J. E. DUNN CONSTRUCTION COMPANY | B= | C | 05/23/2016 | All other required Final inspections are complete. (This is a computer generated result) | BERTW | BERTW | | B= | C | 5206096 |
J. E. DUNN CONSTRUCTION COMPANY | B= | P | 05/20/2016 | . Additional Inspections Required (computer generated): HEATING & PLUMBING ENGRS, INC Mechanical Final Inspection is not Completed yet. | BERTW | BERTW | | B= | P | 5204351 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 05/10/2016 | Double layer 5/8 type x on top side of assembly OK / Still need to see double layer on bottom side of lid assembly / Need mechanical to inspect 2 dampers being installed | NICK | NICK | | BSP | P | 5195508 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | T | 05/05/2016 | PAID (REC#1327891) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: revision to damper in soiled linen area | DALEH | DALEH | | BSP | T | 5192631 |
J. E. DUNN CONSTRUCTION COMPANY | BSP | P | 05/05/2016 | PLAN SPLICE: (No Fee) by: DANM for Construction: Revised UL listed assembly for ceiling | DANM | DANM | | BSP | P | 5192619 |
J. E. DUNN CONSTRUCTION COMPANY | B16 | C | 04/12/2016 | DISCUSSED WITH MARTY FROM DUNN ABOUT PENETRATIONS OF DUCTS IN SOIL ROOM CEILING. THE ARCHITECT AND THE MECHANICAL ENGINEER NEED TO FIND A OPENING PROTECTIVE FIRE DAMPER THAT IS SPECIFICALLY LISTED FOR A HORIZONTAL APPLICATION AS A THROUGH PENETRATION FOR THE UL LISTING SHOWN BY THE ARCHITECT ON THE A-SHEET DETAIL. | JON | JON | | B16 | C | 5175604 |
J. E. DUNN CONSTRUCTION COMPANY | BFR | P | 04/11/2016 | lid framing and core board ok/ wall below lid ok/ need mech and electric contractors attached to this permit and inspections performed. Lid has 2 fire dampers on approved plans that are not listed for this application-reviewed with Nark job super he is going to call Senior Mech inspector Jon | BERTW | BERTW | | BFR | P | 5174142 |
E LIGHT ELECTRIC SERVICES, INC | E= | C | 04/14/2016 | 7th floor meds room , utility room , ---------- OK | CRAIGS | CRAIGS | | E= | C | 5176953 |
HEATING & PLUMBING ENGINEERS, INC | H= | C | 12/28/2016 | NO BALANCE REPORT REQUIRED | JON | JON | | H= | C | 5377588 |
HEATING & PLUMBING ENGINEERS, INC | HE | L | 12/23/2016 | Renewed online for 1/2 Fee at 12/23/2016 11:07:46 AM (RECEIPT #: 1391287) | WEBSITE | WEBSITE | | HE | L | 5376097 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 05/23/2016 | NEED BALANCE REPORT | JON | JON | | H= | P | 5206095 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 05/19/2016 | NEED BALANCE REPORT. NEED ATTACHED PICTURES ON INSPECTION REQUEST FOR BOTTOM SIDE RETAINING ANGLES AND INSTALLED AIR REGISTER. | JON | JON | | HD | P | 5204041 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 05/12/2016 | framing ok for 2 dampers in ceiling. see again when dampers installed and lower retaining angles are not installed to see drywall and expansion room. | JON | JON | | HD | P | 5198063 |