STAN LEWIS, INC | B= | C | 08/02/2016 | | JEREMYA | JEREMYA | | B= | C | 5259288 |
STAN LEWIS, INC | BFR | P | 07/07/2016 | New wall framing per splice OK / Need to complete all other rough inspections | JEREMYA | JEREMYA | | BFR | P | 5240054 |
STAN LEWIS, INC | BSP | T | 06/30/2016 | PAID (REC#1339129) PLAN SPLICE FEE: $50 by: DANM for Construction: Wall between Suites 170 and 180 is new - typical wall detail included | DANM | DANM | | BSP | T | 5235510 |
STAN LEWIS, INC | BFR | R | 06/17/2016 | call with Stan prior to inspection / no site visit done / flower room #2 not built per plan - approved plans show an existing wall on the south side of the room separating the suite to the south - there is not an existing wall in place / need to revise the plans to show the new walls built in the flower room #2 and schedule a re-inspection after the plan splice is approved | BRIANB | BRIANB | | BFR | R | 5225061 |
STAN LEWIS, INC | BFR | L | 06/16/2016 | left v.m at 213-1610 for call ahead / doors locked to suite and no answer 2:20 / no inspection done | BRIANB | BRIANB | | BFR | L | 5224377 |
STAN LEWIS, INC | BFR | P | 06/13/2016 | 09 IEBC JOB / need to complete other rough inspections / flower room #2 south wall incomplete and not built as per plan - need to revise plans / in-fill framing at front office and flower rm #1 okay per table 720.1 (2) / other interior light gauge wall framing okay per plan / reviewed accessible elements with the site rep | BRIANB | BRIANB | | BFR | P | 5220859 |
STAN LEWIS, INC | BSP | T | 05/19/2016 | PAID (REC#1330434) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 5-19-16 | TCRIPPEN | TCRIPPEN | | BSP | T | 5203788 |
STAN LEWIS, INC | BSP | T | 05/06/2016 | PAID (REC#1328233) PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Electrical Splice 5/6/16 | BERTHA | BERTHA | | BSP | T | 5194125 |
FRONT RANGE ELECTRIC, INC. | E= | C | 07/22/2016 | MINI SPLIT 1 20AMP FUSED,MINI SPLIT 2 20 AMP FUSED,...AC 1,2,3, 50 AMP FUSED, | CRAIGS | CRAIGS | | E= | C | 5251474 |
FRONT RANGE ELECTRIC, INC. | E= | R | 07/21/2016 | cant use barrel handle ties for 208 v loads , please install 2 pole breakers for the ahu --- still need to look at the roof top units | CRAIGS | CRAIGS | | E= | R | 5250326 |
FRONT RANGE ELECTRIC, INC. | E= | L | 07/20/2016 | computer called @11:30 left area @ 12:06 --- knocked repeatedly --- no ladder set up for roof access | CRAIGS | CRAIGS | | E= | L | 5249576 |
FRONT RANGE ELECTRIC, INC. | E= | R | 07/19/2016 | need to label the disconnects with unit # and panel fed from , circuit numbers --- note : the ahu units are on single pole 20's it appears they need to be on two pole 20's please verify --- ahu 1,2and 3 or 20 amp breakers in the panel ---- a/c 1,2and 3 are 50 amp breakers in the panel --- mini 1,2 are 20 amp breakers in the panel | CRAIGS | CRAIGS | | E= | R | 5248409 |
FRONT RANGE ELECTRIC, INC. | E= | P | 07/15/2016 | color code posted on the panels ---- panel schedule needs to say what lights the breakers are feeding ---- get all wiring off the grid --- still need to inspec the roof top units Note --- grow rooms OK | CRAIGS | CRAIGS | | E= | P | 5245935 |
FRONT RANGE ELECTRIC, INC. | E= | R | 07/08/2016 | not ready --- need lights hung --- all old electrical removed or brought to code through out unit -- will need access to the roof to inspect roof top units | CRAIGS | CRAIGS | | E= | R | 5240287 |
FRONT RANGE ELECTRIC, INC. | ER | P | 07/06/2016 | large grow room and small grow room OK --- still need existing electrical removed to brought to code | CRAIGS | CRAIGS | | ER | P | 5238096 |
FRONT RANGE ELECTRIC, INC. | ER | R | 07/05/2016 | not ready -- ground screws in all boxes and ground made up | CRAIGS | CRAIGS | | ER | R | 5236967 |
FRONT RANGE ELECTRIC, INC. | ES | P | 06/13/2016 | Commercial Service: 200 amp 4/w suite 180 panel A--- check for the brass tags on final 200 amp 3/w suite 180 panel B--- check for the brass tags on final | CRAIGS | CRAIGS | | ES | P | 5221319 |
GENE'S HEATING AND AIR LLC | H= | C | 08/01/2016 | CORRECTIONS MADE | LUKE | LUKE | | H= | C | 5258798 |
GENE'S HEATING AND AIR LLC | H= | P | 07/26/2016 | INSTALL MOTORIZED OR MANUAL AND BACK DRAFT DAMPERS IN ALL AIR HANDLER OUTSIDE AIR DUCTS. NOW THAT SMOKE DETECTORS HAVE BEEN INSTALLED ARE THE DETECTORS ON SITE WEATHER PROOF? IF NOT NEED TO PROTECT FROM WEATHER. INSTALL REMOTE INDICATORS FOR SMOKE DETECTORS. PERMANENTLY LABEL UNITS ON ROOF WITH ADDRESS AND LETTER OR NUMBER PER OWNERS PREFERENCE. BLACK MARKER IS NOT PERMANENT. | NANCY | NANCY | | H= | P | 5253930 |
GENE'S HEATING AND AIR LLC | HD | P | 07/19/2016 | INSTALL MOTORIZED DAMPER OR MANUAL VOLUME DAMPER WITH BACK DRAFT DAMPER IN ALL OUTSIDE AIR DUCTS. PERMANENTLY LABEL ALL EQUIPMENT WITH AREA SERVED, UNIT NUMBER ETC. FYI: FOR ALL COMMERCIAL INSPECTIONS YOU WANT TO USE THE "HD" CODE, NOT "HRR".. | NANCY | NANCY | | HD | P | 5248416 |
MARTIN'S PLBG SERVICE, INC | P= | C | 08/01/2016 | correction made | TED | TED | | P= | C | 5258245 |
MARTIN'S PLBG SERVICE, INC | P= | P | 07/29/2016 | need vacuum breaker on laundry sink faucet with hose threads (rest ok) | TED | TED | | P= | P | 5257253 |
MARTIN'S PLBG SERVICE, INC | PTO | C | 06/08/2016 | remodel | TED | TED | | PTO | C | 5217480 |