HOMEOWNER | B= | C | 04/18/2016 | All other required Final inspections are complete. (This is a computer generated result) | ERICR | ERICR | | B= | C | 5178799 |
HOMEOWNER | B= | P | 04/01/2016 | corrections completed/ received stamped engineers letter. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977). | ERICR | ERICR | | B= | P | 5167821 |
HOMEOWNER | BFR | C | 04/01/2016 | | ERICR | ERICR | | BFR | C | 5167521 |
HOMEOWNER | BFR | C | 03/31/2016 | corrections completed | ERICR | ERICR | | BFR | C | 5166793 |
HOMEOWNER | B= | P | 03/31/2016 | Built window well out of stones over 4'-0 deep need letter from engineer / Need steps from house to garage/ need fire and engineering finals / truss splice was completed -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977). | ERICR | ERICR | | B= | P | 5166789 |
HOMEOWNER | BSP | T | 03/11/2016 | PAID (REC#1320495): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: New truss engineering | MICHAELA | MICHAELA | | BSP | T | 5153662 |
HOMEOWNER | BLA | C | 01/05/2016 | | BRIANB | BRIANB | | BLA | C | 5110027 |
HOMEOWNER | BIN | P | 12/21/2015 | insulation okay / pending completed BFR inspection | BRIANB | BRIANB | | BIN | P | 5103215 |
HOMEOWNER | BFR | P | 12/21/2015 | still need to splice revised truss design - trusses installed do not match approved design / will need engineering letter for new columns installed under new girder trusses not on approved plans / all other corrections from previous inspection okay | BRIANB | BRIANB | | BFR | P | 5103211 |
HOMEOWNER | BFR | P | 12/17/2015 | missing bracing at T02 & T02C1 trusses / corrections from previous inspection okay / front porch lid, posts and deck frame okay / rear porch lid, posts okay - still need rear deck frame inspected / okay to insulate | BRIANB | BRIANB | | BFR | P | 5100723 |
HOMEOWNER | BSP | T | 12/16/2015 | PAID (REC#1304525) PLAN SPLICE FEE: $50 by: SHELLEY for Construction: extended MBR and deck | SHELLEY | SHELLEY | | BSP | T | 5100246 |
HOMEOWNER | BFR | P | 12/14/2015 | need to complete drain inspection / trusses installed do not match approved plans - need approved design spliced into permit and all trusses inspected / missing lags at the front porch deck ledger / missing (2) 5" lags at the front porch deck beam to post per approved plans / foam & fire stop / top flange BCI over basement bath damaged and drilled / missing hangers at floor joist headout at front of basement in unfinished area / still need rear deck frame inspection | BRIANB | BRIANB | | BFR | P | 5098661 |
HOMEOWNER | BFD | C | 12/14/2015 | engineering letter of inspection received / still need soils letter / updated 12/17 - soils letter received - inspection completed | BRIANB | BRIANB | | BFD | C | 5098647 |
HOMEOWNER | BFN | C | 12/14/2015 | engineering letter of inspection received / eufer documented / foundation design received | BRIANB | BRIANB | | BFN | C | 5098645 |
HOMEOWNER | BFT | C | 12/14/2015 | engineering letter of inspection received | BRIANB | BRIANB | | BFT | C | 5098640 |
HOMEOWNER | BSP | T | 12/10/2015 | PAID (REC#1303971) PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: changed furnace size | JUSTINC | JUSTINC | | BSP | T | 5096485 |
HOMEOWNER | BSP | P | 11/24/2015 | PLAN SPLICE: (No Fee) by: DALEH for Mechanical | DALEH | DALEH | | BSP | P | 5086923 |
HOMEOWNER | BFD | P | 09/18/2015 | AUTHORIZED INSPECTION BY ENGINEER | BPHILLIPS | BPHILLIPS | BPHILLIPS | BFD | P | 5039265 |
HOMEOWNER | BFT | P | 09/18/2015 | AUTHORIZED INSPECTION BY ENGINEER | BPHILLIPS | BPHILLIPS | BPHILLIPS | BFT | P | 5039264 |
HOMEOWNER | BFN | P | 09/18/2015 | AUTHORIZED INSPECTION BY ENGINEER | BPHILLIPS | BPHILLIPS | BPHILLIPS | BFN | P | 5039263 |
HIGH MOUNTAIN ELECTRIC INC. | E= | C | 03/21/2016 | | MIKEC | MIKEC | | E= | C | 5159656 |
HIGH MOUNTAIN ELECTRIC INC. | ES | C | 12/16/2015 | Residential Underground: 200 AMP 3-W NEW RES------OK TO SET METER---- | BRIAN | BRIAN | | ES | C | 5099860 |
HIGH MOUNTAIN ELECTRIC INC. | ER | C | 12/11/2015 | #6 al to cook top,#8 cu to oven, no mcc call service in with rough service not ready at this time. | BRET | BRET | | ER | C | 5097595 |
AIR CONCEPTS HEATING & COOLING | H= | C | 03/16/2016 | THE APPROVED EQUIPMENT LIST IS ON SITE. | JEFFB | JEFFB | | H= | C | 5156861 |
AIR CONCEPTS HEATING & COOLING | H= | P | 03/10/2016 | NO EQUIPMENT LIST WAS ON SITE. NOTES: DIRECT VENT FURNACE. | JEFFB | JEFFB | | H= | P | 5152147 |
AIR CONCEPTS HEATING & COOLING | HI | C | 12/14/2015 | 10# test o.k. 1" main, furnace, water heater, fireplace. | STEVEC | STEVEC | | HI | C | 5097829 |
AIR CONCEPTS HEATING & COOLING | HC | C | 12/04/2015 | RELEASE METER | STEVEC | STEVEC | | HC | C | 5092207 |
AIR CONCEPTS HEATING & COOLING | HRR | C | 12/04/2015 | Equipment does not match, provide revised heat loss calculations and appliance cert by final. Note: duct design matches, basement finish, outside air to return, no A/C. Check for make-up air to to laundry by final. | STEVEC | STEVEC | | HRR | C | 5092200 |
CHEYENNE PLUMBING & HEATING, INC. | P= | C | 03/30/2016 | correction made, RP installed. | TAYLOR | TAYLOR | | P= | C | 5165679 |
CHEYENNE PLUMBING & HEATING, INC. | P= | T | 03/29/2016 | PAID (REC#1320805) can not use metal T- post to support pvb ( 2 different types of metals ). | TAYLOR | TAYLOR | | P= | T | 5164771 |
CHEYENNE PLUMBING & HEATING, INC. | P= | P | 03/22/2016 | install pvb correctly, rest ok, finished basement. | TAYLOR | TAYLOR | | P= | P | 5160003 |
CHEYENNE PLUMBING & HEATING, INC. | PTO | C | 12/04/2015 | finished basement, 3 inch clean out in bedroom, vents through roof. | TAYLOR | TAYLOR | | PTO | C | 5091865 |
CHEYENNE PLUMBING & HEATING, INC. | PB | C | 10/16/2015 | corrections made. | TAYLOR | TAYLOR | | PB | C | 5059374 |
HOMEOWNER | PB | P | 10/15/2015 | waive trip fee, leak at 3x2 wye for tub. | TAYLOR | TAYLOR | | PB | P | 5058327 |
CHEYENNE PLUMBING & HEATING, INC. | PB | P | 10/14/2015 | washer needs to connect to 3 inch drain, rest ok. | TAYLOR | TAYLOR | | PB | P | 5057123 |
CHEYENNE PLUMBING & HEATING, INC. | PB | R | 10/13/2015 | LOST TEST | GABE | GABE | | PB | R | 5056826 |