PEAK PROFESSIONAL CONTRS INC | B= | C | 03/06/2017 | All other required Final inspections are complete. (This is a computer generated result) | JEREMYA | JEREMYA | | B= | C | 5432170 |
PEAK PROFESSIONAL CONTRS INC | B= | P | 12/21/2016 | Shell permit complete. Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977), External Agency Inspection HD= by HEALTHDEPT is not Completed yet. | JEREMYA | JEREMYA | | B= | P | 5374135 |
AIRTECH MECHANICAL, INC. | BSP | P | 12/02/2016 | ADDITIONAL PLAN REVIEW TIME:From: DALEH splice to relocate rtus and gas piping | DALEH | DALEH | | BSP | P | 5358918 |
PEAK PROFESSIONAL CONTRS INC | BSP | P | 12/02/2016 | Splice: Revised roof framing for relocated RTU's | DANM | DANM | | BSP | P | 5358913 |
PEAK PROFESSIONAL CONTRS INC | BSP | P | 11/28/2016 | Trash enclosure needs it's own permit. Not attached to building foundation. | JEREMYA | JEREMYA | | BSP | P | 5353976 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 11/15/2016 | Core/Shell framing complete / Letter for all bolted/welded structural connections on file / Pending other rough inspections | JEREMYA | JEREMYA | | BFR | P | 5344870 |
ELECTRIC TECH INC. | BSP | T | 11/08/2016 | PAID (REC#1384223) PLAN SPLICE FEE: $50 by: SHELBY for Electrical: Omit main disconnects | SHELBY | SHELBY | | BSP | T | 5339732 |
LANDMARK PLUMBING AND HEATING, INC. | BSP | T | 10/13/2016 | PAID (REC#1371969) PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Revised gas piping plan | JUSTINC | JUSTINC | | BSP | T | 5318404 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 10/12/2016 | north side of interior shear wall ok | ERICR | ERICR | | BFR | P | 5316520 |
PEAK PROFESSIONAL CONTRS INC | BIN | C | 10/12/2016 | | ERICR | ERICR | | BIN | C | 5316507 |
PEAK PROFESSIONAL CONTRS INC | BBB | C | 10/03/2016 | All bond beams at patio fireplace OK / Open hole reports on file for canopy pads, trash enclosure and patio enclosure | JEREMYA | JEREMYA | | BBB | C | 5308850 |
PEAK PROFESSIONAL CONTRS INC | BFT | P | 09/16/2016 | Footings at new addition OK pending open hole for this area | JEREMYA | JEREMYA | | BFT | P | 5295492 |
PEAK PROFESSIONAL CONTRS INC | BSP | T | 08/23/2016 | PAID (REC#1352533) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Revise walls add fireplace | MICHAELA | MICHAELA | | BSP | T | 5275469 |
PEAK PROFESSIONAL CONTRS INC | BFT | P | 08/03/2016 | Footings for trash enclosure OK. Balance of footings for job complete. Partial pending stamped open hole | JEREMYA | JEREMYA | | BFT | P | 5261111 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 07/19/2016 | Exterior bumpouts, cornices and aesthetic framing OK | JEREMYA | JEREMYA | | BFR | P | 5248747 |
PEAK PROFESSIONAL CONTRS INC | BSP | P | 07/01/2016 | 4" rigid foam insulation per comm check | JEREMYA | JEREMYA | | BSP | P | 5236658 |
PEAK PROFESSIONAL CONTRS INC | BFT | P | 06/29/2016 | Canopy pads OK / Open hole to follow | JEREMYA | JEREMYA | | BFT | P | 5234430 |
PEAK PROFESSIONAL CONTRS INC | BSP | T | 06/29/2016 | PAID (REC#1338770) PLAN SPLICE FEE: $50 by: JIMA for Construction: SPLICE : CHANGED IECC FORM | JIMA | JIMA | | BSP | T | 5234227 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 06/22/2016 | Parapet framing at entire building OK / Shear wall at SE corner of building OK | JEREMYA | JEREMYA | | BFR | P | 5228335 |
PEAK PROFESSIONAL CONTRS INC | BFN | P | 06/22/2016 | Open hole on file / Need all third party inspection letters | JEREMYA | JEREMYA | | BFN | P | 5228331 |
PEAK PROFESSIONAL CONTRS INC | BFI | C | 04/28/2016 | Rigid foam insulation OK | JEREMYA | JEREMYA | | BFI | C | 5187263 |
PEAK PROFESSIONAL CONTRS INC | BFN | P | 04/25/2016 | Foundation walls OK. Partial for future | JEREMYA | JEREMYA | | BFN | P | 5183953 |
PEAK PROFESSIONAL CONTRS INC | BFT | P | 04/19/2016 | South half of footing OK / Need letter for third party observations and for open hole / Eufer in place | JEREMYA | JEREMYA | | BFT | P | 5180033 |
PEAK PROFESSIONAL CONTRS INC | BFT | P | 04/15/2016 | AUTHORIZED THIRD PARTY INSPECTIONS | JEREMYA | JEREMYA | | BFT | P | 5178680 |
ELECTRIC TECH INC. | E= | C | 11/22/2016 | | TOMC | TOMC | | E= | C | 5351095 |
ELECTRIC TECH INC. | ES | C | 10/21/2016 | Commercial Service: (2) 1200 amp 3 phase services: ok to set meters for: 100,130,150,170,180 and house | MATTHEW | MATTHEW | | ES | C | 5324923 |
ELECTRIC TECH INC. | ES | R | 10/19/2016 | plans need to be revised; shows 2 main disconnects, need ct meter for 600 amp service, can't have dirt around ufer rebar, complete re-inspect once plans are revised | MATTHEW | MATTHEW | | ES | R | 5322253 |
ELECTRIC TECH INC. | ES | R | 10/14/2016 | need ufer ground found or new one | GARYL | GARYL | | ES | R | 5318821 |
ELECTRIC TECH INC. | EUG | P | 09/30/2016 | west and south walkway lights | MATTHEW | MATTHEW | | EUG | P | 5307310 |
ELECTRIC TECH INC. | ER | P | 09/01/2016 | exterior cans light east and west soffits ok | MATTHEW | MATTHEW | | ER | P | 5283221 |
ELECTRIC TECH INC. | EUG | P | 07/22/2016 | north and west pole lights and landscape lighting ok | MATTHEW | MATTHEW | | EUG | P | 5251764 |
ELECTRIC TECH INC. | EUG | P | 07/18/2016 | 3 pvc conduits riser room to outside footed | MATTHEW | MATTHEW | | EUG | P | 5247279 |
ELECTRIC TECH INC. | EUG | P | 05/03/2016 | PVC along footer ran for sub panels, building southwest of Circle K,,,,,,, | GARYL | GARYL | | EUG | P | 5190801 |
LANDMARK PLUMBING AND HEATING, INC. | H= | C | 12/20/2016 | GAS COMPLETE MATCHES MECHANICAL SPLICE.. | LUKE | LUKE | | H= | C | 5372588 |
AIRTECH MECHANICAL, INC. | H= | C | 12/02/2016 | MECHANICAL FINAL OK. | NANCY | NANCY | | H= | C | 5359579 |
LANDMARK PLUMBING AND HEATING, INC. | HC | C | 11/15/2016 | OK TO SET ALL METERS. PEAK PROFESSIONAL WANTS UNIT 100 AND 107 SET FOR THE SHELL. I AM RELEASING ALL METERS, YOU CAN SET THE ONES YOU WANT. PLEASE PROVIDE THE 2 LB APPROVAL LETTERS FOR ALL SUITES ON THIS BUILDING. SORRY FOR THE CONFUSION. CALL ME IF YOU NEED. THANKS. | NANCY | NANCY | | HC | C | 5344270 |
LANDMARK PLUMBING AND HEATING, INC. | HC | C | 11/14/2016 | OK TO SET MEDIUM PRESSURE METER FOR UNIT 170 ONLY. REQUESTING GAS CONTRACTOR TO ONLY PROVIDE A MEDIUM PRESSURE LETTER FOR UNIT 170 AT THIS TIME. ALL OTHER METERS TO BE RELEASED UNDER TENANT FINISH PERMITS. | NANCY | NANCY | | HC | C | 5343556 |
LANDMARK PLUMBING AND HEATING, INC. | HI | C | 11/14/2016 | NEED REVISED/APPROVED PRINTS SHOWING RELOCATED UNITS AND GAS LINES TO FUTURE SUITES 170 AND 180. FIVE 10 LB TESTS OK. GAS INSTALLED AS PER PRINTS EXCEPT FOR SUITES 170 AND 180. WILL RELEASE METER FOR UNIT 170 ONLY. NEED LETTER FROM CSU APPROVING MEDIUM PRESSURE FOR 170. | NANCY | NANCY | | HI | C | 5343548 |
AIRTECH MECHANICAL, INC. | H= | P | 10/13/2016 | Note added by NS 11/29/16: Changed inspection back to partial due to still need revised/approved prints. HEATER INSTALLED IN FIRE RISER ROOM.. | LUKE | LUKE | | H= | P | 5317447 |
AIRTECH MECHANICAL, INC. | H= | P | 10/12/2016 | LOCKED NO ACCESS.. | LUKE | LUKE | | H= | P | 5317278 |
AIRTECH MECHANICAL, INC. | H= | P | 07/20/2016 | MECHANICAL FINAL OK PENDING INSTALLATION OF HEATER IN FIRE RISER ROOM. ROOF ALL OK. NOTE: SMOKE DETECTORS INSTALLED IN ALL UNITS/RETURN DUCTS. | NANCY | NANCY | | H= | P | 5249703 |
AIRTECH MECHANICAL, INC. | H= | P | 07/18/2016 | NO ACCESS TO ROOF TODAY. ALREADY RESCHEDULED FOR WEDNESDAY PER JOE. | NANCY | NANCY | | H= | P | 5247766 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 12/16/2016 | | TIM | TIM | | P= | C | 5370051 |
LANDMARK PLUMBING AND HEATING, INC. | P= | P | 12/15/2016 | in water meter room--complete back drains, install trap guard | TED | TED | | P= | P | 5369421 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 12/15/2016 | core and shell | TED | TED | | PTO | C | 5369413 |
LANDMARK PLUMBING AND HEATING, INC. | PRD | C | 08/05/2016 | roof drains | TED | TED | | PRD | C | 5263174 |
LANDMARK PLUMBING AND HEATING, INC. | PB | C | 07/08/2016 | revise plan to show 5 units instead of six | JOEL | JOEL | | PB | C | 5240741 |