ART C KLEIN CONSTRUCTION, INC. | B= | C | 05/10/2017 | All other required Final inspections are complete. (This is a computer generated result) | NICK | NICK | | B= | C | 5501262 |
ART C KLEIN CONSTRUCTION, INC. | B= | P | 11/18/2016 | Phase 4A area OK / Need mechanical and fire finals complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), FRONTIER MECHANICAL SYSTEMS INC Mechanical Final Inspection is not Completed yet, HVAC SOLUTIONS, INC. Mechanical Final Inspection is not Completed yet. | NICK | NICK | | B= | P | 5348764 |
ART C KLEIN CONSTRUCTION, INC. | BLA | C | 11/14/2016 | | NICK | NICK | | BLA | C | 5343463 |
ART C KLEIN CONSTRUCTION, INC. | BFR | P | 09/22/2016 | Welding letters on file | NICK | NICK | | BFR | P | 5299582 |
ART C KLEIN CONSTRUCTION, INC. | B= | P | 09/21/2016 | Final for new bathroom OK / Still need final for all other areas of project -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), FOSTER ELECTRIC CORP Electrical Final Inspection is not Completed yet, HVAC SOLUTIONS, INC. Mechanical Final Inspection is not Completed yet. | NICK | NICK | | B= | P | 5299077 |
ART C KLEIN CONSTRUCTION, INC. | BFR | P | 09/21/2016 | Service drive framing OK interior and exterior / Need welding report for this area | NICK | NICK | | BFR | P | 5299073 |
ART C KLEIN CONSTRUCTION, INC. | BIN | P | 09/16/2016 | South East exterior insulation ( R-19 batt and 1" rigid ) OK | NICK | NICK | | BIN | P | 5295751 |
ART C KLEIN CONSTRUCTION, INC. | BFR | P | 08/24/2016 | Letter on file for welding of door way on S1 grid line and for bolts / Frame for service write up area OK / Frame for mezzanine OK / Need all MEP's complete | NICK | NICK | | BFR | P | 5277189 |
HVAC SOLUTIONS, INC. | BSP | T | 07/19/2016 | PAID (REC#1342791) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: splic eto remove mezzanine and add one more service bay delta 8 | DALEH | DALEH | | BSP | T | 5248291 |
ART C KLEIN CONSTRUCTION, INC. | BSP | T | 07/19/2016 | PAID (REC#1343264) PLAN SPLICE FEE: $50 by: SHELLEY for Construction: Revised floor plan to enlarge service bays and reduce mezzanine. | SHELLEY | SHELLEY | | BSP | T | 5248210 |
FOSTER ELECTRIC CORPORATION | BSP | P | 07/19/2016 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: Added third drive-thru lane. ED101, E111, E121, E501, E601, E602 | BERTHA | BERTHA | | BSP | P | 5248145 |
ART C KLEIN CONSTRUCTION, INC. | BFR | P | 07/13/2016 | Frame for bathroom areas OK / Reviewed accessible elements with contractor / Welding letters for bathroom and saddles on file / Need all MEP's complete for bathroom area | NICK | NICK | | BFR | P | 5244016 |
ART C KLEIN CONSTRUCTION, INC. | BBB | C | 07/11/2016 | Bond beam for parapet wall OK | NICK | NICK | | BBB | C | 5241697 |
ART C KLEIN CONSTRUCTION, INC. | BBB | P | 05/17/2016 | Top of wall bond beam OK | NICK | NICK | | BBB | P | 5201150 |
ART C KLEIN CONSTRUCTION, INC. | BBB | P | 05/13/2016 | Bond beam at 9' OK | NICK | NICK | | BBB | P | 5199217 |
ART C KLEIN CONSTRUCTION, INC. | BBB | R | 05/12/2016 | Not ready for inspection, field cancelled | NICK | NICK | | BBB | R | 5198061 |
ART C KLEIN CONSTRUCTION, INC. | BBB | P | 05/10/2016 | #5 dowel 4' oc OK / Base bond beam OK / Still need to see bond beam at 7', 9', and top of wall | NICK | NICK | | BBB | P | 5196021 |
FOSTER ELECTRIC CORPORATION | E= | C | 11/03/2016 | | BRIAN | BRIAN | | E= | C | 5335227 |
FOSTER ELECTRIC CORPORATION | ER | C | 10/31/2016 | CEILINGS---OK | BRIAN | BRIAN | | ER | C | 5331778 |
FOSTER ELECTRIC CORPORATION | ER | P | 10/04/2016 | pre insulation in ceiling phase 2---- | BRIAN | BRIAN | | ER | P | 5309730 |
FOSTER ELECTRIC CORPORATION | ER | P | 09/23/2016 | ceiling in service write up area,see plan,fire alarm and power | JOHNN | JOHNN | | ER | P | 5301727 |
FOSTER ELECTRIC CORPORATION | ER | P | 09/19/2016 | rest of the walls ---ok | BRIAN | BRIAN | | ER | P | 5296238 |
FOSTER ELECTRIC CORPORATION | ER | P | 08/26/2016 | FIRE ALARM----5 DEVICE LETTER---OK | BRIAN | BRIAN | | ER | P | 5278970 |
FOSTER ELECTRIC CORPORATION | ESL | C | 08/24/2016 | FLOOR BOXES IN LOBBY AREA---- | BRIAN | BRIAN | | ESL | C | 5276701 |
FOSTER ELECTRIC CORPORATION | E= | P | 08/24/2016 | BATHROOMS --OK | BRIAN | BRIAN | | E= | P | 5276700 |
FOSTER ELECTRIC CORPORATION | ER | P | 08/24/2016 | UPSTAIRS WALL---OK | BRIAN | BRIAN | | ER | P | 5276692 |
FOSTER ELECTRIC CORPORATION | ER | P | 08/19/2016 | WALLS --SEE PLANS-- | BRIAN | BRIAN | | ER | P | 5273223 |
FOSTER ELECTRIC CORPORATION | ER | P | 07/08/2016 | BATH ROOMS---WALLS AND HARD LID---WITH FIRE ALARM BOXES AND CONDUIT---- | BRIAN | BRIAN | | ER | P | 5240633 |
FRONTIER MECHANICAL SYSTEMS INC | H= | C | 04/21/2017 | CORRECTION MADE | JERRYF | JERRYF | | H= | C | 5482835 |
FRONTIER MECHANICAL SYSTEMS INC | HI | C | 04/21/2017 | CORRECTION MADE | JERRYF | JERRYF | | HI | C | 5482831 |
FRONTIER MECHANICAL SYSTEMS INC | HI | R | 12/16/2016 | GAS CONNECTOR IS STILL NOT CORRECT | JERRYF | JERRYF | | HI | R | 5370191 |
FRONTIER MECHANICAL SYSTEMS INC | HI | R | 12/16/2016 | GAS IS STILL NOT CORRECT | JERRYF | JERRYF | | HI | R | 5370182 |
FRONTIER MECHANICAL SYSTEMS INC | HI | P | 12/15/2016 | NEED GAS CONNECTOR INSTALLED PER INSTALL MANUAL REQUIREMENTS - ATTACH PICTURE OF CORRECTION TO NEXT INSPECTION REQUEST | JERRYF | JERRYF | | HI | P | 5368908 |
HVAC SOLUTIONS, INC. | H= | C | 12/15/2016 | CORRECTIONS MADE | JERRYF | JERRYF | | H= | C | 5368652 |
FRONTIER MECHANICAL SYSTEMS INC | HI | T | 12/14/2016 | PAID (REC#1389279): NEED LADDER FOR ACCESS TO TUBE HEATER AND INSTALL MANUAL - STOPPED INSPECTION - NEED CONTACT INFO FOR ONSITE PERSONNEL FOR LADDER SET UP AND TILE REMOVAL | JERRYF | JERRYF | | HI | T | 5368005 |
HVAC SOLUTIONS, INC. | H= | P | 11/21/2016 | STILL NEED ALL ROOF EQUIPMENT LABELED - TAB REPORT HAS BEEN RECEIVED | JERRYF | JERRYF | | H= | P | 5349337 |
HVAC SOLUTIONS, INC. | H= | P | 11/16/2016 | PARTIAL PENDING TAB REPORT - LABEL ALL ROOF EQUIPMENT - REST OK | JERRYF | JERRYF | | H= | P | 5345944 |
FRONTIER MECHANICAL SYSTEMS INC | HI | P | 11/10/2016 | NEED INSTALL MANUAL TO VERIFY TUBE HEATER LOCATION CLEARANCES - NEED TUBE HEATER GAS FLEX INSTALLED PER MANUAL NOTES: 10# OK - PIPING PER PLAN | JERRYF | JERRYF | | HI | P | 5341635 |
HVAC SOLUTIONS, INC. | H= | P | 09/19/2016 | THIS INSPECTION WAS ONLY FOR THE FOLLOWING - ALL RESTROOM SA/RA AND EXHAUST GRILLES COMPLETE - NEED ALL EQUIPMENT LABELED ON ROOF | JERRYF | JERRYF | | H= | P | 5296504 |
HVAC SOLUTIONS, INC. | HD | P | 08/15/2016 | RTU 1 AND RESTROOM EXHAUST ABOVE CEILING OK | JERRYF | JERRYF | | HD | P | 5268880 |
HVAC SOLUTIONS, INC. | HD | P | 07/26/2016 | STILL NEED TO SEE EXHAUST DUCT FOR BATHROOM GROUP TERMINATE OUT OF THE BUILDING. NOTE: ROUGH DUCT FOR BATHROOMS OK. NO DIFFUSERS AT THIS TIME. | LUKE | LUKE | | HD | P | 5254105 |
HVAC SOLUTIONS, INC. | HD | P | 07/13/2016 | rough duct ok for mens and womens bathrooms, and janitor closet main level ok to wrap.. | LUKE | LUKE | | HD | P | 5244214 |
UNIQUE RADIANT HTG. & PLBG. | P= | C | 09/16/2016 | | TAYLOR | TAYLOR | | P= | C | 5295397 |
UNIQUE RADIANT HTG. & PLBG. | PTO | C | 09/16/2016 | correction made. | TAYLOR | TAYLOR | | PTO | C | 5295394 |
UNIQUE RADIANT HTG. & PLBG. | P= | P | 09/15/2016 | pending PTO inspection. | TAYLOR | TAYLOR | | P= | P | 5294705 |
UNIQUE RADIANT HTG. & PLBG. | PTO | P | 09/15/2016 | need to test vent for floor drains, rest ok. | TAYLOR | TAYLOR | | PTO | P | 5294702 |
UNIQUE RADIANT HTG. & PLBG. | PB | C | 08/22/2016 | trench drains ok. | TAYLOR | TAYLOR | | PB | C | 5275213 |
UNIQUE RADIANT HTG. & PLBG. | P= | P | 08/19/2016 | mens/ womens restrooms and H2O tie in ok. | TAYLOR | TAYLOR | | P= | P | 5274072 |
UNIQUE RADIANT HTG. & PLBG. | PB | P | 08/19/2016 | need to test all 3 inch for floor drains. | TAYLOR | TAYLOR | | PB | P | 5274069 |
UNIQUE RADIANT HTG. & PLBG. | P= | P | 08/10/2016 | need partitions installed, need 17 inches from floor to rim of urinal, undersized H2O tie in, janitor room 108 ok. | TAYLOR | TAYLOR | | P= | P | 5266379 |
UNIQUE RADIANT HTG. & PLBG. | PTO | P | 07/08/2016 | mens room 109, womens room 110, janitor room 108 ok, check water heater and H2O tie in by final, note: still need mechanical permit attached. | TAYLOR | TAYLOR | | PTO | P | 5241078 |
UNIQUE RADIANT HTG. & PLBG. | PB | P | 04/26/2016 | mens room 109, womens room 110, janitor room 108 ok. | TAYLOR | TAYLOR | | PB | P | 5185239 |
UNIQUE RADIANT HTG. & PLBG. | PB | P | 04/25/2016 | under floor to unfinished area o.k, still need elec and mechanical attachments | JOEL | JOEL | | PB | P | 5183316 |
UNIQUE RADIANT HTG. & PLBG. | PB | T | 04/20/2016 | PAID (REC#1324730) AFTER-HOURS INSPECTION: $200 From: TERRI 4/24/16 12-3 p.m. | TERRI | TERRI | | PB | T | 5180462 |