CQL-2000 CONSTRUCTORS, LLC. | B= | C | 05/27/2016 | All other required Final inspections are complete. (This is a computer generated result) | BOBF | BOBF | | B= | C | 5209640 |
CQL-2000 CONSTRUCTORS, LLC. | B= | P | 05/26/2016 | pending mech building okay. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), WESTECH MECHANICAL INC Mechanical Final Inspection is not Completed yet. | BOBF | BOBF | | B= | P | 5209045 |
CQL-2000 CONSTRUCTORS, LLC. | B= | P | 04/07/2016 | Temp CO: pending finals ( Expires: 5/7/2016 12:00:00 AM) | BPHILLIPS | BPHILLIPS | | B= | P | 5171803 |
CQL-2000 CONSTRUCTORS, LLC. | B= | P | 04/07/2016 | per Bob F no life safety items -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), COMMERCIAL SPECIALISTS OF S. C Electrical Final Inspection is not Completed yet, IT'S ELECTRIC LLC Electrical Final Inspection is not Completed yet, WESTECH MECHANICAL INC Mechanical Final Inspection is not Completed yet, WILKINSON PLUMBING & HEATING, Plumbing Final Inspection is not Completed yet. | BERTW | BERTW | | B= | P | 5171734 |
CQL-2000 CONSTRUCTORS, LLC. | BSP | P | 04/06/2016 | revise one line | SHELBY | SHELBY | | BSP | P | 5171697 |
CQL-2000 CONSTRUCTORS, LLC. | BSP | P | 04/06/2016 | PLAN SPLICE: (No Fee) by: SHELLEY for Construction: Removed rated med gas closet - portable cylinders to be used. | SHELLEY | SHELLEY | | BSP | P | 5171645 |
WESTECH MECHANICAL INC | BSP | T | 04/06/2016 | PAID (REC#1322433) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: remove med gas from drawings | DALEH | DALEH | | BSP | T | 5171639 |
WILKINSON PLUMBING & HEATING, | BSP | T | 04/06/2016 | PAID (REC#1322434) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 4-6-16 | TCRIPPEN | TCRIPPEN | | BSP | T | 5171625 |
CQL-2000 CONSTRUCTORS, LLC. | B= | R | 04/06/2016 | need to have plan splice approved, need to complete Fire final. mech final, elec final and plumb final. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), COMMERCIAL SPECIALISTS OF S. C Electrical Final Inspection is not Completed yet, IT'S ELECTRIC LLC Electrical Final Inspection is not Completed yet, WESTECH MECHANICAL INC Mechanical Final Inspection is not Completed yet, WILKINSON PLUMBING & HEATING, Plumbing Final Inspection is not Completed yet. | BOBF | BOBF | | B= | R | 5170962 |
CQL-2000 CONSTRUCTORS, LLC. | B= | R | 04/04/2016 | need plan splice to delete med gas room approved, complete mech, elec and fire finals / grab bar in restroom to extend to 54" from back wall. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), COMMERCIAL SPECIALISTS OF S. C Electrical Final Inspection is not Completed yet, IT'S ELECTRIC LLC Electrical Final Inspection is not Completed yet, WESTECH MECHANICAL INC Mechanical Final Inspection is not Completed yet. | BOBF | BOBF | | B= | R | 5168801 |
CQL-2000 CONSTRUCTORS, LLC. | BSP | P | 04/01/2016 | Met with Barry (super) and talked about med gas room requirements, He indicated that med gas room has been deleted and office will be using portable tanks, I told him plans would have to be revised and submitted to PPRBD and fire dept before final inspections | BOBF | BOBF | | BSP | P | 5167936 |
CQL-2000 CONSTRUCTORS, LLC. | BFR | P | 02/22/2016 | pending other required inspections, light metal framing for walls okay / reviewed accessible requirements for break room and rest room with superintendent | BOBF | BOBF | | BFR | P | 5139140 |
IT'S ELECTRIC | E= | C | 05/26/2016 | Plans revised | JOSEPH | JOSEPH | | E= | C | 5208752 |
COMMERCIAL SPECIALISTS OF S. C | E= | C | 04/07/2016 | FIRE ALARM INSPECTION: | BRET | BRET | | E= | C | 5171800 |
IT'S ELECTRIC | E= | P | 04/04/2016 | REVISE PLANS TOE LINE TO SHOW REMOVAL OF LIGHT / EX FAN IN MED GAS CLOSET AND ONE LINE SHOW 200 AMP 4/W FROM 400 AMP 4/W SUB PANEL | CRAIG | CRAIG | | E= | P | 5168605 |
IT'S ELECTRIC | E= | P | 04/01/2016 | revise plans to show removal of light and ex-fan in med gas closet | CRAIG | CRAIG | | E= | P | 5167885 |
IT'S ELECTRIC | EP | C | 03/31/2016 | 200 amp 4/w to two panels ok | CRAIG | CRAIG | | EP | C | 5166702 |
IT'S ELECTRIC | E= | P | 03/31/2016 | all outlets within 6' of sinks need to be gfi protected and readily accessible ------------ in sterilization room gfi outlet wired wrong left of sink ------------- nc cable needs to be in boxes in front of dental chairs ------------ | CRAIG | CRAIG | | E= | P | 5166699 |
IT'S ELECTRIC | ER | P | 03/30/2016 | ceiling ok | CRAIG | CRAIG | | ER | P | 5165649 |
COMMERCIAL SPECIALISTS OF S. C | ER | C | 03/22/2016 | FIRE ALARM INSPECTION: | BRET | BRET | | ER | C | 5166385 |
IT'S ELECTRIC | ER | P | 02/29/2016 | walls complete, 2' from panel to electric room ok | BRET | BRET | | ER | P | 5144359 |
IT'S ELECTRIC | ER | P | 02/18/2016 | walls ok except reception desk. | BRET | BRET | | ER | P | 5136753 |
WESTECH MECHANICAL INC | H= | C | 05/27/2016 | MECHANICAL FINAL OK. TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 5209639 |
WESTECH MECHANICAL INC | H= | P | 05/26/2016 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5209053 |
WESTECH MECHANICAL INC | H= | P | 04/06/2016 | AS NOTED AT ROUGH INSPECTION ISOLATE ALL PVC FROM RETURN AIR PLENUM, SEE IMC 602.2.1. ISOLATE DRYER VENT FROM RETURN AIR PLENUM, SEE IMC 502.9.1. STILL NEED TO SEAL JOINT ON TRUNK LINE OF PO-01. PROPERLY TERMINATE DRYER VENT ON ROOF WITH A DRYER VENT CAP. NO SCREEN IS ALLOWED IN DRYER VENT. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5171249 |
WESTECH MECHANICAL INC | HD | L | 04/05/2016 | LOCKED AT 5:00 PM. | NANCY | NANCY | | HD | L | 5170656 |
WESTECH MECHANICAL INC | HD | P | 03/30/2016 | WALL IS ALREADY ROCKED WHERE DRYER VENT IS SUPPOSED TO BE INSTALLED. NO DRYER VENT YET. SEE NOTE ON M2..1 REGARDING POSITIVE PRESSURE VENT IN THE RETURN AIR PLENUM. SEE IMC 502.9.1 (COMPRESSED GASES, MEDICAL GAS SYSTEMS). NO MED GAS ROOM EXHAUST INSTALLED YET. NO BATH EXHAUST YET. ISOLATE ALL PVC FROM RETURN AIR PLENUM. SEAL PD-01 TRUNK LINE AT S AND DRIVE JOINTS. PROPERLY SUPPORT 10 INCH ROUND FLEX IN OP-3. OK TO CLOSE UP WRAP. | NANCY | NANCY | | HD | P | 5166327 |
WILKINSON PLUMBING & HEATING, | P= | C | 05/26/2016 | CORRECTIONS MADE , PLAN SPLICE SHOWS DELETION OF ALL MED GAS LINES AND EQUIPMENT | GABE | GABE | | P= | C | 5208995 |
WILKINSON PLUMBING & HEATING, | P= | P | 04/04/2016 | ALL TO PLAN , ALL HAND WASH AND CLINICAL SINKS TEMPERED , PENDING PLAN REVISION | GABE | GABE | | P= | P | 5168750 |
WILKINSON PLUMBING & HEATING, | PTO | C | 04/01/2016 | NOTE : ALL VAC LINES IN PER PLAN | GABE | GABE | | PTO | C | 5167584 |
WILKINSON PLUMBING & HEATING, | PTO | P | 02/18/2016 | DWV AND WATER ON TEST AND TO PLAN , NEED TO RED LINE PLANS TO SHOW DESIGN CHANGE , MED GAS PIPING NOT IN | GABE | GABE | | PTO | P | 5137334 |