CMG CORP | B= | C | 07/13/2016 | | JOHN | JOHN | | B= | C | 5244313 |
CMG CORP | B= | P | 07/13/2016 | Need to install occupant load sign / Need to install accessible signs for rest rooms on latch side of door / Need fire final complete -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2). | NICK | NICK | | B= | P | 5243944 |
CMG CORP | BSP | R | 05/31/2016 | Could not find anyone on site, all doors locked / Do not know what inspection was for? | NICK | NICK | | BSP | R | 5211208 |
CMG CORP | BSP | P | 05/24/2016 | Added EM and X type light fixtures and existing panel schedule B | BERTHA | BERTHA | | BSP | P | 5207417 |
LANDMARK PLUMBING AND HEATING, INC. | BSP | P | 05/24/2016 | PLAN SPLICE: (No Fee) by: DALEH for Mechanical: approved a new hood and mua unit | DALEH | DALEH | | BSP | P | 5207396 |
LANDMARK PLUMBING AND HEATING, INC. | BSP | P | 05/24/2016 | PLAN SPLICE: (No Fee) by: TCRIPPEN for Mechanical: mechanical splice 5-24-16 | TCRIPPEN | TCRIPPEN | | BSP | P | 5207335 |
LANDMARK PLUMBING AND HEATING, INC. | BSP | T | 05/24/2016 | PAID (REC#1331630): PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 5-14-16 | TCRIPPEN | TCRIPPEN | | BSP | T | 5207321 |
CMG CORP | BSP | P | 04/04/2016 | Double layer of 5/8 rock for U 408 wall OK / Reviewed accessibility with Chris / Hood is going on CMU wall | NICK | NICK | | BSP | P | 5168870 |
LUMENOCITY ELECTRICAL DESIGN, LLC | E= | C | 07/05/2016 | | BRIAN | BRIAN | | E= | C | 5236907 |
LUMENOCITY ELECTRICAL DESIGN, LLC | EP | C | 07/01/2016 | | BRIAN | BRIAN | | EP | C | 5236056 |
LUMENOCITY ELECTRICAL DESIGN, LLC | E= | P | 07/01/2016 | still need roof gfci installed----still need 15 amp breakers on the MUA and HOOD EF--------STILL NEED THE SCREWS INSTALLED ON THE DISCONNECT DOORS ( ON THE BUILDING DISCONNECTS ) ------- | BRIAN | BRIAN | | E= | P | 5236055 |
LUMENOCITY ELECTRICAL DESIGN, LLC | E= | P | 06/27/2016 | DINING --OK------------------NEED GFCI PROTECTION IN KITCHEN-- ( NOTE CAN NOT HAVE DEVICE BEHIND ANY EQUIPMENT )------NEED TO FINISH AC UNIT----NEED 15 AMP OCP ON MUA AND HOOD------NEED 20 AMP OCP ON SMALL AC--NEED SERVICE OUTLETS FINISHED-----NEED HANDEL TIES IN PANEL ON ALL MCC'S-------NEED TO FINISH LABELING PANEL -----NEED TO LABEL WHERE IT FEEDS FROM AND INSTALL SCREWS IN THE DISCONNECT COVERS------ | BRIAN | BRIAN | | E= | P | 5231613 |
LUMENOCITY ELECTRICAL DESIGN, LLC | ER | C | 06/27/2016 | CORRECTIONS MADE---GRID CEILING --OK | BRIAN | BRIAN | | ER | C | 5231592 |
LUMENOCITY ELECTRICAL DESIGN, LLC | ER | P | 06/17/2016 | NEED TO CORRECT THE KITCHEN RECPT WITH THE WRONG BOXES AND CONNECTORS----WALL LIGHTS OK---NEED TO GROUND THE 2 LARGE PENDANT LIGHTS -----NEED GRID CEILING INSP---- | BRIAN | BRIAN | | ER | P | 5225481 |
LUMENOCITY ELECTRICAL DESIGN, LLC | ER | R | 06/01/2016 | NEED TO USE PROPER CONNECTORS THROUGH OUT THE WHOLE ELECT. SYSTEM----NEED COMPLETELY REMOVE ALL LIGHTS AND OUTLETS FOR ROUGH INSPECTION-----MET WITH CONTRACTOR------ | BRIAN | BRIAN | | ER | R | 5212071 |
LUMENOCITY ELECTRICAL DESIGN, LLC | ER | R | 05/26/2016 | need to remove all devices and lights -----MUST MEET ME ON SITE----- | BRIAN | BRIAN | | ER | R | 5209704 |
LUMENOCITY ELECTRICAL DESIGN, LLC | ER | R | 05/20/2016 | NEED ELECTRICIAN ON SITE-----WALLS COVERED UP-----DEVICES INSTALLED------WORK ON PRINT DOES NOT MATCH WHATS DONE----- | BRIAN | BRIAN | | ER | R | 5204908 |
LUMENOCITY ELECTRICAL DESIGN, LLC | ER | L | 05/16/2016 | DOOR LOCKED | BRIAN | BRIAN | | ER | L | 5200062 |
CMG CORP | FP= | C | 06/02/2016 | | KEITH | KEITH | BDA | FP= | C | 5213680 |
LANDMARK PLUMBING AND HEATING, INC. | H= | C | 07/13/2016 | GAS/WATER HEATER VENT FINAL OK. | NANCY | NANCY | | H= | C | 5243645 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | C | 07/13/2016 | MECHANICAL FINAL OK. INTERLOCKS OK. ALL CORRECTIONS MADE. | NANCY | NANCY | | H= | C | 5243644 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | P | 07/13/2016 | TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | P | 5243580 |
LANDMARK PLUMBING AND HEATING, INC. | H= | P | 07/12/2016 | INSTALL HIGH TRANSFER GRILL ON FURNACE MECHANICAL ROOM DOOR FOR GAS REGULATOR VENTILATION. REST OF GAS/WATER HEATER VENT FINAL OK. | NANCY | NANCY | | H= | P | 5242592 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | R | 07/06/2016 | NOT READY. CALLED GAS CONTRACTOR WITH GAS AND WATER HEATER ISSUES. NO TEMP SENSOR IN HOOD AND INTERLOCKS TO BE CORRECT BY NEXT INSPECTION.. 2- GREASE FILTERS NOT HELD IN PLACE WHEN FAN IN OPERATION. 3- NEED TO REMOVE ALL COMBUSTIBLES OFF THE TOP OF THE HOOD. 4- WAS NOT ABLE TO LEAN THE GREASE FAN BACK TO FOR INSPECTION DUE TO HINGE PROBLEMS. 5- CANNOT INSTALL UNI-STRUT UP AGAINST GREASE WRAP FOR GREASE DUCT SUPPORT, THIS SHOULD HAVE BEEN INCORPORATED IN WITH THE WRAP. 6- CANNOT PENETRATE TYPE 1 HOOD WITH SCREWS TO SECURE ELECTRICAL WORK. 7- NEED TO SUPPORT FURNACE VENTING IN MECHANICAL CLOSET AND NEED ENGINEER TO ADDRESS HOW CLOSET WILL BE VENTILATED AND THE SIZING. 8- FURNACE IN KITCHEN NEEDS PRIMARY AND AUXILIARY DRAIN COMPLETED, 9-- NEED BALANCE REPORT. 10- MAY HAVE MORE ISSUES AFTER NEXT INSPECTION. | JON | JON | | H= | R | 5238302 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 06/08/2016 | ENTRY FOR REVIEW OF PICTURES OF GREASE WRAP ABOVE ROOF ONLY STILL NEED TO CALL INSPECTION FOR GREASE DUCT BELOW ROOF LIN E. | JON | JON | | HD | P | 5218150 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | L | 06/06/2016 | CANCELED AT CALL AHEAD BY CONTRACTOR | JERRYF | JERRYF | | HD | L | 5215718 |
RIAL HEATING AND AIR CONDITIONING, INC. | HV | L | 06/06/2016 | CANCELED AT CALL AHEAD BY CONTRACTOR | JERRYF | JERRYF | | HV | L | 5215717 |
LANDMARK PLUMBING AND HEATING, INC. | HC | C | 05/25/2016 | OK TO SET 2 LB METER. | NANCY | NANCY | | HC | C | 5208180 |
LANDMARK PLUMBING AND HEATING, INC. | HI | P | 05/16/2016 | NEED REVISED/APPROVED PRINTS SHOWING NEW GAS LAYOUT TO GET METER RELEASE. BY FINAL NEED LETTER FROM CSPU APPROVING MEDIUM PRESSURE FOR THIS ADDRESS. 10 LB TEST OK. INSTALL REGULATORS 'MEDIUM PRESSURE" LABELS AND CONNECT TO APPLIANCES BY FINAL. | NANCY | NANCY | | HI | P | 5199964 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 05/13/2016 | Ok to wrap grease duct in down through roof curb, will need proper service platforms and rails by final. Rough duct on HVAC ok.. Need water heater and vent inspections for water heater vents called. | JON | JON | | HD | P | 5199584 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 05/11/2016 | INSTALL TWO LAYERS OF GREASE WRAP WITH BANDS A MINIMUM OF 18 ABOVE ANY COMBUSTIBLES AT THE ROOF DECK, INCLUDING ROOFING MATERIAL.. TOP OF TYPE I FAN IS BELOW TOP OF VERTICAL WALL, WALL IS LESS THAN 10 FEET FROM FAN. EITHER EXTEND CURB OR INSTALL FACTORY EXTENSION. SEAL VENTS ON CURB. | NANCY | NANCY | | HD | P | 5196685 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 05/10/2016 | WALL ON RIGHT SIDE OF HOOD OK. | NANCY | NANCY | | HD | P | 5195432 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 05/09/2016 | GREASE DUCT OK, OK TO WRAP. EQUIPMENT ON ROOF: SEE IMC 306.5.1 (SLOPED ROOFS) REGARDING PLATFORMS AND GUARDS. SEE IMC304.11 (GUARDS). | NANCY | NANCY | | HD | P | 5194460 |
RIAL HEATING AND AIR CONDITIONING, INC. | H16 | C | 05/06/2016 | WHAT TYPE OF FIREPLACE IS BEING INSTALLED? MECHANICAL SHEET SHOWS BOTH A GAS AND ELECTRIC FIREPLACE, GAS SHEET DOES NOT SHOW ANY GAS TO FIREPLACE | NANCY | NANCY | | H16 | C | 5193224 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 05/05/2016 | HOODMART HOOD BEING INSTALLED, PRINTS SHOW ACCUREX HOOD WITH ZERO CLEARANCE ON THE RIGHT HAND SIDE BEING INSTALLED. NEED REVISED/APPROVED PRINTS. HOODMART HOOD HAS NO FACTORY LABEL SHOWING CLEARANCE TO COMBUSTIBLE MATERIALS REQUIREMENTS. IF BUILDING WALL ON RIGHT SIDE OF HOOD WILL NEED A MINIMUM OF 3 INCHES FROM WALL TO HOOD. WALL MUST HAVE METAL AND SHEET ROCK INSTALLED ON METAL STUDS. WILL NEED TO SEE WALL BEFORE ROCK IS INSTALLED ON BOTH SIDES. | NANCY | NANCY | | HD | P | 5192702 |
RIAL HEATING AND AIR CONDITIONING, INC. | HRP | C | 05/05/2016 | TWO 300 LB TESTS OK. LINESET IN WALL OK, OK TO COVER. | NANCY | NANCY | | HRP | C | 5192701 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 04/28/2016 | LIGHT TEST GOOD FROM HOOD CONNECTION TO SECOND 90' NOTE: OK TO WRAP THAT SECTION. | LUKE | LUKE | | HD | P | 5186722 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 06/20/2016 | corrections made. | TAYLOR | TAYLOR | | P= | C | 5226087 |
LANDMARK PLUMBING AND HEATING, INC. | P= | P | 06/01/2016 | install dishwasher and hand sink with mixing valve at bar area, need 1 inch air gaps at T&P drains for water heaters, pull plug and install trap guard in floor drain at kitchen area, rest ok. | TAYLOR | TAYLOR | | P= | P | 5212471 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 04/18/2016 | correction made, check water heaters by final. | TAYLOR | TAYLOR | | PTO | C | 5179307 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 04/14/2016 | undersized cold water pipe above PRV, rest ok. | TAYLOR | TAYLOR | | PTO | P | 5177468 |
LANDMARK PLUMBING AND HEATING, INC. | PB | C | 04/06/2016 | | TAYLOR | TAYLOR | | PB | C | 5171316 |
LANDMARK PLUMBING AND HEATING, INC. | PB | P | 04/01/2016 | install grease interceptor and vents, rest ok, revise plans to show 3 inch S.S. and G.W. by final. | TAYLOR | TAYLOR | | PB | P | 5168179 |