COLARELLI CONSTRUCTION, INC. | B= | C | 04/14/2016 | | JEREMYA | JEREMYA | | B= | C | 5177081 |
FRONT RANGE ELECTRIC, INC. | BSP | T | 03/29/2016 | PAID (REC#1320747) PLAN SPLICE FEE: $50 by: SHELBY for Electrical: revise one line | SHELBY | SHELBY | | BSP | T | 5165233 |
COLARELLI CONSTRUCTION, INC. | BSP | T | 02/08/2016 | PAID (REC#1311995) PLAN SPLICE FEE: $50 by: SHELBY for Electrical: Remove room at top of production area from scope and move loads to Production sorage room (121). | SHELBY | SHELBY | | BSP | T | 5130004 |
FRONT RANGE ELECTRIC, INC. | E= | C | 04/07/2016 | | JOSEPH | JOSEPH | | E= | C | 5171831 |
FRONT RANGE ELECTRIC, INC. | E= | P | 04/06/2016 | Insta-hot requires disconnecting means.----------Cord ends need to be listed for horsepower use. If you can submit manufactures information that shows cord caps are listed for horsepower then that will work.------------Disconnect for exhaust fan is more that 50 feet from unit | JOSEPH | JOSEPH | | E= | P | 5170915 |
FRONT RANGE ELECTRIC, INC. | E= | R | 04/01/2016 | Still need to hot check cutting room | JOSEPH | JOSEPH | | E= | R | 5167535 |
FRONT RANGE ELECTRIC, INC. | EP | C | 04/01/2016 | Inspected all sub panels and transformer. | JOSEPH | JOSEPH | | EP | C | 5167533 |
FRONT RANGE ELECTRIC, INC. | ES | C | 04/01/2016 | Commercial Service: 400 amp commercial service------------- meter is in and sealed no action is required | JOSEPH | JOSEPH | | ES | C | 5167531 |
FRONT RANGE ELECTRIC, INC. | E= | R | 03/30/2016 | See service comments--------- Still need to inspect cut room | JOSEPH | JOSEPH | | E= | R | 5165686 |
FRONT RANGE ELECTRIC, INC. | ES | R | 03/30/2016 | Can't run equipment grounding conductors with service conductors to service disconnect.-----Cant' mix service and feeder conductors in same raceway.----Labels Fault current for service, panels and where they are fed from, phase color designation.-------- Loose conductors many locations.--------Main breakers in sub installed upside down.---In 225 kva trans, Neutral/ground connection missing. and scrape paint on bond connections, also equipment grounding conductor is double lugged. ----------Bond service raceways correctly.----Service neutrals need to bond to metal junction box upstream of service disconnect.----Bonding bushings loose.---------Group neutrals in sub panels.---------Did not inspect cutting room because no power for hot check | JOSEPH | JOSEPH | | ES | R | 5165684 |
FRONT RANGE ELECTRIC, INC. | ES | R | 03/29/2016 | need approved drawings on site | CRAIGS | CRAIGS | | ES | R | 5164517 |
FRONT RANGE ELECTRIC, INC. | ES | P | 03/25/2016 | Commercial Service: pre release only --- contractor assures me they have a letter from manufacture for tapping the main buss and will have it scanned in to there permit | CRAIGS | CRAIGS | | ES | P | 5162297 |
FRONT RANGE ELECTRIC, INC. | ES | R | 03/22/2016 | Complete re-inspection required.-------------- The only thing I inspected was the service disconnect.-----------Following is a partial list only---------Plans do not accurately reflect what was installed. Plans show feeders coming off a 400 amp fusible disconnect mounted inside a 1600 amp mdp.--------- Contractor tapped directly off the service bus. This requires a letter from the manufacturer giving their approval. ----- At the new 400 amp fused disconnect, you will need to re-establish the neutral to ground connection because this is a service disconnect. ------The service neutrals are not routed through the disconnect. ------Use appropiate bonding bushings for 480 volt.------------Label service disconnect --------Can't bond to painted surfaces.---------Amend plans ------Phase color designation-----------label with fault current information and date.---------Conductors of the same circuit need to be routed in the same raceway----------Follow rules for paralleled installations | JOSEPH | JOSEPH | | ES | R | 5160122 |
FRONT RANGE ELECTRIC, INC. | E= | R | 03/22/2016 | Not ready for final | JOSEPH | JOSEPH | | E= | R | 5160102 |
FRONT RANGE ELECTRIC, INC. | ES | P | 03/15/2016 | Residential Overhead: pre release only | RANDY | RANDY | | ES | P | 5154885 |
HVAC SOLUTIONS, INC. | H= | C | 04/13/2016 | MECHANICAL FINAL OK. LETTER FROM MECHANICAL CONTRACTOR VERIFYING INTERLOCKS RECEIVED AND SCANNED. | NANCY | NANCY | | H= | C | 5175741 |
HVAC SOLUTIONS, INC. | H= | P | 04/12/2016 | TEST AND BALANCE REPORT RECEIVED AND SCANNED. LETTER FROM ENGINEER STATING HEATERS INSTALLED ARE APPROVED FOR A WET ENVIRONMENT RECEIVED AND SCANNED. STILL NEED VERIFICATION OF INTERLOCKS. RANCH FOODS IS ALREADY IN THIS AREA AND WORKING, AREA HAS TO BE SHUT DOWN AND COMPLETELY CLEANED WHEN OUTSIDE PERSONNEL ENTER AREA. WILL ACCEPT LETTER FROM CONTRACTOR STATING INTERLOCKS ARE FUNCTIONING AS PER PRINTS SO AREA WILL NOT NEED TO BE SHUT DOWN AND CLEANED FOR ANOTHER INSPECTION. | NANCY | NANCY | | H= | P | 5174737 |
HVAC SOLUTIONS, INC. | H= | P | 02/25/2016 | COMPLETE ALL WIRING AND CALL FOR INSPECTION TO VERIFY INTERLOCKS. MODEL NUMBER OF ELECTRIC HEATERS INSTALLED DOES NOT MATCH WHAT IS SHOWN ON PRINTS, ARE THESE HEATERS DESIGNED TO BE INSTALLED IN THIS ENVIRONMENT? | NANCY | NANCY | | H= | P | 5142351 |
HVAC SOLUTIONS, INC. | HD | P | 02/19/2016 | TRANSFER AIR OK FOR INSULATION | JERRYF | JERRYF | | HD | P | 5138367 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 02/23/2016 | meat cutting room | TED | TED | | P= | C | 5139873 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 02/17/2016 | hand and meat sink dvw ok | TED | TED | | PB | P | 5135717 |
OLSON PLUMBING & HEATING COMPANY | PB | C | 02/03/2016 | trench drains ok, note, floor sink at northwest side deleted. | DICK | DICK | | PB | C | 5127371 |