GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 05/20/2016 | engineering received for welding and for footings | DANE | DANE | | B= | C | 5204176 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 05/11/2016 | need to complete fire final / need stamped letter for footing reinforcement and stamped letter for welding inspection / engineer letter received for micropiles / OK for final when items above are completed -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2). | DANE | DANE | | B= | P | 5197102 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 03/23/2016 | remainder of light gauge steel framing OK pending other roughs / need 3rd party inspection letters for all welding and bolting and for new footings | DANE | DANE | | BFR | P | 5161075 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 03/07/2016 | fur in walls at exterior walls and ridged insulation at same exterior walls OK at southwest corner of job in rooms 105 and 106 OK pending other rough inspections | DANE | DANE | | BFR | P | 5148923 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 05/04/2016 | | BRET | BRET | | E= | C | 5191710 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 05/04/2016 | FIRE ALARM INSPECTION: | BRET | BRET | | E= | C | 5191700 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | C | 04/29/2016 | print room ceiling | BRET | BRET | | ER | C | 5187985 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 04/01/2016 | FIRE ALARM INSPECTION: wall conduit only, no cable to new device location will be installed at time ceiling inspection, | BRET | BRET | | ER | P | 5167738 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 03/22/2016 | walls marked on plans | BRET | BRET | | ER | P | 5160426 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 03/07/2016 | walls see plans. electrical on pre-cast ok for spray. | BRET | BRET | | ER | P | 5149447 |
HVAC SOLUTIONS, INC. | H= | C | 05/10/2016 | MECHANICAL FINAL OK. TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 5195320 |
HARMON - BONDED PLUMBING & HEATING, INC. | H= | C | 05/03/2016 | MECHANICAL PIPING FINAL OK. | NANCY | NANCY | | H= | C | 5190928 |
HARMON - BONDED PLUMBING & HEATING, INC. | HWP | P | 04/29/2016 | PIPING ALREADY UNDER WORKING PRESSURE. NO VISIBLE LEAKS. OK TO INSULATE AND LABEL. COMPLETE CONDENSATE DRAIN. | NANCY | NANCY | | HWP | P | 5188347 |
HVAC SOLUTIONS, INC. | HRP | C | 04/29/2016 | TWO 375 LB TESTS OK. | NANCY | NANCY | | HRP | C | 5188342 |
HVAC SOLUTIONS, INC. | HD | C | 04/29/2016 | FOR FINAL PROVIDE TEST AND BALANCE REPORT. ABOVE CEILING ALL OK. MEZZANINE ALL OK. | NANCY | NANCY | | HD | C | 5188340 |
HVAC SOLUTIONS, INC. | HD | P | 04/19/2016 | PRINT ROOM: SUPPLY TRUNK LINES AND LATERALS ABOVE CEILING OK. OK TO WRAP LATERALS. NO FLEX OF DIFFUSERS YET. | NANCY | NANCY | | HD | P | 5179852 |
HARMON - BONDED PLUMBING & HEATING, INC. | P= | C | 05/03/2016 | NOTE : DRAINAGE INSTALLED , SECURED AND INSULATED , ALL TO PLAN | GABE | GABE | | P= | C | 5190734 |
HARMON - BONDED PLUMBING & HEATING, INC. | PTO | C | 04/29/2016 | WATER CONNECTIONS TO DEIONIZED AND RO SYSTEM , BACK FLOW INSTALLED , OK TO INSULATE , PIPING OK TO PLAN ON TEST , NEED TO CHECK DRAINAGE AT FINAL | GABE | GABE | | PTO | C | 5188090 |