5TH FLOOR - 4 F/D FRAMING ON 3TD FLOOR OK | JERRYF | JERRYF | | HD | P | 5009485 |
MECHONE, INC. | HD | P | 08/03/2015 | 66 X 24 AND 2 4 X 24 F/D FRAMING ON 5TH FLOOR CORRIDOR OK - NEED ALL OTHER 3TD AND 5TH FLOOR F/D FRAMING FRAMED PER INSTALL MANUAL | JERRYF | JERRYF | | HD | P | 5006603 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 09/23/2015 | 3rd and 5th floor ok | TED | TED | | P= | C | 5042207 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 08/27/2015 | rooms 5556, 5558, 5560, 5562, 5564, 5566 walls ceiling and under floor ok | TED | TED | | PTO | P | 5023373 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 08/18/2015 | rooms 3514, 3516, 3518, 3520, 3522, 3526, 3530, 3532, 3534 3536, 5514, 5516, 55185520, 5522, 5524, 5526, 5530,5532, 5534, 5536, 5538, 5540, dwv and water in walls and under floor ok | TED | TED | | PTO | P | 5016802 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 08/05/2015 | rooms, 3502,3504,3506, 3508, 3510, 3512,--5502, 5504, 5506, 5508, 5510, 5512, dwv and water ok in walls, need to correct dwv connections in floors below (correction made and inspected on 8-18 ) | TED | TED | | PTO | P | 5008145 |