MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | B= | C | 12/07/2017 | All other required Final inspections are complete. (This is a computer generated result) | NATHAN | NATHAN | | B= | C | 5707012 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | B= | P | 04/13/2017 | exterior core and shell. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977), External Agency Inspection HD= by HEALTHDEPT is not Completed yet. | NATHAN | NATHAN | | B= | P | 5474768 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BFR | C | 12/12/2016 | engineer letter for structural observation on file / letter of deletion for perimeter drain picked up | NATHAN | NATHAN | | BFR | C | 5365236 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BIN | C | 12/12/2016 | walls at J line 3-7 and M line 4-6 okay | NATHAN | NATHAN | | BIN | C | 5365235 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BFR | P | 12/01/2016 | Framing for riser room OK / Electrical room not framed, contractor said may be removed from plans / Framing for interior wall on J line OK / Framing for interior wall at Entry lobby OK / Need all MEP's complete / Need Eng for foundation drain / Need Eng for structural bolting and welding | NICK | NICK | | BFR | P | 5357437 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BSP | T | 10/20/2016 | PAID (REC#1374311) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: Revised gas layout | DALEH | DALEH | | BSP | T | 5324046 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BBB | C | 05/20/2016 | top of wall BBB okay | NATHAN | NATHAN | | BBB | C | 5204416 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BBB | P | 05/16/2016 | 8' BBB at N line 3-6 and top of wall M line 1-7 okay | NATHAN | NATHAN | | BBB | P | 5200085 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BBB | P | 05/06/2016 | top of wall BBB at grid line 3&7 J_M okay. | NATHAN | NATHAN | | BBB | P | 5193677 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BBB | P | 05/03/2016 | BBB at 8' and verticals J line NORTH 1-9 OKAY / top of wall and vertical at all 1-9 line A-J okay. | NATHAN | NATHAN | | BBB | P | 5190443 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BBB | P | 04/20/2016 | see sheet S-5 for details on windows and doors not done south, east, and west top off wall BBB okay except for previous mentioned and marked areas. | NATHAN | NATHAN | | BBB | P | 5180677 |
JUST JENN INC | BSP | T | 04/05/2016 | PAID (REC#1344386) PLAN SPLICE FEE: $50 by: SHELBY for Electrical: Revise service/one line | SHELBY | SHELBY | | BSP | T | 5170666 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BSP | P | 03/25/2016 | ALL COLLAR TIES OKAY, letter for bar couplers picked up | NATHAN | NATHAN | | BSP | P | 5162777 |
JUST JENN INC | BSP | T | 03/21/2016 | PAID (REC#1344386) PLAN SPLICE FEE: $50 by: SHELBY for Electrical | SHELBY | SHELBY | | BSP | T | 5159453 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BFI | C | 02/25/2016 | All foundation rigid insulation OK | NICK | NICK | | BFI | C | 5141982 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BFI | P | 02/24/2016 | Rigid insulation for warehouse portion OK, need to see insulation for office area | NICK | NICK | | BFI | P | 5140878 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BFN | C | 02/24/2016 | Eng letter of observation on file / Compaction test on file | NICK | NICK | | BFN | C | 5140876 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BFT | C | 02/24/2016 | Eng letter of observation on file / Open hole on file / Drain required | NICK | NICK | | BFT | C | 5140865 |
JUST JENN INC | E= | C | 02/14/2017 | 4-30 AMP CU UNITS ON ROOF--OK | BRIAN | BRIAN | | E= | C | 5415075 |
JUST JENN INC | E= | P | 12/28/2016 | STILL NEED AC UNITS ON THE ROOF----TO ICY TO GET ON ROOF | BRIAN | BRIAN | | E= | P | 5378439 |
JUST JENN INC | ER | P | 10/06/2016 | WALLS COMPLETE---- | BRIAN | BRIAN | | ER | P | 5312639 |
JUST JENN INC | EP | C | 09/22/2016 | | CRAIGS | CRAIGS | | EP | C | 5299824 |
JUST JENN INC | EP | R | 09/20/2016 | THE LUGS ARE LOOSE TO THE BUSSING --ALL PANELS--- | BRIAN | BRIAN | | EP | R | 5298277 |
JUST JENN INC | EP | R | 09/15/2016 | need to check sub panels | TIMA | TIMA | | EP | R | 5294009 |
JUST JENN INC | ES | C | 09/15/2016 | Commercial Service: 2-600 amp 4/w ct metered services ok to energize---mike domingez approved 30" meter clearance--- | TIMA | TIMA | | ES | C | 5294007 |
JUST JENN INC | ES | R | 09/14/2016 | plans need spliced to show the 1200 amp bussed gutter was not installed --- plans have to show what was installed ,(I.E conductor size , type ,)---- ufer rebar is too small has to be a #4 , need a detail on the prints showing the anchor bolts are tied to the rebar and is continuous to the footer or dig down to the footer and chip until you find re bar --- main bonding jumper to small --- complete re inspection is required | CRAIGS | CRAIGS | | ES | R | 5292772 |
JUST JENN INC | EUG | P | 07/26/2016 | NORTH SIDE POLE LIGHTS--2------------OK | BRIAN | BRIAN | | EUG | P | 5254478 |
JUST JENN INC | ESL | P | 03/03/2016 | slab work in building is complete | GARYL | GARYL | | ESL | P | 5146872 |
JUST JENN INC | ESL | P | 02/26/2016 | PVC IN WAREHOUSE -ONLY-----OK | BRIAN | BRIAN | | ESL | P | 5143046 |
JUST JENN INC | ESL | P | 02/23/2016 | 6 - 2.5" pvc from east wall running west | TOMC | TOMC | | ESL | P | 5140003 |
AIRTECH MECHANICAL, INC. | H= | P | 02/28/2017 | NEED THE FOLLOWING TO COMPLETE FINAL - TAB REPORT - REVISE PLAN TO DUCTED RETURN AND INSTALL DUCT OR PROTECT ALL PVC IN RA PLENUM - TAG ALL CONDENSERS CORRECTLY - RELOCATE ALL OSA DUCT INLETS TO MAINTAIN PROPER CLEARANCE TO FURNACE EXHAUST ATTACH PICTURES OF OSA DUCT TO NEXT INSPECTION REQUEST - REST OK | JERRYF | JERRYF | | H= | P | 5426638 |
AIRTECH MECHANICAL, INC. | H= | C | 02/28/2017 | CORE AND SHELL IS COMPLETE | JERRYF | JERRYF | | H= | C | 5426631 |
DRUMMOND PLUMBING LLC | H= | C | 01/17/2017 | ALL / REGS / LABELS / 2# LETTER AND LIMITERS COMPLETE | JERRYF | JERRYF | | H= | C | 5389750 |
AIRTECH MECHANICAL, INC. | H= | P | 01/12/2017 | SEE NOTES | JERRYF | JERRYF | | H= | P | 5387711 |
AIRTECH MECHANICAL, INC. | H= | P | 01/12/2017 | PARTIAL PENDING THE FOLLOWING - TAB REPORT - ROOF INSPECTION | JERRYF | JERRYF | | H= | P | 5387668 |
AIRTECH MECHANICAL, INC. | HV | P | 12/30/2016 | PARTIAL PENDING ROOF INSPECTION AND SOME SUPPORT STRAPS AT UNIT HEATER VENTS | JERRYF | JERRYF | | HV | P | 5379797 |
AIRTECH MECHANICAL, INC. | H= | R | 12/30/2016 | NOT READY TO MANY ITEMS TO LIST - STOPPED INSPECTION - RE INSPECT ALL - WAIVED TRIP FEE | JERRYF | JERRYF | | H= | R | 5379796 |
DRUMMOND PLUMBING LLC | HC | C | 10/21/2016 | RELEASE METER | JERRYF | JERRYF | | HC | C | 5325012 |
DRUMMOND PLUMBING LLC | HI | C | 10/21/2016 | PRESSURE TEST OK ON 2 LINES - PIPING PER PLAN - AT FINAL CONFIRM ALL REGS. AND LABELS | JERRYF | JERRYF | | HI | C | 5325006 |
DRUMMOND PLUMBING LLC | P= | C | 11/17/2016 | | JOEL | JOEL | | P= | C | 5347054 |
DRUMMOND PLUMBING LLC | PTO | C | 11/17/2016 | | JOEL | JOEL | | PTO | C | 5347053 |
DRUMMOND PLUMBING LLC | PB | C | 03/04/2016 | SS trunk line ok, no water sevice. | DICK | DICK | | PB | C | 5147827 |