FACILITIES CONTRACTING, INC. | B= | C | 07/08/2016 | all finals complete | DANE | DANE | | B= | C | 5240356 |
FACILITIES CONTRACTING, INC. | B= | P | 06/30/2016 | E= complete. Additional Inspections Required (computer generated): ENVIRONMENTAL HTG & AIR COND Mechanical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 5235125 |
FACILITIES CONTRACTING, INC. | B= | P | 06/03/2016 | OK pending E= | DANE | DANE | | B= | P | 5214260 |
FACILITIES CONTRACTING, INC. | B= | P | 04/29/2016 | still need E= / still need to install all office doors into jams and inspect single action knobs / all other items corrected -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), HIGHER POWER ELECTRIC Electrical Final Inspection is not Completed yet, SPECIAL SYSTEMS DESIGN,LLC Electrical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 5188063 |
FACILITIES CONTRACTING, INC. | B= | P | 04/27/2016 | need all remaining MEP finals / need single action locks at door to corridor from IT room and at door at room 211 / double key lock at main door needs to have an indicator / need door to remain unlocked sign in contrasting color over main door / need to install all office doors and single action knobs at all office doors -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), FRONTIER MECHANICAL SYSTEMS INC Mechanical Final Inspection is not Completed yet, HIGHER POWER ELECTRIC Electrical Final Inspection is not Completed yet, SPECIAL SYSTEMS DESIGN,LLC Electrical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 5185817 |
FACILITIES CONTRACTING, INC. | BFR | P | 04/01/2016 | Interior wall framing OK / Pending other inspections / Training with Dakota Barr | JEREMYA | JEREMYA | | BFR | P | 5167804 |
SPECIAL SYSTEMS DESIGN,LLC | E= | C | 06/03/2016 | FIRE ALARM INSPECTION: | GARYL | GARYL | | E= | C | 5213987 |
HIGHER POWER ELECTRIC | E= | C | 05/17/2016 | | GARYL | GARYL | | E= | C | 5201194 |
HIGHER POWER ELECTRIC | E= | P | 04/29/2016 | Phase one okay | GARYL | GARYL | | E= | P | 5188253 |
SPECIAL SYSTEMS DESIGN,LLC | E= | P | 04/28/2016 | FIRE ALARM INSPECTION: Phase one complete | GARYL | GARYL | | E= | P | 5187100 |
HIGHER POWER ELECTRIC | E= | P | 04/26/2016 | ceilings okay, all areas except: partitions in "IT" room, "entry", north window area, labeling of panels | GARYL | GARYL | | E= | P | 5185118 |
SPECIAL SYSTEMS DESIGN,LLC | ER | C | 04/14/2016 | FIRE ALARM INSPECTION: | GARYL | GARYL | | ER | C | 5177369 |
HIGHER POWER ELECTRIC | ER | P | 04/01/2016 | walls ok | BRET | BRET | | ER | P | 5167968 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 07/01/2016 | MECHANICAL CONTRACTOR NEEDS TO GET ATTACHED TO PERMIT K14572 AND GET REMOVED FROM THIS PERMIT. SEE B16 COMMENTS ON PERMIT K14572 FOR MECHANICAL INSPECTION NOTES. | NANCY | NANCY | | HD | P | 5236671 |
FRONTIER MECHANICAL SYSTEMS INC | H= | C | 04/29/2016 | HOT WATER PIPING FINAL OK. | NANCY | NANCY | | H= | C | 5187505 |
ALL SEASONS HEATING AND AIR CONDITIONING | H= | C | 04/27/2016 | MECHANICAL FINAL OK. TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 5185415 |
FRONTIER MECHANICAL SYSTEMS INC | H= | P | 04/21/2016 | MECHANICAL FINAL OK PENDING CONTRACTOR CHANGING SCOPE OF WORK TO THREE HOT WATER PIPING INSTEAD OF THREE GAS LINES. | NANCY | NANCY | | H= | P | 5182146 |
FRONTIER MECHANICAL SYSTEMS INC | HWP | C | 04/21/2016 | PIPING TO THREE VAV'S OK., ALREADY UNDER WORKING PRESSURE, NO VISIBLE LEAKS. OK TO COMPLETE INSULATION AT FITTINGS. | NANCY | NANCY | | HWP | C | 5182145 |
ALL SEASONS HEATING AND AIR CONDITIONING | H= | P | 04/20/2016 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. INCLUDE OUTSIDE AIR READING, SEE VENTILATION SCHEDULE SHEET M0.1. | NANCY | NANCY | | H= | P | 5180739 |
ALL SEASONS HEATING AND AIR CONDITIONING | HD | P | 04/06/2016 | NEED WHOEVER IS DOING THE PIPING TO THE VAV'S TO ATTACH TO PERMIT. ROUGH TRUNK LINES AND LATERALS OK, OK TO WRAP. NO NEW VAV'S, FLEX OR DIFFUSERS YET.
| NANCY | NANCY | | HD | P | 5171071 |