WELLS & WEST GENERAL CONTRACTORS, INC. | B= | C | 05/16/2016 | All other required Final inspections are complete. (This is a computer generated result) | BRIANB | BRIANB | | B= | C | 5199669 |
WELLS & WEST GENERAL CONTRACTORS, INC. | B= | P | 05/12/2016 | building okay / pending other final inspections. Additional Inspections Required (computer generated): AIR TECH MECHANICAL INC Mechanical Final Inspection is not Completed yet. | BRIANB | BRIANB | | B= | P | 5197888 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 02/23/2016 | room 202 framing okay / should be last of framing inspections | NATHAN | NATHAN | | BFR | P | 5140149 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 02/04/2016 | 2nd floor - light steel stud framing at office 218 & 219 okay / 2nd floor in-fill light steel framing per plan okay / still need to inspect framing for office 202 / pending electrical and mechanical inspections | BRIANB | BRIANB | | BFR | P | 5128377 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BSP | P | 01/29/2016 | PLAN SPLICE: (No Fee) by: SHELLEY for Construction: revised floor plan | SHELLEY | SHELLEY | | BSP | P | 5126160 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BSP | P | 01/29/2016 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: added 2 offices, added 1 new secure office | JUSTINC | JUSTINC | | BSP | P | 5126116 |
PROCOM ELECTRICAL SERVICES, INC. | BSP | T | 01/29/2016 | PAID (REC#1310913) PLAN SPLICE FEE: $50 by: TIMA for Electrical: floor plan revesion | TIMA | TIMA | | BSP | T | 5126103 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 01/06/2016 | with completed mechanical and electric at first floor only all light steel stud framing okay | NATHAN | NATHAN | | BFR | P | 5110945 |
PROCOM ELECTRICAL SERVICES, INC. | E= | C | 05/11/2016 | FIRE ALARM INSPECTION: For fire alarm | SHELBY | SHELBY | | E= | C | 5197298 |
PROCOM ELECTRICAL SERVICES, INC. | E= | C | 05/06/2016 | | TOMC | TOMC | | E= | C | 5193386 |
PROCOM ELECTRICAL SERVICES, INC. | EP | C | 05/06/2016 | panels MDP1 , MDP2 , L1B5 , L1B7 , L1B6 (1&2) , L2B1&2 , H2B & transformer | TOMC | TOMC | | EP | C | 5193384 |
PROCOM ELECTRICAL SERVICES, INC. | E= | P | 05/04/2016 | NEED EP AND TRANSFORMER INSP----TI INSP-----LOOKED AT ROOF AND COOLING-----NEED TO LABEL ALL ROOF EQUIPMENT-----NEED TO MOUNT THE GROUNDING LUG IN DISCONNECTS WITH BOLT AND REMOVE THE PAINT-------NEED 25 AMP BREAKER ON CRACK UNIT # 3-----NEED 20 AMP BREAKERS FOR CU-3 AND 4----NEED TO PANEL SCH ---------NEED TO HAVE THE GEAR OPEN ON NEXT INSP THANKS------- | BRIAN | BRIAN | | E= | P | 5192054 |
PROCOM ELECTRICAL SERVICES, INC. | ER | C | 03/28/2016 | FIRE ALARM INSPECTION: FIRE ALARM complete | TOMC | TOMC | | ER | C | 5163660 |
PROCOM ELECTRICAL SERVICES, INC. | ER | P | 03/17/2016 | | TOMC | TOMC | | ER | P | 5157073 |
PROCOM ELECTRICAL SERVICES, INC. | ER | P | 02/03/2016 | 2 - floor boxes on main floor RM 120 , walls in conference room 2nd floor | TOMC | TOMC | | ER | P | 5127281 |
PROCOM ELECTRICAL SERVICES, INC. | ER | P | 01/05/2016 | Rms # 101 - 103 , 105 - 108 perimeter walls east and north , new interior walls east side of building north end | TOMC | TOMC | | ER | P | 5109651 |
AIRTECH MECHANICAL, INC. | H= | C | 05/16/2016 | MECHANICAL FINAL OK | NANCY | NANCY | | H= | C | 5199668 |
AIRTECH MECHANICAL, INC. | H= | P | 04/22/2016 | TEST AND BALANCE REPORT RECEIVED. STILL NEED MINI-SPLIT CONDENSATE DRAIN INSTALLED. | NANCY | NANCY | | H= | P | 5182220 |
AIRTECH MECHANICAL, INC. | H= | P | 03/31/2016 | PARTIAL PENDING TAB REPORT AND PICTURE OF CONDENSATE DRAIN TO MINI SPLIT - REST OK | JERRYF | JERRYF | | H= | P | 5166482 |
AIRTECH MECHANICAL, INC. | HRP | C | 03/31/2016 | PRESSURE TEST OK ON ALL LINES | JERRYF | JERRYF | | HRP | C | 5166475 |
AIRTECH MECHANICAL, INC. | HD | P | 02/22/2016 | ABOVE CEILING OK IN THE FOLLOWING AREAS - 1ST FLOOR ROOMS 106 - 2 RELOCATED VAV'S IN MAIN FLOOR CORRIDOR - 107 LAB DUCT OK STILL NEED CRAC UNIT / HRP AND DRAINS - 2ND FLOOR - ABOVE CEILING OK IN THE FOLLOWING ROOMS - 201 - 202 - 203 - 216 - STILL NEED MINI SPLITS COMPLETED ALL CRAC UNITS INSTALLED / HRP AND DRAINS AND ROOF INSPECTION | JERRYF | JERRYF | | HD | P | 5139351 |
AIRTECH MECHANICAL, INC. | HD | L | 02/19/2016 | CANCELED AT CALL AHEAD | JERRYF | JERRYF | | HD | L | 5138329 |