COLORADO REAL ESTATE GROUP,INC. | B= | C | 02/01/2017 | corrections okay | BRIANB | BRIANB | | B= | C | 5404390 |
COLORADO REAL ESTATE GROUP,INC. | B= | P | 01/25/2017 | Temp CO: All partial ( Expires: 2/24/2017 12:00:00 AM) | JANE | JANE | | B= | P | 5398690 |
COLORADO REAL ESTATE GROUP,INC. | B= | P | 01/24/2017 | missing code compliant numeric address posted on home / missing insulation at crawl space rim / missing ladder at basement window well / unfinished basement / no deck installed -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection HD= by HEALTHDEPT is not Completed yet. | BRIANB | BRIANB | | B= | P | 5396911 |
COLORADO REAL ESTATE GROUP,INC. | BLA | C | 10/03/2016 | | BRIANB | BRIANB | | BLA | C | 5308843 |
COLORADO REAL ESTATE GROUP,INC. | BFD | C | 10/03/2016 | foundation inspections completed 16DEC15 | BRIANB | BRIANB | | BFD | C | 5308795 |
COLORADO REAL ESTATE GROUP,INC. | BSP | R | 08/25/2016 | gas meter release requested with BSP inspection - see comments from HC inspection dated 6/22 / no answer at 650-2647 - no site visit / no inspection done | BRIANB | BRIANB | | BSP | R | 5278101 |
COLORADO REAL ESTATE GROUP,INC. | BIN | C | 06/28/2016 | | BRIANB | BRIANB | | BIN | C | 5232999 |
COLORADO REAL ESTATE GROUP,INC. | BFR | C | 06/28/2016 | corrections from previous inspection okay / garage portal wall nailing completed / unfinished basement / no deck installed | BRIANB | BRIANB | | BFR | C | 5232992 |
COLORADO REAL ESTATE GROUP,INC. | BFR | R | 06/23/2016 | strap top plates that do not overlap / firestop b-vent chase / steel sims under steel beam and glue / ok to insulate | DALE | DALE | | BFR | R | 5229578 |
COLORADO REAL ESTATE GROUP,INC. | BSP | R | 05/31/2016 | what is inspection for? | DALE | DALE | | BSP | R | 5211195 |
COLORADO REAL ESTATE GROUP,INC. | BTR | C | 05/25/2016 | | DALE | DALE | | BTR | C | 5207943 |
COLORADO REAL ESTATE GROUP,INC. | BSP | P | 04/22/2016 | porh lid ok / need to nail narrow braced wall per plan | DALE | DALE | | BSP | P | 5182590 |
COLORADO REAL ESTATE GROUP,INC. | BSP | P | 03/17/2016 | only posts at porch ok | DALE | DALE | | BSP | P | 5157414 |
COLORADO REAL ESTATE GROUP,INC. | BFN | C | 12/16/2015 | ok per eng. | DALE | DALE | | BFN | C | 5099597 |
COLORADO REAL ESTATE GROUP,INC. | BFT | C | 12/16/2015 | ok per eng. | DALE | DALE | | BFT | C | 5099596 |
COLORADO REAL ESTATE GROUP,INC. | BFD | P | 12/10/2015 | need bft and bfn / foundation design and open hole on file | DALE | DALE | | BFD | P | 5096277 |
COLORADO REAL ESTATE GROUP,INC. | BFT | P | 11/13/2015 | AUTHORIZED INSPECTION BY ENGINEER | MINDY | MINDY | MINDY | BFT | P | 5078948 |
COLORADO REAL ESTATE GROUP,INC. | BFN | P | 11/13/2015 | AUTHORIZED INSPECTION BY ENGINEER | MINDY | MINDY | MINDY | BFN | P | 5078947 |
SOUTHERN COLORADO ELECTRIC INC. | E= | C | 01/23/2017 | | JOSEPH | JOSEPH | | E= | C | 5395646 |
SOUTHERN COLORADO ELECTRIC INC. | E= | T | 01/20/2017 | PAID (REC#1396615): Still missing dedicated circuit for ejection pit. This has now been requested 3 times. | JOSEPH | JOSEPH | | E= | T | 5394898 |
SOUTHERN COLORADO ELECTRIC INC. | E= | R | 01/19/2017 | inter-system bond terminal still buried, gfci protect front outlet, gfci protect fireplace in master bath, need dedicated 20 amp circuit for spa (need dead face and 12-2nm), need afci and gfci for washer, no power to smokes (check living room), box above tub deck has energized nm in it; disconnect from source and cut so it can't be re-energized, need dedicated circuit for sump pit, provide paperwork for exterior arch lights----------------- closet shelves not installed at final------------- 30 amp a/c installed | MATTHEW | MATTHEW | | E= | R | 5393557 |
SOUTHERN COLORADO ELECTRIC INC. | ES | C | 01/19/2017 | Residential Underground: 200 amp 3/w: new res-------- meter is set; need seal | MATTHEW | MATTHEW | | ES | C | 5393553 |
SOUTHERN COLORADO ELECTRIC INC. | ES | R | 01/17/2017 | Cut or remove old cables in utility pedestal. Presently they are about 1 - 2 inches from live terminals. ---------- | JOSEPH | JOSEPH | | ES | R | 5391051 |
SOUTHERN COLORADO ELECTRIC INC. | E= | T | 01/17/2017 | PAID (REC#1395983): Complete re-inspection required. Following is a partial list only. ---------- Wire ac unit ---------No access to jetted tub ------- Driveway coach lights not wired and contractor says they will not be wired at final.-------- No power to 1/2 of garage receptacles --------- Protect cables at garage exterior wall between garage doors.------------Inter-system bonding terminal buried in stucco.------------ Many switches don't seem to switch anything.---------Show with paperwork that puck lights are listed for exterior use.-------No power to exterior receptacles--------Exterior boxes not listed for wet location.-----Remove cover at fireplace next to jetted tub.----- Pull wall oven out to show that contractor used CU/AL fittings.-------Need dedicated circuit for pit motor and outlet should be within 2 - 3 feet of pit. ------------Too much to list --------had to stop after 45 min. ---------Electrician needs to hot check entire house b | JOSEPH | JOSEPH | | E= | T | 5391050 |
SOUTHERN COLORADO ELECTRIC INC. | EUG | C | 07/20/2016 | From well head to home | JOSEPH | JOSEPH | | EUG | C | 5249852 |
SOUTHERN COLORADO ELECTRIC INC. | ES | R | 05/10/2016 | Tape yellow service neutral with white tape.---------GEC in service disconnect should terminate at service neutral not just panel enclosure.-------Remove temp and terminate in utility pedestal | JOSEPH | JOSEPH | | ES | R | 5195676 |
SOUTHERN COLORADO ELECTRIC INC. | ER | C | 05/10/2016 | Electrical contractor says that outlet spacing behind kitchen sink is ok because of the distance from sink to window.-----------Notes unfinished basement---------Sub panel ok------6/3 cu------------6/3 al------------14/3---------no vac----------UFER is in basement and is not ir | JOSEPH | JOSEPH | | ER | C | 5195669 |
EAGLE HEATING AND AIR CONDITIONING, INC. | H= | C | 01/18/2017 | Unfinished basement. Note: A/C complete, conditioned crawlspace. | JEFFL | JEFFL | | H= | C | 5391958 |
EAGLE HEATING AND AIR CONDITIONING, INC. | HC | C | 06/22/2016 | RELEASE METER | JEFFL | JEFFL | | HC | C | 5228715 |
EAGLE HEATING AND AIR CONDITIONING, INC. | HRR | C | 06/22/2016 | Corrections made. | JEFFL | JEFFL | | HRR | C | 5228705 |
EAGLE HEATING AND AIR CONDITIONING, INC. | HRR | P | 05/05/2016 | Bath exhausts not complete. Rest ok. Notes-- unfinished basement.. direct vent furnace.. Duct design.. **Equipment cert needs to be on sight at final to verify furnace capacity. | JEFFL | JEFFL | | HRR | P | 5193093 |
WHITE BROS CUSTOM PLUMBING & HEATING | HI | C | 04/21/2016 | 10 LB. test ok. Notes-- 1 1/4'' main.. 1furnace.. 2wh..2fp.. 1 dryer | JEFFL | JEFFL | | HI | C | 5182147 |
WHITE BROS CUSTOM PLUMBING & HEATING | P= | C | 01/24/2017 | received potable water cert | TIM | TIM | | P= | C | 5396329 |
WHITE BROS CUSTOM PLUMBING & HEATING | P= | P | 12/09/2016 | need potable water cert | TIM | TIM | | P= | P | 5364890 |
WHITE BROS CUSTOM PLUMBING & HEATING | PTO | C | 04/21/2016 | by final need access to tempering valve at master tub | TIM | TIM | | PTO | C | 5181964 |
WHITE BROS CUSTOM PLUMBING & HEATING | PB | C | 04/08/2016 | | TIM | TIM | | PB | C | 5173425 |
HOMEOWNER | PWO | C | 03/17/2016 | | TIM | TIM | | PWO | C | 5157675 |