BRYAN CONSTRUCTION, INC. | B= | C | 08/15/2016 | | BERTW | BERTW | | B= | C | 5269150 |
BRYAN CONSTRUCTION, INC. | BFR | C | 08/15/2016 | | BERTW | BERTW | | BFR | C | 5269082 |
BRYAN CONSTRUCTION, INC. | BFR | P | 11/24/2015 | construction type 1A floors need 2hr through penetration firestop details for plumbing pipes in floors @ all breakroom sinks/reviewed accessible elements with Nathan job super/all new walls are missing top of wall bracing per plans-check @ final inspection/pending all other roughs completed | BERTW | BERTW | | BFR | P | 5086205 |
BIBLE ELECTRIC, INC. | E= | C | 02/05/2016 | | BRET | BRET | | E= | C | 5129095 |
BIBLE ELECTRIC, INC. | ER | C | 01/19/2016 | CEILINGS OK | BRIAN | BRIAN | | ER | C | 5117833 |
BIBLE ELECTRIC, INC. | ER | P | 01/13/2016 | ceilings ok except east hall 3 fixtures under duct work | BRET | BRET | | ER | P | 5115053 |
BIBLE ELECTRIC, INC. | ER | P | 01/05/2016 | ALL CEILINGS EXCEPT THE 2 HALL WAYS WITH THE 2X2 LIGHTS---SEE PLANS---- | BRIAN | BRIAN | | ER | P | 5109657 |
BIBLE ELECTRIC, INC. | E= | C | 12/22/2015 | FIRE ALARM INSPECTION: | BRET | BRET | | E= | C | 5103514 |
BIBLE ELECTRIC, INC. | ER | C | 12/22/2015 | FIRE ALARM INSPECTION: | BRET | BRET | | ER | C | 5103513 |
BIBLE ELECTRIC, INC. | ER | P | 12/22/2015 | exterior office ceiling ok corridors open office and center offices not ready | BRET | BRET | | ER | P | 5103512 |
BIBLE ELECTRIC, INC. | E= | P | 12/18/2015 | PARTIAL CEILING ---SEE PLANS---- | BRIAN | BRIAN | | E= | P | 5101501 |
BIBLE ELECTRIC, INC. | ER | P | 11/23/2015 | new walls ok | BRET | BRET | | ER | P | 5085839 |
HARMON - BONDED PLUMBING & HEATING, INC. | H= | C | 04/19/2016 | OK | JERRYF | JERRYF | | H= | C | 5179521 |
COLORADO SHEET METAL CO., INC. | H= | C | 04/18/2016 | REVISED TEST AND BALANCE REPORT RECEIVED, OUTSIDE AIR READING INCLUDED. | NANCY | NANCY | | H= | C | 5178770 |
COLORADO SHEET METAL CO., INC. | H= | P | 03/03/2016 | OUTSIDE AIR NOT VERIFIED ON BALANCE REPORT FROM SHEET M-4.. THE CFM NUMBER LISTED OR THE MINIMUM 37% FROM THE FOOT NOTES. RE-REQUEST AND SEND JUST ONE MORE SHEET SHOWING THE MINIMUM OUTSIDE AIR VERIFICATION. THE REPORT ATTACHED ON THIS INSPECTION HAS BEEN UPLOADED. | JON | JON | | H= | P | 5147078 |
COLORADO SHEET METAL CO., INC. | H= | P | 01/22/2016 | PARTIAL PENDING TAB REPORT - REST OK - F/D RETAINAGE OK | JERRYF | JERRYF | | H= | P | 5121368 |
HARMON - BONDED PLUMBING & HEATING, INC. | HWP | P | 01/12/2016 | ABOVE CEILING ON 11 HWP BOX CONNECTIONS OK TO INSULATE | JERRYF | JERRYF | | HWP | P | 5114400 |
COLORADO SHEET METAL CO., INC. | HD | P | 11/25/2015 | TWO FIRE DAMPER FRAMES AT LOBBY WALL OK, OK TO INSTALL DAMPER, OK FOR SHEET ROCK. | NANCY | NANCY | | HD | P | 5087321 |
COLORADO SHEET METAL CO., INC. | HD | P | 11/24/2015 | PROPERLY FRAME TWO FIRE DAMPERS AT LOBBY AREA. ROUGH SUPPLY TRUNK LINES AND LATERALS OK, OK TO WRAP. NO NEW VAV'S YET. KEEP DAMPER INSTALLATION INSTRUCTIONS ON SITE FOR NEXT INSPECTION. | NANCY | NANCY | | HD | P | 5086131 |
HARMON - BONDED PLUMBING & HEATING, INC. | P= | C | 02/04/2016 | correction made | TED | TED | | P= | C | 5128232 |
HARMON - BONDED PLUMBING & HEATING, INC. | P= | R | 02/03/2016 | need approved plans on site, hi- loop for dishwashers, hammer arrestors for ice makers, need ladder and access to water heaters. | TAYLOR | TAYLOR | | P= | R | 5127169 |
HARMON - BONDED PLUMBING & HEATING, INC. | PTO | C | 12/09/2015 | H2O above ceiling and drains below floor for sinks ok, check all water heaters at final. | TAYLOR | TAYLOR | | PTO | C | 5095698 |
HARMON - BONDED PLUMBING & HEATING, INC. | PTO | P | 12/04/2015 | h2o and pan drains in walls only | JOEL | JOEL | | PTO | P | 5092348 |